中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZBJ9-24-180b-2s-4s
LZZBJ9-24/180b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer
10kVLZZBJ9-24-180b-2s-4s
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZBJ9-24-180b-2s-4s

LZZBJ9-24/180b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s; primary current optional range 20-2500A. For 2s type: rated output 10-20VA under different accuracy grades, weight 36kg; for 4s type: rated output 15-20VA under different accuracy grades, weight 50kg; short-time thermal current:31.5-100kA, rated dynamic stable current:80-160kA; ambient operating temperature -5℃~+40℃.

Key Engineering Advantages

  • 24kV indoor epoxy cast current transformer
  • 2s/4s two structures optional
  • reliable thermal and dynamic stability
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZBJ9-24-180b-2s-4s

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):12/42/75kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

24 kV two- or four-core epoxy-cast CT, 20–2500 A, 0.2/0.5/5P10 at 10–20 VA, 36 kg.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLZZBJ9-24-180b-2s-4sFactory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)12/42/75kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium voltage switchgear panels
  • Current measurement and protection in 10kV systems
  • Revenue metering with 0.2S or 0.5S accuracy
  • Applications requiring high short-time thermal current (up to 100kA)

Not Recommended For

  • Outdoor installations without additional enclosure
  • Gas-insulated switchgear (GIS) due to different mounting
  • High-voltage transmission lines above 24kV
  • DC systems or non-sinusoidal waveforms

Topology & Wiring

Connect primary through the bushing. Secondary terminals: 1S1-1S2 for metering, 2S1-2S2 for protection (if present). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the difference between the 24 kV 180b and 220b frames?

A: The 180b covers up to 2500 A at 36 kg; the 220b goes to 3150 A with heavier burdens and weighs 43 kg.

Q: Which accuracy classes are available?

A: 0.2(5)/0.2(5), 0.2(5)/0.5, 0.2(5)/5P10 and 0.5/5P10, with 10–20 VA depending on the ratio band.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZBJ9-24-180b-2s-4s
10 cols · 6 rows

LZZBJ9-24/180b/2s (4s) Series Current Transformer

Rated primary current (A)Accuracy classCombinedAccuracy class & rated output (VA) 0.2/5Accuracy class & rated output (VA) 0.5/5Accuracy class & rated output (VA) 10P10Accuracy class & rated output (VA) 10P15Accuracy class & rated output (VA) 10P20Short-time thermal current (kA/s)Rated dynamic current (kA)Weight (kg)
20-2000.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10101015151515037536
3000.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10101015151531.58036
400-5000.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P1010101515154511036
600-8000.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P1010101515156313036
1000-12500.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P1015152020208016036
1500-25000.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10151520202010016036
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZBJ9-24-180b-2s-4s — click image to zoom / view original.

Product Overview

About This Product

LZZBJ9-24-180b-2s-4s

LZZBJ9-24/180b/2s(4s) is a 24 kV indoor epoxy-cast current transformer available with two or four cores, covering 20 A to 2500 A. It is the lighter of the two 24 kV frames at 36 kg, and is used in 24 kV distribution switchgear where the higher 220b frame is not required.

The datasheet lists 0.2(5)/0.2(5), 0.2(5)/0.5, 0.2(5)/5P10 and 0.5/5P10 combinations with 10 VA on the metering cores, 15 VA on the 10P10/10P15/10P20 cores, and 20 VA at 1000 A and above. Short-time thermal current runs from 150 kA at 20–200 A to 100 kA with a 160 kA dynamic rating at 1500–2500 A.

Choose the 180b when the panel is a standard 24 kV cubicle and the fault level is moderate; step up to the 220b when the ratio exceeds 2500 A or the secondary burden is heavier. As with the rest of the family, the secondary must be earthed at one point and never open-circuited under load.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZBJ9-24/220b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer
10kV
Current Transformer50/60Hz

LZZBJ9-24-220b-2s-4s

Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s, primary current optional range 20-3150A. 2s model weight is 43kg with rated output 15-30VA at different accuracy grades; 4s model weight is 70kg with rated output 15-30VA at different accuracy grades; short-time thermal current ranges 31.5-100kA, rated dynamic stable current ranges 80-160kA; ambient operating temperature -5℃~+40℃.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZBJ9-35/250b/4s Indoor Single-phase Epoxy Resin Casting Current Transformer
35kV
Current Transformer50/60Hz

LZZBJ9-35-250b-4s

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-35/250b/4s Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-250b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZBJ9-35A Indoor Single-phase Epoxy Resin Casting Current Transformer
35kV
Current Transformer50/60Hz

LZZBJ9-35A

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-35A Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs