Transformator arus resin epoksi cor satu fasa dalam ruangan, sesuai dengan GB/T20840.1/2 & IEC61869-1/2, tingkat isolasi 12/42/75kV, 50/60Hz, arus sekunder 5A/1A. Rentang arus primer opsional: 20-200A, 300-400A, 500-600A, 800-1000A, 1200-1250A, 1500-3150A; opsi keluaran nominal lebih kaya untuk belitan proteksi, berat bersih 80kg, suhu operasi -5°C hingga +40°C.
Transformator arus cetakan epoksi 12kV dalam ruangan untuk switchgear MV; cocok untuk pengukuran dan proteksi hingga arus primer 3150A.
| Parameter | Spesifikasi | Verifikasi |
|---|---|---|
| Jenis Produk | Transformator Arus | IEC 61869 / GB/T 20840 |
| Kode Model | LZZBJ9-12-225b-4s | Penandaan pabrik |
| Tegangan Primer | 12kV | Uji tegangan nominal (IEC 61869-1/3) |
| Arus Sekunder | 5A/1A | Pemeriksaan rasio pada frekuensi nominal |
| Kelas Akurasi | 0.2/0.5/1.0 | Uji akurasi (IEC 61869-2 / IEEE C57.13) |
| Beban Nominal | [On Request] | Uji beban pada VA nominal |
| Jenis Isolasi | Dry Epoxy Resin | Uji dielektrik sesuai standar |
| Tingkat Isolasi (BIL) | [On Request] | Ketahanan frekuensi daya & impuls petir |
| Standar | IEC 61869 / GB/T 20840 | Tersertifikasi sesuai standar yang tercantum |
| Frekuensi | 50/60Hz | Sesuai IEC 61869-1 |
| Lingkungan | [On Request] | Sesuai batas lembar data |
Ideal Untuk
Tidak Direkomendasikan Untuk
Untuk CT: Hubungkan primer melalui bushing; terminal sekunder adalah 1S1/1S2 untuk pengukuran, dan 2S1/2S2 untuk proteksi jika ada. Jangan pernah membuka rangkaian sekunder CT saat bertegangan - tegangan berbahaya. Tanahkan belitan sekunder pada satu titik. Ikuti konvensi terminal IEC 61869. ⚠️ Safety: Follow the nameplate terminal diagram and ground the secondary winding at one point.
Sesuai dengan: IEC 61869 / GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
T: Apa tingkat isolasi CT ini?
J: Tingkat isolasi adalah 12/42/75kV, yang berarti tegangan sistem 12kV, tahan tegangan frekuensi daya 42kV, dan tahan impuls petir 75kV.
T: Rentang arus primer apa yang tersedia?
J: Rentang opsional meliputi 20-200A, 300-400A, 500-600A, 800-1000A, 1200-1250A, 1500-3150A.
T: Apakah dapat digunakan di luar ruangan?
J: Tidak, ini dirancang hanya untuk penggunaan dalam ruangan.
Bidang yang hilang ditandai [Atas Permintaan] — tidak pernah direkayasa. Baris verifikasi M2/M5/M6 mengikuti konvensi IEC 61869 / IEEE C57.13.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA)COSφ=0.8 | Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 200-200 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 150 | 375 | 82 |
| 300 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 31.5 | 80 | 82 |
| 400 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 45 | 112.5 | 82 |
| 500-600 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 63 | 130 | 82 |
| 800-1000 | 0.2(5)/0.5/5P/5P | 30 30 40 30 20 | 80 | 160 | 82 |
| 1200-3150 | 0.2(5)/0.5/5P/5P | 30 30 40 30 20 | 100 | 160 | 82 |

Gambar dimensi & garis besar LZZBJ9-12-225b-4s — klik gambar untuk memperbesar / melihat asli.
LZZBJ9-12/225b/4s completes the 12 kV four-core trio with the 195b and 198b. It is specified from 200 A to 3150 A, with 20 VA on the metering cores, 25 VA on the first protection core and 15–20 VA on the remainder, rising to 30/40/20 VA in the 800 A and above bands.
The accuracy string is 0.2(5)/0.5/5P/5P, and the short-time thermal current climbs from 150 kA at 200 A to 100 kA with a 160 kA dynamic rating at 1200–3150 A. The unit weighs 82 kg and is cast in the same dry epoxy as the rest of the family, so no oil maintenance applies.
Treat 225b as a frame choice, not a performance upgrade: it shares the electrical table with 195b and 198b and differs in the casting that determines how it sits in the switchgear. When a project mixes the three across feeders, keep the frame code on the nameplate so maintenance can match replacements.
Keluarga produk sama, rating berbeda — bandingkan sebelum menentukan spesifikasi.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan, 12kV
Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2. Tingkat isolasi: 12/42/75kV, frekuensi 50/60Hz, arus sekunder 5A atau 1A. Rentang arus primer opsional: 5-100A、150A、200-300A、400-600A、800-1200A、1500-2500A. Berbagai kombinasi kelas akurasi termasuk 0,2S/0,5S dan kelas proteksi, dengan arus tahan termal & dinamis jangka pendek yang sesuai untuk setiap rentang, cocok untuk pengukuran dan proteksi relai pada kabinet switchgear tegangan menengah. Suhu operasi lingkungan: -5°C hingga +40°C, berat bersih 25kg.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan
Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2; tingkat isolasi nominal 24/65/125kV, frekuensi nominal 50/60Hz, arus sekunder nominal 5A atau 1A. Arus primer opsional mencakup 20–2000A; keluaran nominal kelas akurasi: 10VA untuk 0,2(S)/0,5(S), 15VA untuk 10P15; arus termal jangka pendek berkisar 31,5–100kA, arus tahan dinamis nominal berkisar 80–160kA; berat produk: 36,5kg; suhu operasi lingkungan -5°C hingga +40°C.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan
Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2; tingkat isolasi nominal 24/65/125kV, frekuensi nominal 50/60Hz, arus sekunder nominal 5A atau 1A. Dua struktur opsional: 2s dan 4s; rentang arus primer opsional 20-2500A. Untuk tipe 2s: keluaran nominal 10-20VA pada berbagai kelas akurasi, berat 36kg; untuk tipe 4s: keluaran nominal 15-20VA pada berbagai kelas akurasi, berat 50kg; arus termal jangka pendek: 31,5-100kA, arus tahan dinamis nominal: 80-160kA; suhu operasi lingkungan -5°C hingga +40°C.