Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2; tingkat isolasi nominal 40,5/95/185kV, frekuensi nominal 50/60Hz, arus sekunder nominal 5A atau 1A. Arus primer opsional mencakup 20–3150A; keluaran nominal kelas akurasi: 30VA(0,2S/0,5S), 30VA(0,5), 50VA(5P10), 40VA(5P15), 30VA(5P20); arus tahan termal waktu singkat berkisar 4–31,5kA, arus tahan dinamis nominal berkisar 10–130kA; berat produk: 112kg; suhu operasi lingkungan -5°C hingga +40°C.
LZZBJ9-35 adalah transformator arus cetakan epoksi dalam ruangan 35kV untuk switchgear tegangan menengah, menawarkan belitan multi-akurasi dan stabilitas termal/dinamis tinggi.
| Parameter | Spesifikasi | Verifikasi |
|---|---|---|
| Jenis Produk | Transformator Arus | [Atas Permintaan] |
| Kode Model | LZZBJ9-35-250b-4s | Penandaan pabrik |
| Tegangan Primer | 35kV | Uji tegangan nominal (IEC 61869-1/3) |
| Arus Sekunder | 5A/1A | Pemeriksaan rasio pada frekuensi nominal |
| Kelas Akurasi | [On Request] | Uji akurasi (IEC 61869-2 / IEEE C57.13) |
| Beban Nominal | [On Request] | Uji beban pada VA nominal |
| Jenis Isolasi | Dry Epoxy Resin | Uji dielektrik sesuai standar |
| Tingkat Isolasi (BIL) | 40.5/95/185kV | Ketahanan frekuensi daya & impuls petir |
| Standar | [On Request] | Tersertifikasi sesuai standar yang tercantum |
| Frekuensi | 50/60Hz | Sesuai IEC 61869-1 |
| Lingkungan | Ambient: -5℃~+40℃ | Sesuai batas lembar data |
Ideal Untuk
Tidak Direkomendasikan Untuk
Untuk CT: Hubungkan primer melalui bushing. Terminal sekunder: 1S1-1S2 untuk pengukuran, 2S1-2S2 untuk proteksi. Jangan pernah membuka rangkaian sekunder CT saat berenergi - tegangan berbahaya. Tanahkan belitan sekunder pada satu titik. Ikuti penandaan terminal IEC 61869-2. ⚠️ Safety: Follow the nameplate terminal diagram and ground the secondary winding at one point.
Sesuai dengan: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
T: Apa tingkat isolasi CT ini?
J: Tingkat isolasi adalah 12/42/75kV, yang berarti tegangan sistem 12kV, tahan tegangan frekuensi daya 42kV, tahan impuls petir 75kV.
T: Apakah CT ini dapat digunakan untuk pengukuran dan proteksi sekaligus?
J: Ya, CT ini memiliki beberapa inti dengan kelas akurasi 0,2S/0,5S untuk pengukuran dan 5P10/5P15/5P20 untuk proteksi.
T: Apa berat dan jenis pemasangannya?
J: Beratnya 112kg dan dirancang untuk pemasangan dalam ruangan, biasanya pada panel switchgear.
Bidang yang hilang ditandai [Atas Permintaan] — tidak pernah direkayasa. Baris verifikasi M2/M5/M6 mengikuti konvensi IEC 61869 / IEEE C57.13.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 | Short-time thermal current Ith (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 20 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 4 1 | 10 | 112 |
| 30-40 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 4 2 | 10 | 112 |
| 50 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 12 1 | 30 | 112 |
| 75 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 16 1 | 40 | 112 |
| 100-150 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 25 1 | 63 | 112 |
| 200-300 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 31.5 1 | 80 | 112 |
| 400-600 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 31.5 2 | 80 | 112 |
| 800-1600 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | 31.5 4 | 130 | 112 |
| 2000-3150 | 0.2(5)/0.5/5P/5P | 30 30 50 40 30 | [On Request] | [On Request] | 112 |

Gambar dimensi & garis besar LZZBJ9-35-250b-4s — klik gambar untuk memperbesar / melihat asli.
LZZBJ9-35/250b/4s is the 35 kV four-core model with the heaviest secondary burden in the family: 30 VA, 30 VA, 50 VA, 40 VA and 30 VA across its cores at the lower ratios. The 112 kg casting is what supports that winding volume at 35 kV insulation level, 40.5/95/185 kV.
It covers 20 A to 3150 A with accuracy 0.2(5)/0.5/5P/5P. Short-time thermal current is stated as 4 kA for 1 s at 20 A, rising through 12, 16, 25 and 31.5 kA to a 31.5 kA/4 s rating at 800–1600 A; dynamic ratings run from 10 kA to 130 kA. The last band, 2000–3150 A, is marked on request for thermal and dynamic figures.
This is the model to specify when the protection relays or metering equipment draw more than the 10–30 VA available on the lighter 35 kV frames. It is indoor only, and because of the mass it is normally installed with a lifting arrangement rather than hand-lifted into the panel.
Keluarga produk sama, rating berbeda — bandingkan sebelum menentukan spesifikasi.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan
Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2; tingkat isolasi nominal 40,5/95/185kV, frekuensi nominal 50/60Hz, arus sekunder nominal 5A atau 1A. Arus primer opsional: 20–2500A; keluaran akurasi: 10VA(0,2S/0,5S), 15VA(0,5), 30VA(5P10), 20VA(5P15), 15VA(5P20); arus termal 4–31,5kA, arus dinamis 10–130kA; berat 70kg; suhu lingkungan -5°C hingga +40°C.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan
Transformator arus resin epoksi cor satu fasa dalam ruangan sesuai standar GB/T20840.1/2 dan IEC61869-1/2; tingkat isolasi nominal 40,5/95/185kV, frekuensi nominal 50/60Hz, arus sekunder nominal 5A atau 1A. Arus primer opsional mencakup 20–3150A; keluaran nominal kelas akurasi: 30VA (0,2S/0,5S), 30VA (0,5), 30VA (5P20), 25VA (5P25), 20VA (5P30); arus tahan termal waktu singkat berkisar 25–150kA, arus tahan dinamis nominal berkisar 63–375kA; berat produk: 140kg; suhu operasi lingkungan -5°C hingga +40°C.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan
Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2; tingkat isolasi nominal 40,5/95/185kV, frekuensi nominal 50/60Hz, arus sekunder nominal 5A atau 1A. Arus primer opsional mencakup 20–3150A dengan kelas akurasi dan nilai daya nominal yang sama dengan seri; arus termal jangka pendek berkisar 4–31,5kA, arus tahan dinamis nominal berkisar 10–130kA; berat produk: 78kg; suhu operasi lingkungan -5°C hingga +40°C.