中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZBJ9-12GY2
LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV
12kVLZZBJ9-12GY2
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 12kV
Secondary Metering (1S1 - 1S2): ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZBJ9-12GY2

LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV

LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV is designed for metering and protection in power systems. Key ratings: primary voltage 12kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.

Key Engineering Advantages

  • 12kV insulation grade
  • epoxy resin casting
  • multiple current ranges & accuracy classes for metering+protection
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZBJ9-12GY2

Electrical Parameters

Primary Rated Voltage (Un):12kV
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Standards Conformance:GB/T 17201
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Compact 12 kV epoxy-cast CT, 5–2500 A, 0.2(S)/5(10)P at 10/15 VA, 25 kg.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerGB/T 17201
Model CodeLZZBJ9-12GY2Factory nameplate marking
Primary Voltage12kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsGB/T 17201Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium-voltage switchgear panels
  • Metering and relay protection applications
  • 10kV power systems
  • Ambient temperatures from -5°C to +40°C

Not Recommended For

  • Outdoor installations
  • Gas-insulated switchgear (GIS)
  • Systems above 12kV
  • High-humidity or corrosive environments

Topology & Wiring

connect primary through the bushing; secondary terminals are 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal conventions.

Standards & Compliance

Compliant with: GB/T 17201

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the lowest primary current available?

A: 5 A, which is why this frame is also used for low-ratio metering duties.

Q: How heavy is the LZZBJ9-12GY2?

A: 25 kg, the lightest of the 12 kV LZZBJ9 frames.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZBJ9-12GY2
9 cols · 6 rows

LZZBJ9-12GY2 Current Transformer

Rated primary current I1n (A)Accuracy classCombined0.2(S)/0.5S0.55P10/10P105(10)P15/5(10)P20Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
5-1000.2(S)/5(10)P 0.5(S)/5(10)P10101515150 I1n375 I1n25
1500.2(S)/5(10)P 0.5(S)/5(10)P1010151531.58025
200-3000.2(S)/5(10)P 0.5(S)/5(10)P1010151545112.525
400-6000.2(S)/5(10)P 0.5(S)/5(10)P101015156313025
800-12000.2(S)/5(10)P 0.5(S)/5(10)P1020201510016025
1500-25000.2(S)/5(10)P 0.5(S)/5(10)P1020201510016025
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZBJ9-12GY2 — click image to zoom / view original.

Product Overview

About This Product

LZZBJ9-12GY2

LZZBJ9-12GY2 is the compact 12 kV model: 5 A to 2500 A primary in a 25 kg cast body, the lightest unit in the LZZBJ9 12 kV range. It is used where panel space and weight matter more than the highest fault ratings, such as ring-main units and smaller distribution cubicles.

The datasheet lists 0.2(S)/5(10)P and 0.5(S)/5(10)P combinations with 10 VA on the metering core and 15 VA on the protection core. Short-time thermal current is 150 times primary for 1 s in the 5–100 A band, then 31.5 kA, 45 kA, 63 kA and 100 kA as the ratio rises; dynamic ratings run from 80 kA to 160 kA.

Because the frame starts at 5 A, the same model also covers low-ratio metering duties that the larger 12 kV frames do not reach. Check that the protection core's 5(10)P rating matches the fault level at the installation point before selecting this lighter frame instead of the 175b.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer
20kV
Current Transformer50/60Hz

LZZBJ9-20-180b-3

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-20-180b-3) is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, secondary voltage 5A/1A. Design: insulation level 24/65/125kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZBJ9-24/180b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer
10kV
Current Transformer50/60Hz

LZZBJ9-24-180b-2s-4s

Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s; primary current optional range 20-2500A. For 2s type: rated output 10-20VA under different accuracy grades, weight 36kg; for 4s type: rated output 15-20VA under different accuracy grades, weight 50kg; short-time thermal current:31.5-100kA, rated dynamic stable current:80-160kA; ambient operating temperature -5℃~+40℃.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZBJ9-24/220b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer
10kV
Current Transformer50/60Hz

LZZBJ9-24-220b-2s-4s

Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s, primary current optional range 20-3150A. 2s model weight is 43kg with rated output 15-30VA at different accuracy grades; 4s model weight is 70kg with rated output 15-30VA at different accuracy grades; short-time thermal current ranges 31.5-100kA, rated dynamic stable current ranges 80-160kA; ambient operating temperature -5℃~+40℃.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs