Indoor epoxy resin casting current transformer designed for CGIS gas insulated switchgear, with multiple accuracy class, rated burden and primary current options.
CGIS3808是一款专为CGIS气体绝缘开关柜设计的户内电流互感器,额定电压12kV,二次侧输出5A或1A,频率支持50/60Hz。其绝缘方式为干式环氧树脂浇注,结构为大型深矩形外壳,宽度345mm,适合高电流等级应用。准确级组合包括0.2FS10/0.5SFS10、0.5、5(10)P10、5(10)P20、5(10)P30,覆盖测量与保护需求。该产品适用于12kV电力系统的计量、测量及继电保护,典型部署于CGIS开关柜内部。
| Paramètre | Spécification | Vérification |
|---|---|---|
| Type de produit | Current Transformer | [On Request] |
| Code modèle | CGIS3808 | Marquage de la plaque constructeur |
| Tension primaire | 12kV | Essai de tension nominale (IEC 61869-1/3) |
| Tension secondaire | 5A or 1A | Vérification du rapport à la fréquence nominale |
| Classe de précision | 0.2FS10/0.5SFS10,0.5,5(10)P10,5(10)P20,5(10)P30 | Essai de précision (IEC 61869-2 / IEEE C57.13) |
| Charge nominale | [On Request] | Essai de charge à la puissance VA nominale |
| Type d'isolement | Dry Epoxy Resin | Essais diélectriques selon la norme |
| Niveau d'isolement (BIL) | [On Request] | Tenue à fréquence industrielle et au choc de foudre |
| Normes | [On Request] | Certifié selon les normes listées |
| Fréquence | 50/60Hz | Selon IEC 61869-1 |
| Environnement | [On Request] | Selon les limites de la fiche technique |
Idéal pour
Non recommandé pour
警告:电流互感器(CT)二次侧严禁开路!在运行中,若二次回路开路,将产生危险的高电压,危及人身和设备安全。因此,二次侧端子(1S1/1S2)必须可靠连接,且当未接入负荷(如仪表、继电器等)时,应将二次端子短接并接地。接线时,应确保极性正确,一次侧P1流入,二次侧1S1流出,以保证保护方向正确。二次回路应使用铜芯导线,截面不小于2.5mm²,且回路中不得装设熔断器。安装时,应确保互感器固定牢靠,避免振动。接地:二次回路必须有一点可靠接地,通常将1S2端接地。接线方式:根据保护或测量需求,可采用星形或三角形接线,但必须保证二次负荷不超过额定值。请遵循IEC 61869-2或IEEE C57.13相关要求,并由专业人员进行安装和调试。 ⚠️ Safety: Never open-circuit the secondary of a CT while energized — hazardous voltage develops.
Conforme à : [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q : 该电流互感器的额定一次电流是多少?
R : 额定一次电流未在规格中明确,请提供具体参数或咨询制造商,否则为[On Request]。
Q : 该互感器的准确级有哪些?
R : 准确级包括0.2FS10、0.5SFS10、0.5、5(10)P10、5(10)P20、5(10)P30,具体组合可选。
Q : 该互感器适用于什么绝缘系统?
R : 采用干式环氧树脂绝缘,适用于CGIS气体绝缘开关设备。
Q : 该互感器的二次额定电流是多少?
R : 二次额定电流为5A或1A,可根据需求选择。
Q : 该互感器的额定频率是多少?
R : 额定频率为50/60Hz。
Q : 该互感器的安装尺寸如何?
R : 外形为345mm宽的大型矩形外壳,具体安装尺寸请参考技术图纸或咨询制造商。
Q : 该互感器是否适用于高电流等级?
R : 是的,该互感器支持高电流等级,具体额定一次电流范围请咨询制造商。
Les champs manquants sont marqués [On Request] — jamais inventés. Les lignes de vérification M2/M5/M6 suivent les conventions IEC 61869 / IEEE C57.13.
| Accuracy classCombined | Rated output (VA) | 400 | 500 | 800 | 1000 | 1200 | 1500 | 2000 | 2500 | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| h | l | h | l | h | l | h | l | h | l | h | l | h | l | h | l | ||
| 0.2FS10 / 0.5FS10 | 2.5 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 |
| 5 | 30 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 7.5 | 35 | 35 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 10 | 40 | 40 | 35 | 35 | 30 | 30 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 15 | 45 | 45 | 40 | 40 | 35 | 35 | 30 | 30 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | |
| 20 | 55 | 55 | 50 | 50 | 40 | 40 | 35 | 35 | 35 | 35 | 25 | 25 | 25 | 25 | 25 | 25 | |
| 25 | 65 | 65 | 55 | 55 | 45 | 45 | 40 | 40 | 40 | 40 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 30 | 75 | 75 | 80 | 80 | 50 | 50 | 45 | 45 | 40 | 40 | 35 | 35 | 30 | 30 | 25 | 25 | |
| 0.5FS10 | 2.5 | 25 | 25 | 25 | 20 | 20 | 20 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 30 |
| 5 | 30 | 30 | 25 | 25 | 20 | 20 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 7.5 | 35 | 35 | 30 | 30 | 20 | 20 | 20 | 20 | 20 | 20 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 10 | 40 | 40 | 35 | 35 | 25 | 25 | 20 | 20 | 20 | 20 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 15 | 45 | 45 | 40 | 40 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | |
| 20 | 55 | 55 | 50 | 50 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | |
| 25 | 65 | 65 | 55 | 55 | 35 | 35 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | |
| 30 | 75 | 75 | 60 | 60 | 40 | 40 | 35 | 35 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | |
| 5P10 / 10P10 | 2.5 | 25 | 25 | 20 | 20 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 |
| 5 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 7.5 | 35 | 35 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 10 | 40 | 40 | 35 | 35 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 15 | 55 | 55 | 50 | 50 | 35 | 35 | 35 | 35 | 35 | 35 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 20 | 70 | 70 | 60 | 60 | 40 | 40 | 40 | 40 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | |
| 25 | 80 | 80 | 70 | 70 | 50 | 50 | 45 | 45 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | |
| 30 | 95 | 95 | 80 | 80 | 70 | 70 | 50 | 50 | 45 | 45 | 40 | 40 | 40 | 40 | 40 | 40 | |
| 5P20 / 10P20 | 2.5 | 35 | 35 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 30 |
| 5 | 45 | 45 | 40 | 40 | 30 | 30 | 35 | 35 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | |
| 7.5 | 60 | 60 | 50 | 50 | 35 | 35 | 40 | 40 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | |
| 10 | 75 | 75 | 65 | 65 | 45 | 45 | 45 | 45 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | |
| 15 | 100 | 100 | 75 | 75 | 55 | 55 | 55 | 55 | 50 | 50 | 45 | 45 | 45 | 45 | 45 | 45 | |
| 20 | 125 | 125 | 95 | 95 | 75 | 75 | 65 | 65 | 60 | 60 | 55 | 55 | 50 | 50 | 50 | 50 | |
| 25 | 125 | 125 | 110 | 110 | 90 | 90 | 75 | 75 | 70 | 70 | 65 | 65 | 55 | 55 | 55 | 55 | |
| 30 | 130 | 130 | 120 | 120 | 100 | 100 | 90 | 90 | 75 | 75 | 70 | 70 | 60 | 60 | 55 | 55 | |
| 5P30 / 10P30 | 2.5 | 45 | 45 | 40 | 40 | 35 | 35 | 35 | 35 | 35 | 35 | 30 | 30 | 32 | 32 | 32 | 32 |
| 5 | 70 | 70 | 60 | 60 | 45 | 45 | 45 | 45 | 40 | 40 | 40 | 40 | 37 | 37 | 37 | 37 | |
| 7.5 | 90 | 90 | 75 | 75 | 55 | 55 | 50 | 50 | 45 | 45 | 42 | 42 | 37 | 37 | 37 | 37 | |
| 10 | 110 | 110 | 85 | 85 | 65 | 65 | 55 | 55 | 50 | 50 | 47 | 47 | 42 | 42 | 42 | 42 | |
| 15 | 125 | 125 | 115 | 115 | 90 | 90 | 80 | 80 | 70 | 70 | 60 | 60 | 53 | 53 | 48 | 48 | |
| 20 | 140 | 140 | 110 | 110 | 100 | 100 | 85 | 85 | 75 | 75 | 62 | 62 | 58 | 58 | 58 | 58 | |
| 25 | 135 | 135 | 115 | 115 | 100 | 100 | 85 | 85 | 72 | 72 | 62 | 62 | 62 | 62 | 62 | — | |
| 30 | 135 | 135 | 115 | 115 | 95 | 95 | 85 | 85 | 72 | 72 | 62 | 62 | 62 | 62 | 62 | — | |

Dessin d'encombrement et de dimensions du CGIS3808 — cliquez sur l'image pour zoomer / afficher l'original.