Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s; primary current optional range 20-2500A. For 2s type: rated output 10-20VA under different accuracy grades, weight 36kg; for 4s type: rated output 15-20VA under different accuracy grades, weight 50kg; short-time thermal current:31.5-100kA, rated dynamic stable current:80-160kA; ambient operating temperature -5℃~+40℃.
24 kV two- or four-core epoxy-cast CT, 20–2500 A, 0.2/0.5/5P10 at 10–20 VA, 36 kg.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ9-24-180b-2s-4s | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the bushing. Secondary terminals: 1S1-1S2 for metering, 2S1-2S2 for protection (if present). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the difference between the 24 kV 180b and 220b frames?
A: The 180b covers up to 2500 A at 36 kg; the 220b goes to 3150 A with heavier burdens and weighs 43 kg.
Q: Which accuracy classes are available?
A: 0.2(5)/0.2(5), 0.2(5)/0.5, 0.2(5)/5P10 and 0.5/5P10, with 10–20 VA depending on the ratio band.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) 0.2/5 | Accuracy class & rated output (VA) 0.5/5 | Accuracy class & rated output (VA) 10P10 | Accuracy class & rated output (VA) 10P15 | Accuracy class & rated output (VA) 10P20 | Short-time thermal current (kA/s) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|
| 20-200 | 0.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10 | 10 | 10 | 15 | 15 | 15 | 150 | 375 | 36 |
| 300 | 0.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10 | 10 | 10 | 15 | 15 | 15 | 31.5 | 80 | 36 |
| 400-500 | 0.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10 | 10 | 10 | 15 | 15 | 15 | 45 | 110 | 36 |
| 600-800 | 0.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10 | 10 | 10 | 15 | 15 | 15 | 63 | 130 | 36 |
| 1000-1250 | 0.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10 | 15 | 15 | 20 | 20 | 20 | 80 | 160 | 36 |
| 1500-2500 | 0.2(5)/0.2(5) 0.2(5)/0.5 0.2(5)/5P10 0.5/5P10 | 15 | 15 | 20 | 20 | 20 | 100 | 160 | 36 |
Dimension & outline drawing of LZZBJ9-24-180b-2s-4s — click image to zoom / view original.
LZZBJ9-24/180b/2s(4s) is a 24 kV indoor epoxy-cast current transformer available with two or four cores, covering 20 A to 2500 A. It is the lighter of the two 24 kV frames at 36 kg, and is used in 24 kV distribution switchgear where the higher 220b frame is not required.
The datasheet lists 0.2(5)/0.2(5), 0.2(5)/0.5, 0.2(5)/5P10 and 0.5/5P10 combinations with 10 VA on the metering cores, 15 VA on the 10P10/10P15/10P20 cores, and 20 VA at 1000 A and above. Short-time thermal current runs from 150 kA at 20–200 A to 100 kA with a 160 kA dynamic rating at 1500–2500 A.
Choose the 180b when the panel is a standard 24 kV cubicle and the fault level is moderate; step up to the 220b when the ratio exceeds 2500 A or the secondary burden is heavier. As with the rest of the family, the secondary must be earthed at one point and never open-circuited under load.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s, primary current optional range 20-3150A. 2s model weight is 43kg with rated output 15-30VA at different accuracy grades; 4s model weight is 70kg with rated output 15-30VA at different accuracy grades; short-time thermal current ranges 31.5-100kA, rated dynamic stable current ranges 80-160kA; ambient operating temperature -5℃~+40℃.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-35/250b/4s Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-250b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-35A Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.