LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-20-180b-3) is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, secondary voltage 5A/1A. Design: insulation level 24/65/125kV, Dry Epoxy Resin, 50/60Hz operation.
20 kV three-core epoxy-cast CT, 20–2000 A, 0.2(S)/0.5(S)/10P at 10–15 VA, 36.5 kg.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ9-20-180b-3 | Factory nameplate marking |
| Primary Voltage | 20kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 24/65/125kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary in series with the line. Secondary terminals: 1S1-1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: Does the accuracy class change with ratio?
A: Yes. The table shows 0.2(S)/0.2(S) up to 200 A, 0.2(S)/0.5(S) from 300–500 A, and 0.5(S)/10P from 600 A upward.
Q: How many cores does the 20 kV model have?
A: Three, which is what the 3 in the model code denotes.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | 0.2(S) | 0.5(S) | 1J/P15 | Short-time thermal current Ith (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|
| 20-200 | 0.2(S)/0.2(S) | 10 | 10 | 15 | 150 I1n | 375 I1n | 36.5 |
| 300 | 0.2(S)/0.5(S) | 10 | 10 | 15 | 31.5 | 80 | 36.5 |
| 400-500 | 0.2(S)/0.5(S) | 10 | 10 | 15 | 45 | 110 | 36.5 |
| 600-800 | 0.5(S)/10P | 10 | 10 | 15 | 63 | 130 | 36.5 |
| 1600-2000 | 0.5(S)/10P | 10 | 15 | 15 | 100 | 160 | 36.5 |
Dimension & outline drawing of LZZBJ9-20-180b-3 — click image to zoom / view original.
LZZBJ9-20/180b/3 is the 20 kV model, with three secondary cores and a 36.5 kg cast body. It covers 20 A to 2000 A primary and is specified for 20 kV switchgear where a 12 kV frame would be under-insulated and a 24 kV frame oversized.
Accuracy is listed as 0.2(S)/0.2(S) in the 20–200 A band, 0.2(S)/0.5(S) from 300 A to 500 A, and 0.5(S)/10P from 600 A to 2000 A, with 10 VA and 15 VA outputs. Short-time thermal current is 150 times primary at the bottom of the range and rises to 100 kA with a 160 kA dynamic rating at 1600–2000 A.
The three-core arrangement suits a panel that needs one metering circuit and two protection circuits but does not have room for a four-core casting. Note that the accuracy class shifts from 0.2(S) to 0.5(S) above 500 A in the published table, so revenue metering at high ratios should be checked against the actual ratio band.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s; primary current optional range 20-2500A. For 2s type: rated output 10-20VA under different accuracy grades, weight 36kg; for 4s type: rated output 15-20VA under different accuracy grades, weight 50kg; short-time thermal current:31.5-100kA, rated dynamic stable current:80-160kA; ambient operating temperature -5℃~+40℃.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 24/65/125kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Two optional structures: 2s and 4s, primary current optional range 20-3150A. 2s model weight is 43kg with rated output 15-30VA at different accuracy grades; 4s model weight is 70kg with rated output 15-30VA at different accuracy grades; short-time thermal current ranges 31.5-100kA, rated dynamic stable current ranges 80-160kA; ambient operating temperature -5℃~+40℃.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-35/250b/4s Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-35-250b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.