LZZBJ9-35G Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-G) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
35 kV epoxy-cast CT, 20–3150 A, six accuracy pairings at 10 VA per core, 78 kg.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ9-35-G | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 40.5/95/185kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: How does the 35G differ from the 35A?
A: The G frame offers 0.5(S) metering and additional core pairings; the A frame is 8 kg lighter with fewer combinations.
Q: What is the short-time rating at 800–1600 A?
A: 31.5 kA for 4 s, with a 130 kA dynamic rating.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSΦ=0.8 | Accuracy class & rated output (VA) COSΦ=0.8 | Accuracy class & rated output (VA) COSΦ=0.8 | Accuracy class & rated output (VA) COSΦ=0.8 | Accuracy class & rated output (VA) COSΦ=0.8 | Accuracy class & rated output (VA) COSΦ=0.8 | Short-time thermal current Ith (kA/S) | Short-time thermal current Ith (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 4 | 1 | 10 | 78 |
| 30-40 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 4 | 2 | 10 | 78 |
| 50 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 12 | 1 | 30 | 78 |
| 75 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 16 | 1 | 40 | 78 |
| 100-150 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 25 | 1 | 63 | 78 |
| 200-300 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 31.5 | 1 | 80 | 78 |
| 400-600 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 31.5 | 2 | 80 | 78 |
| 800-1600 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | 31.5 | 4 | 130 | 78 |
| 2000-3150 | 0.2(S)/0.5(S) | 0.2(S)/0.5S | 0.2(S)/5P | 0.2(S)/0.5(S)/5P | 0.2(S)/5P/5P | 0.5(S)/5P/5P | 10 | [On Request] | [On Request] | [On Request] | 78 |
Dimension & outline drawing of LZZBJ9-35-G — click image to zoom / view original.
LZZBJ9-35G is the 35 kV model that balances mass and output: 78 kg, 20 A to 3150 A, and six accuracy pairings across its cores. It sits between the 70 kg 35A and the 140 kg 35D1, and is the usual choice for standard 35 kV indoor switchgear.
The datasheet gives 0.2(S)/0.5(S), 0.2(S)/0.5S, 0.2(S)/5P, 0.2(S)/0.5(S)/5P, 0.2(S)/5P/5P and 0.5(S)/5P/5P as selectable combinations, with 10 VA on each core. Short-time thermal current runs from 4 kA/1 s at 20 A to 31.5 kA/4 s at 800–1600 A, with dynamic ratings of 10–130 kA.
Compared with the 35A, the G frame adds the 0.5(S) metering class and slightly heavier output options; compared with the 35D1, it trades 30 VA protection cores for a 62 kg lighter casting. Specify the core pairing explicitly, since the same model code is delivered with several.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer,10kV
LZZBJ9-10 Indoor Single-phase Epoxy Resin Casting Current Transformer,10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.
10kV Indoor Epoxy Cast Current Transformer for KYN28 Cabinet
LZZBJ9-10GWA,B,C 10kV Indoor Epoxy Cast Current Transformer for KYN28 Cabinet (LZZBJ9-10GWA-B-C) is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A or 1A, accuracy class 0.2S, 0.5, 5P20, 5P30. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869, GB/T 20840.