LZZBJ9-35A Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Lightest 35 kV frame, 20–1600 A, 0.2/0.5, 0.2/5P, 0.5/5P at 10–30 VA, 70 kg.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ9-35A | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 40.5/95/185kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary in series with the line. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: Why is the 35A lighter than the 35G?
A: It uses a smaller casting with fewer winding combinations and no 0.5(S) metering option, which brings the mass down from 78 kg to 70 kg.
Q: What outputs are available?
A: 10 VA, 15 VA, 30 VA, 20 VA and 15 VA across the five cores, depending on the accuracy pairing.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 0.2 (S)/0.5S | Accuracy class & rated output (VA) COSφ=0.8 0.5 | Accuracy class & rated output (VA) COSφ=0.8 5P10 | Accuracy class & rated output (VA) COSφ=0.8 5P15 | Accuracy class & rated output (VA) COSφ=0.8 5P20 | Short-time thermal current Ith (kA/S) kA | Short-time thermal current Ith (kA/S) s | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 4 | 1 | 10 | 70 |
| 30-40 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 4 | 2 | 10 | 70 |
| 50 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 12 | 1 | 30 | 70 |
| 75 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 16 | 1 | 40 | 70 |
| 100-150 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 25 | 1 | 63 | 70 |
| 200-300 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 31.5 | 1 | 80 | 70 |
| 400-600 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 31.5 | 2 | 80 | 70 |
| 800-1600 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 31.5 | 4 | 130 | 70 |
| 2000-2500 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | [On Request] | [On Request] | [On Request] | [On Request] |
Dimension & outline drawing of LZZBJ9-35A — click image to zoom / view original.
LZZBJ9-35A is the lightest 35 kV frame in the LZZBJ9 family at 70 kg, covering 20 A to 1600 A with five cores. It is the standard indoor 35 kV unit for panels where the 30 VA protection burden of the D1 frame is not needed.
Accuracy combinations are 0.2/0.5, 0.2/5P and 0.5/5P, with rated outputs of 10 VA, 15 VA, 30 VA, 20 VA and 15 VA across the cores. Short-time thermal current is 4 kA/1 s at 20 A and rises to 31.5 kA/4 s at 800–1600 A, with dynamic ratings from 10 kA to 130 kA.
The A frame is the one to compare against the G frame: same 35 kV insulation and the same ratio ceiling, 8 kg lighter, but without the 0.5(S) metering option and with fewer core pairings. For straightforward metering-plus-protection duty at moderate burden it is the more economical choice.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-35D1 Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-35G Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-G) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.