KEMA & ISO 9001/14001 Certified|Exporting to 50+ Countries (IEC 61869-3 / IEEE C57.13)
24/7 Global Engineering Hotline: 86 18852046268|sales@potentialtransformers.com
中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZBJ9-35A
LZZBJ9-35A Indoor Single-phase Epoxy Resin Casting Current Transformer
35kVLZZBJ9-35A
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 35kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZBJ9-35A

LZZBJ9-35A Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-35A Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • 35kV indoor epoxy cast current transformer
  • wide current range
  • excellent thermal and dynamic stability
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZBJ9-35A

Electrical Parameters

Primary Rated Voltage (Un):35kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):40.5/95/185kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Lightest 35 kV frame, 20–1600 A, 0.2/0.5, 0.2/5P, 0.5/5P at 10–30 VA, 70 kg.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLZZBJ9-35AFactory nameplate marking
Primary Voltage35kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)40.5/95/185kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium-voltage switchgear panels
  • Metering and protection in 35kV systems
  • Applications requiring high accuracy (0.2S/0.5S) and protection classes (5P10/5P20)
  • Environments with ambient temperature -5°C to +40°C

Not Recommended For

  • Outdoor installations (not weatherproof)
  • High-voltage transmission systems above 35kV
  • DC systems (AC only)
  • Applications requiring low thermal current below 4kA

Topology & Wiring

Connect primary in series with the line. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: Why is the 35A lighter than the 35G?

A: It uses a smaller casting with fewer winding combinations and no 0.5(S) metering option, which brings the mass down from 78 kg to 70 kg.

Q: What outputs are available?

A: 10 VA, 15 VA, 30 VA, 20 VA and 15 VA across the five cores, depending on the accuracy pairing.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZBJ9-35A
11 cols · 9 rows

LZZBJ9-35A LZZQB8-35A LZZB8-35 (Q) Current Transformer — Technical Data

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA) COSφ=0.8 0.2 (S)/0.5SAccuracy class & rated output (VA) COSφ=0.8 0.5Accuracy class & rated output (VA) COSφ=0.8 5P10Accuracy class & rated output (VA) COSφ=0.8 5P15Accuracy class & rated output (VA) COSφ=0.8 5P20Short-time thermal current Ith (kA/S) kAShort-time thermal current Ith (kA/S) sRated dynamic current Idyn (kA)Weight (kg)
200.2/0.5 0.2/5P 0.5/5P1015302015411070
30-400.2/0.5 0.2/5P 0.5/5P1015302015421070
500.2/0.5 0.2/5P 0.5/5P10153020151213070
750.2/0.5 0.2/5P 0.5/5P10153020151614070
100-1500.2/0.5 0.2/5P 0.5/5P10153020152516370
200-3000.2/0.5 0.2/5P 0.5/5P101530201531.518070
400-6000.2/0.5 0.2/5P 0.5/5P101530201531.528070
800-16000.2/0.5 0.2/5P 0.5/5P101530201531.5413070
2000-25000.2/0.5 0.2/5P 0.5/5P1015302015[On Request][On Request][On Request][On Request]
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZBJ9-35A — click image to zoom / view original.

Product Overview

About This Product

LZZBJ9-35A

LZZBJ9-35A is the lightest 35 kV frame in the LZZBJ9 family at 70 kg, covering 20 A to 1600 A with five cores. It is the standard indoor 35 kV unit for panels where the 30 VA protection burden of the D1 frame is not needed.

Accuracy combinations are 0.2/0.5, 0.2/5P and 0.5/5P, with rated outputs of 10 VA, 15 VA, 30 VA, 20 VA and 15 VA across the cores. Short-time thermal current is 4 kA/1 s at 20 A and rises to 31.5 kA/4 s at 800–1600 A, with dynamic ratings from 10 kA to 130 kA.

The A frame is the one to compare against the G frame: same 35 kV insulation and the same ratio ceiling, 8 kg lighter, but without the 0.5(S) metering option and with fewer core pairings. For straightforward metering-plus-protection duty at moderate burden it is the more economical choice.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZBJ9-35D1 Indoor Single-phase Epoxy Resin Casting Current Transformer
35kV
Current Transformer50/60Hz

LZZBJ9-35D1

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-35D1 Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZBJ9-35G Indoor Single-phase Epoxy Resin Casting Current Transformer
35kV
Current Transformer50/60Hz

LZZBJ9-35-G

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-35G Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-G) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZBJ9-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer
35kV
Current Transformer50/60Hz

LZZBJ9-35-Q

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs