LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV is designed for metering and protection in power systems. Key ratings: primary voltage 12kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.
Compact 12 kV epoxy-cast CT, 5–2500 A, 0.2(S)/5(10)P at 10/15 VA, 25 kg.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | GB/T 17201 |
| Model Code | LZZBJ9-12GY2 | Factory nameplate marking |
| Primary Voltage | 12kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | GB/T 17201 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
connect primary through the bushing; secondary terminals are 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal conventions.
Compliant with: GB/T 17201
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the lowest primary current available?
A: 5 A, which is why this frame is also used for low-ratio metering duties.
Q: How heavy is the LZZBJ9-12GY2?
A: 25 kg, the lightest of the 12 kV LZZBJ9 frames.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | 0.2(S)/0.5S | 0.5 | 5P10/10P10 | 5(10)P15/5(10)P20 | Short-time thermal current Ith (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|
| 5-100 | 0.2(S)/5(10)P 0.5(S)/5(10)P | 10 | 10 | 15 | 15 | 150 I1n | 375 I1n | 25 |
| 150 | 0.2(S)/5(10)P 0.5(S)/5(10)P | 10 | 10 | 15 | 15 | 31.5 | 80 | 25 |
| 200-300 | 0.2(S)/5(10)P 0.5(S)/5(10)P | 10 | 10 | 15 | 15 | 45 | 112.5 | 25 |
| 400-600 | 0.2(S)/5(10)P 0.5(S)/5(10)P | 10 | 10 | 15 | 15 | 63 | 130 | 25 |
| 800-1200 | 0.2(S)/5(10)P 0.5(S)/5(10)P | 10 | 20 | 20 | 15 | 100 | 160 | 25 |
| 1500-2500 | 0.2(S)/5(10)P 0.5(S)/5(10)P | 10 | 20 | 20 | 15 | 100 | 160 | 25 |
Dimension & outline drawing of LZZBJ9-12GY2 — click image to zoom / view original.
LZZBJ9-12GY2 is the compact 12 kV model: 5 A to 2500 A primary in a 25 kg cast body, the lightest unit in the LZZBJ9 12 kV range. It is used where panel space and weight matter more than the highest fault ratings, such as ring-main units and smaller distribution cubicles.
The datasheet lists 0.2(S)/5(10)P and 0.5(S)/5(10)P combinations with 10 VA on the metering core and 15 VA on the protection core. Short-time thermal current is 150 times primary for 1 s in the 5–100 A band, then 31.5 kA, 45 kA, 63 kA and 100 kA as the ratio rises; dynamic ratings run from 80 kA to 160 kA.
Because the frame starts at 5 A, the same model also covers low-ratio metering duties that the larger 12 kV frames do not reach. Check that the protection core's 5(10)P rating matches the fault level at the installation point before selecting this lighter frame instead of the 175b.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-20-180b-3) is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, secondary voltage 5A/1A. Design: insulation level 24/65/125kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s; primary current optional range 20-2500A. For 2s type: rated output 10-20VA under different accuracy grades, weight 36kg; for 4s type: rated output 15-20VA under different accuracy grades, weight 50kg; short-time thermal current:31.5-100kA, rated dynamic stable current:80-160kA; ambient operating temperature -5℃~+40℃.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s, primary current optional range 20-3150A. 2s model weight is 43kg with rated output 15-30VA at different accuracy grades; 4s model weight is 70kg with rated output 15-30VA at different accuracy grades; short-time thermal current ranges 31.5-100kA, rated dynamic stable current ranges 80-160kA; ambient operating temperature -5℃~+40℃.