Almost every indoor instrument transformer between 7.2 kV and 12 kV is insulated with vacuum-cast epoxy. The reason is not fashion: epoxy is dimensionally stable, flame-retardant, maintenance-free, and — if it is cast correctly — free of the voids that start partial discharge. When a cast-resin unit fails in service, the failure usually traces back to something that happened in the mould, not to the load it was carrying.

This note covers what actually decides the life of a 7.2–12 kV cast-resin VT or CT: the casting process, the field-grading screen, the partial-discharge test at 1.2 Um, the 12/42/75 kV insulation level, and how a 0.2S metering core is specified for a KYN28-class panel.

  • Vacuum casting is what makes a void-free epoxy body possible; a void is a gas pocket inside solid insulation and therefore a partial-discharge site.
  • Partial discharge is measured at 1.2 Um — 14.4 kV for a 12 kV unit — and the acceptance limit is what shapes the field-grading screen.
  • Insulation level for 12 kV indoor equipment is 12/42/75 kV: rated voltage, one-minute power-frequency withstand, lightning impulse.
  • A 0.2S metering core holds its accuracy down to light load; a 0.5 core does not. They are not interchangeable on a tariff meter.

1. Why vacuum casting, and what happens without it

Epoxy resin is mixed with a hardener and a silica filler, degassed, and poured into a heated mould around the winding. Vacuum and pressure are used because the mixture traps air: without them, bubbles remain in the resin and at the resin–conductor interface.

A bubble inside solid insulation is worse than a bubble in air. The dielectric constant of gas is roughly a third of that of epoxy, so the field in the void is higher than in the surrounding resin. Once the field exceeds the breakdown strength of the gas, the void discharges — repeatedly, at every voltage peak. Each discharge erodes the void wall, the void grows, and eventually the erosion path reaches the conductor.

This is why the process matters more than the raw material: two suppliers can buy the same resin system and produce very different transformers. The measurable difference is partial discharge.

2. The field-grading screen

A cast-resin unit is not a uniform cylinder. The primary conductor is at high voltage, the mounting flange is at earth, and the epoxy between them carries a field that is strongest where the geometry is sharpest — at the end of a winding, at the edge of a flange, at the transition into the shed.

Two measures control it:

  • Semiconductive screening — a conductive or semi-conductive layer over the primary conductor smooths the field at the conductor surface, removing the sharp edge that would otherwise start a discharge.
  • Earthed screen — a conductive layer on the outside of the cast body, connected to the flange, fixes the outer surface at earth potential. The insulation then works between two defined electrodes rather than between a conductor and "wherever the mounting bracket happens to be".

The screen is also what allows the unit to be touched safely: without it, the epoxy surface carries a capacitive voltage and a person standing on a concrete floor is part of the circuit.

3. Partial discharge at 1.2 Um

IEC 61869-2 and -3 require a partial-discharge test as a routine test — on every unit, not on a sample. The test voltage is 1.2 Um, which for 12 kV equipment is 14.4 kV, and the acceptance limit for cast-resin instrument transformers is typically 5 pC (some specifications allow 10 pC or 20 pC; a 5 pC limit is a statement about the process, not just the product).

Why 1.2 Um rather than Um: the voltage factor of a VT can hold 1.2 Um continuously, so the insulation must be discharge-free at that level, not merely at nominal.

Two practical consequences for buyers:

  • A test report that lists only "PD test passed" without the measured value is not evidence. Ask for the picocoulomb figure and the test voltage.
  • A unit that passes at 5 pC on the bench can still discharge in service if it is mounted with a floating bracket or a poor earth connection — the screen only works when it is earthed.

4. Insulation level: 12/42/75 kV means three different tests

The three numbers are not three voltages of the same kind:

FigureTestApplied to
12 kVRated voltage (Um = 12 kV)The reference for all other levels and for the 1.2 Um PD test
42 kVPower-frequency withstand, 1 minutePrimary winding to earth and between windings
75 kVLightning impulse withstand (1.2/50 µs)Primary winding to earth; type test on the design

A 7.2 kV unit uses a lower insulation level (typically 7.2/20/40 kV or 7.2/28/60 kV depending on the specification). Mixing the two in one order is a common mistake: the 7.2 kV transformer will fit the 12 kV panel, but it will not survive the panel's impulse test.

5. Heat, class and the second life of a cast unit

Epoxy is a poor thermal conductor compared with copper, and the winding hotspot inside a cast body runs hotter than the same winding in oil. Cast-resin instrument transformers are therefore rated by insulation class — class B (130 °C) or class F (155 °C) — and the class is a limit on the hotspot, not on the average winding temperature.

Two things shorten the life of a cast unit that is thermally adequate on paper:

  • Cyclic loading. Repeated heating and cooling cycles between copper and epoxy create mechanical stress at the interface, because the two materials expand at different rates. A unit that runs at 90 °C continuously is usually happier than one that swings between 40 °C and 120 °C every day.
  • Ambient. A transformer rated for 40 °C ambient inside a panel that reaches 55 °C at the top is a transformer operating outside its thermal design, whatever the nameplate says.

6. Metering cores: what 0.2S buys you

For a 0.5 class CT, the accuracy is guaranteed from 5 % to 120 % of rated current. For 0.2S, the lower limit extends to 1 % — the "S" stands for "special", and it exists for a specific commercial problem: a feeder that is lightly loaded most of the time.

A 200/5 A CT with a 0.5 core is accurate at 10 A and above. If the actual load is 2 A, the core is outside its specified range, and the meter error can exceed the class even though the CT is not defective. This is the case that 0.2S metering was invented for.

The cost of 0.2S is a larger core and tighter winding control, and it only pays off if the burden is also right: 0.2S at 15 VA is meaningful, 0.2S at 5 VA with a 30 VA connected burden is not.

7. Routine tests and type tests

Routine tests on every unit: power-frequency withstand, partial discharge, and accuracy (ratio and phase error at the specified burden). Type tests on the design: temperature rise, lightning impulse, short-circuit withstand, and — where specified — mechanical and environmental tests.

For a repeat order, a routine test report plus the original type-test report is normally sufficient. For a new design, insist on witnessing the type tests or on a third-party report; the impulse test in particular is destructive, so it is done once and never repeated on delivered units.

8. A datasheet line that can be built

CT, 12 kV indoor, 200/5 A, metering core class 0.2S at 15 VA, protection core 5P10 at 15 VA, insulation 12/42/75 kV, ≤5 pC at 1.2 Um (14.4 kV), cast epoxy, KYN28 mounting, IEC 61869-2, routine test report with measured PD values.

9. Frequently asked questions

Is 5 pC a standard limit or a customer requirement?

IEC sets a limit that varies with the insulation level and the type of transformer; 5 pC is a common, tighter customer requirement for cast-resin medium-voltage units. It is achievable with proper vacuum casting, which is why it is a useful proxy for process quality.

Can a cast-resin VT be repaired after a partial-discharge failure?

Practically, no. The discharge path is inside solid insulation; grinding it out and re-casting is a factory operation, and the repaired area is rarely as good as the original. Treat a PD failure as a design or process problem and replace the unit.

Why is the earthed screen important for safety?

Because it fixes the outer surface at earth potential. Without it, the epoxy surface is capacitively coupled to the primary and can hold a dangerous voltage; with it, the unit can be mounted on a metal frame and touched after isolation without a floating surface charge.

Does a higher accuracy class reduce the temperature rise?

No. Accuracy and thermal behaviour are separate designs: a high-accuracy core may even run warmer because it has more iron. Specify both, and test both.

10. References and further reading

  1. Morphologic analysis and diagnosis of defects inside cast resin medium voltage current transformers insulation by digital partial discharges acquisitions, IEEE conference paper — links PD acquisition patterns to specific casting defects. IEEE Xplore
  2. Finite element solution method on power loss of plateau type and epoxy resin casting current transformer, IEEE conference paper — thermal and loss modelling of cast-resin CTs. IEEE Xplore
  3. IEC 61869-2, Instrument transformers — Part 2: Additional requirements for current transformers.
  4. IEC 61869-3, Instrument transformers — Part 3: Additional requirements for inductive voltage transformers.

Specifying a 10 kV or 12 kV indoor unit for a KYN28 panel? Our current transformer range lists ratios, classes and burdens per model, and the voltage transformer range covers the phase-to-earth and residual-winding variants.