Indoor zero sequence current transformer for 35kV and below systems. Used for three-phase cable ground protection in small grounding current systems. Can also be used with relay protection devices. Rated frequency 50Hz or 60Hz. Available in Φ80 to Φ240 inner diameter sizes. Split design with clamp fastening, can be installed without power interruption. Compliant with IEC 61869 and GB/T 20840 standards. Epoxy resin cast construction, suitable for indoor installation.
Indoor split-core zero-sequence CT for 35kV systems, ideal for retrofit earth-fault protection on cables without service interruption.
| Paramètre | Spécification | Vérification |
|---|---|---|
| Type de produit | Current Transformer | IEC 61869, GB/T 20840 |
| Code modèle | LXK80-240 | Marquage de la plaque constructeur |
| Tension primaire | Up to 35kV | Essai de tension nominale (IEC 61869-1/3) |
| Tension secondaire | [On Request] | Vérification du rapport à la fréquence nominale |
| Classe de précision | [On Request] | Essai de précision (IEC 61869-2 / IEEE C57.13) |
| Charge nominale | [On Request] | Essai de charge à la puissance VA nominale |
| Type d'isolement | Dry Epoxy Resin | Essais diélectriques selon la norme |
| Niveau d'isolement (BIL) | [On Request] | Tenue à fréquence industrielle et au choc de foudre |
| Normes | IEC 61869, GB/T 20840 | Certifié selon les normes listées |
| Fréquence | 50/60Hz | Selon IEC 61869-1 |
| Environnement | [On Request] | Selon les limites de la fiche technique |
Idéal pour
Non recommandé pour
For zero-sequence CTs, the three-phase cables must pass through the window together, with the secondary winding connected to a relay or protection device. Terminals are typically marked 1S1 and 1S2; ensure polarity is consistent with the protection scheme. Never open-circuit the secondary of a CT while energized - hazardous voltage may occur. Ground the secondary winding at one point to ensure safety and proper operation.
Conforme à : IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q : What is the maximum system voltage for this CT?
R : It is rated for systems up to 35kV, with insulation level to be confirmed for specific models.
Q : Can it be installed without power interruption?
R : Yes, the split-core design with clamp fastening allows hot-line installation.
Q : What inner diameters are available?
R : The CT is available in Φ80 to Φ240 mm inner diameter sizes.
Les champs manquants sont marqués [On Request] — jamais inventés. Les lignes de vérification M2/M5/M6 suivent les conventions IEC 61869 / IEEE C57.13.
| Rated current ratio (A) | Accuracy class | Rated output (VA) |
|---|---|---|
| 60-75/1 | 10P5 | 2.5 |
| 100/1 | 10P5 | 3.75 |
| 150/1 | 10P5 | 2.5 |
| 200/1-300/1 | 10P10 | 3.75 |
| 400/1-600/1 | 10P10 | 5 |
| 100/5 | 10P5 | 2.5 |
| 150-200/5 | 10P5 | 2.5 |
| 300/5-400/5 | 10P10 | 3.75 |
| 500/5 | 10P10 | 5 |
| 600/5 | 10P10 | 5 |

Dessin d'encombrement et de dimensions du LXK80-240 — cliquez sur l'image pour zoomer / afficher l'original.