10kV indoor busbar-type epoxy resin cast current transformer. Through-core design for easy installation on busbars. Rated insulation level 12/42/75kV, 50/60Hz, secondary current 5A or 1A. Compliant with IEC 61869 and GB/T 20840 standards. Vacuum epoxy casting process, low partial discharge, reliable performance. Suitable for medium voltage switchgear, customizable ratio and accuracy.
LMZ9-10 is a 10kV indoor busbar-type current transformer with epoxy cast insulation, suitable for medium voltage switchgear applications.
| Paramètre | Spécification | Vérification |
|---|---|---|
| Type de produit | Current Transformer | IEC 61869, GB/T 20840 |
| Code modèle | LMZ9-10 | Marquage de la plaque constructeur |
| Tension primaire | 10kV | Essai de tension nominale (IEC 61869-1/3) |
| Tension secondaire | 5A or 1A | Vérification du rapport à la fréquence nominale |
| Classe de précision | [On Request] | Essai de précision (IEC 61869-2 / IEEE C57.13) |
| Charge nominale | [On Request] | Essai de charge à la puissance VA nominale |
| Type d'isolement | Dry Epoxy Resin | Essais diélectriques selon la norme |
| Niveau d'isolement (BIL) | 12/42/75kV | Tenue à fréquence industrielle et au choc de foudre |
| Normes | IEC 61869, GB/T 20840 | Certifié selon les normes listées |
| Fréquence | 50/60Hz | Selon IEC 61869-1 |
| Environnement | Indoor busbar-type epoxy resin cast | Selon les limites de la fiche technique |
Idéal pour
Non recommandé pour
For current transformer (CT) wiring: Connect primary busbar through the window. Secondary terminals are 1S1 and 1S2 for the main winding; if dual ratio, additional taps may be present. Ensure secondary is never open-circuited while energized - hazardous voltage can occur. Ground the secondary circuit at one point only, preferably at the CT terminal box, to ensure safety and proper operation. Follow IEC 61869-2 and IEEE C57.13 for terminal markings and connections.
Conforme à : IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q : What is the insulation level of LMZ9-10?
R : The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, and 75kV lightning impulse withstand.
Q : Can LMZ9-10 be used outdoors?
R : No, it is designed for indoor use only. Outdoor installation would require additional weatherproofing.
Q : What are the secondary current options?
R : The secondary current can be 5A or 1A, as specified.
Les champs manquants sont marqués [On Request] — jamais inventés. Les lignes de vérification M2/M5/M6 suivent les conventions IEC 61869 / IEEE C57.13.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 (0.2 (S)) | Accuracy class & rated output (VA) COSφ=0.8 (0.5 (S)) | Accuracy class & rated output (VA) COSφ=0.8 (5 (10)P10) | Weight (kg) |
|---|---|---|---|---|---|
| 400~800 | 0.2(S) 0.5(S) 5(10)P10 | 3VA | 3VA | 2VA | 5 |

Dessin d'encombrement et de dimensions du LMZ9-10 — cliquez sur l'image pour zoomer / afficher l'original.