中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZBJ9-12-225b-4s
LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV
12kVLZZBJ9-12-225b-4s
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 12kV
Secondary Metering (1S1 - 1S2):5A/1A (0.2/0.5/1.0)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZBJ9-12-225b-4s

LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV

LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-225b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Key Engineering Advantages

  • 12kV insulation
  • epoxy casting
  • high protection-grade output
  • weight 80kg
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZBJ9-12-225b-4s

Electrical Parameters

Primary Rated Voltage (Un):12kV
Secondary Winding Currents:5A/1A
Metering & Protection Class:0.2/0.5/1.0
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Standards Conformance:IEC 61869 / GB/T 20840
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

12 kV four-core epoxy-cast CT, 200–3150 A, third frame variant of the 195b/198b design, 82 kg.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 61869 / GB/T 20840
Model CodeLZZBJ9-12-225b-4sFactory nameplate marking
Primary Voltage12kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class0.2/0.5/1.0Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 61869 / GB/T 20840Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium-voltage switchgear panels
  • Metering and protection applications at 12kV class
  • Primary current ranges from 20A to 3150A
  • Systems with 50/60Hz frequency

Not Recommended For

  • Outdoor installations
  • High-voltage systems above 12kV
  • DC applications
  • Gas-insulated switchgear (GIS) without adaptation

Topology & Wiring

Connect primary through the bushing; secondary terminals are 1S1/1S2 for metering, and 2S1/2S2 for protection if present. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 terminal conventions.

Standards & Compliance

Compliant with: IEC 61869 / GB/T 20840

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: Does the 225b offer higher ratings than the 195b?

A: No. The ratings are shared across the three frames; the difference is mechanical, not electrical.

Q: What is the rated output at 800 A and above?

A: 30 VA, 30 VA, 40 VA, 30 VA and 20 VA across the five cores.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZBJ9-12-225b-4s
6 cols · 6 rows

LZZBJ9-12/198b/4s Current Transformer — Technical Data

Rated primary current (A)Accuracy classCombinedAccuracy class & rated output (VA)COSφ=0.8Short-time thermal current (kA)Rated dynamic current (kA)Weight (kg)
200-2000.2(5)/0.5/5P/5P20 20 25 20 1515037582
3000.2(5)/0.5/5P/5P20 20 25 20 1531.58082
4000.2(5)/0.5/5P/5P20 20 25 20 1545112.582
500-6000.2(5)/0.5/5P/5P20 20 25 20 156313082
800-10000.2(5)/0.5/5P/5P30 30 40 30 208016082
1200-31500.2(5)/0.5/5P/5P30 30 40 30 2010016082
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZBJ9-12-225b-4s — click image to zoom / view original.

Product Overview

About This Product

LZZBJ9-12-225b-4s

LZZBJ9-12/225b/4s completes the 12 kV four-core trio with the 195b and 198b. It is specified from 200 A to 3150 A, with 20 VA on the metering cores, 25 VA on the first protection core and 15–20 VA on the remainder, rising to 30/40/20 VA in the 800 A and above bands.

The accuracy string is 0.2(5)/0.5/5P/5P, and the short-time thermal current climbs from 150 kA at 200 A to 100 kA with a 160 kA dynamic rating at 1200–3150 A. The unit weighs 82 kg and is cast in the same dry epoxy as the rest of the family, so no oil maintenance applies.

Treat 225b as a frame choice, not a performance upgrade: it shares the electrical table with 195b and 198b and differs in the casting that determines how it sits in the switchgear. When a project mixes the three across feeders, keep the frame code on the nameplate so maintenance can match replacements.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV
12kV
Current Transformer50/60Hz

LZZBJ9-12GY2

Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV

LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV is designed for metering and protection in power systems. Key ratings: primary voltage 12kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceGB/T 17201
View Specs
LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer
20kV
Current Transformer50/60Hz

LZZBJ9-20-180b-3

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-20-180b-3) is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, secondary voltage 5A/1A. Design: insulation level 24/65/125kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZBJ9-24/180b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer
10kV
Current Transformer50/60Hz

LZZBJ9-24-180b-2s-4s

Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s; primary current optional range 20-2500A. For 2s type: rated output 10-20VA under different accuracy grades, weight 36kg; for 4s type: rated output 15-20VA under different accuracy grades, weight 50kg; short-time thermal current:31.5-100kA, rated dynamic stable current:80-160kA; ambient operating temperature -5℃~+40℃.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs