Transformator arus resin epoksi cor satu fasa dalam ruangan, sesuai dengan GB/T20840.1/2 & IEC61869-1/2, tingkat isolasi 12/42/75kV, 50/60Hz, arus sekunder 5A/1A. Rentang arus primer opsional: 20-200A, 300-400A, 500-600A, 800-1000A, 1200-1250A, 1500-3150A; kombinasi akurasi beragam untuk pengukuran dan proteksi, pencocokan parameter tahan independen, berat bersih 78kg, suhu operasi -5°C hingga +40°C.
CT cetakan epoksi dalam ruangan untuk sistem 12kV, cocok untuk pengukuran dan proteksi hingga 3150A.
| Parameter | Spesifikasi | Verifikasi |
|---|---|---|
| Jenis Produk | Transformator Arus | IEC 61869 / GB/T 20840 |
| Kode Model | LZZBJ9-12-198b-4s | Penandaan pabrik |
| Tegangan Primer | 12kV | Uji tegangan nominal (IEC 61869-1/3) |
| Arus Sekunder | [On Request] | Pemeriksaan rasio pada frekuensi nominal |
| Kelas Akurasi | 0.5/1.0/3.0 | Uji akurasi (IEC 61869-2 / IEEE C57.13) |
| Beban Nominal | [On Request] | Uji beban pada VA nominal |
| Jenis Isolasi | Dry Epoxy Resin | Uji dielektrik sesuai standar |
| Tingkat Isolasi (BIL) | [On Request] | Ketahanan frekuensi daya & impuls petir |
| Standar | IEC 61869 / GB/T 20840 | Tersertifikasi sesuai standar yang tercantum |
| Frekuensi | 50/60Hz | Sesuai IEC 61869-1 |
| Lingkungan | [On Request] | Sesuai batas lembar data |
Ideal Untuk
Tidak Direkomendasikan Untuk
Untuk CT: Hubungkan primer melalui bushing. Terminal sekunder: 1S1 dan 1S2 untuk belitan pengukuran; jika ada belitan proteksi, gunakan 2S1 dan 2S2. Jangan pernah membuka rangkaian sekunder CT saat bertegangan - tegangan berbahaya. Tanahkan rangkaian sekunder pada satu titik saja. Ikuti IEC 61869-2 untuk penandaan terminal dan jarak aman. ⚠️ Safety: Follow the nameplate terminal diagram and ground the secondary winding at one point.
Sesuai dengan: IEC 61869 / GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
T: Apa tingkat isolasi CT ini?
J: Tingkat isolasi adalah 12/42/75kV, yang berarti tegangan sistem 12kV, tahan tegangan frekuensi daya 42kV, dan tahan impuls petir 75kV.
T: Apakah CT ini dapat digunakan untuk pengukuran dan proteksi sekaligus?
J: Ya, CT ini menawarkan kelas akurasi 0,5, 1,0, dan 3,0, memungkinkan kombinasi untuk pengukuran dan proteksi.
T: Apa berat dan rentang suhu operasinya?
J: Berat bersih adalah 78kg, dan suhu operasi adalah -5°C hingga +40°C.
Bidang yang hilang ditandai [Atas Permintaan] — tidak pernah direkayasa. Baris verifikasi M2/M5/M6 mengikuti konvensi IEC 61869 / IEEE C57.13.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 | Short-time thermal current (kA/S) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 200 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 150 | 375 | 82 |
| 300 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 31.5 | 80 | 82 |
| 400 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 45 | 112.5 | 82 |
| 500-600 | 0.2(5)/0.5/5P/5P | 20 20 25 20 15 | 63 | 130 | 82 |
| 800-1000 | 0.2(5)/0.5/5P/5P | 30 30 40 30 20 | 80 | 160 | 82 |
| 1200-3150 | 0.2(5)/0.5/5P/5P | 30 30 40 30 20 | 100 | 160 | 82 |

Gambar dimensi & garis besar LZZBJ9-12-198b-4s — klik gambar untuk memperbesar / melihat asli.
LZZBJ9-12/198b/4s is one of three dimensional variants (195b, 198b, 225b) of the same 12 kV four-core design. It covers 200 A to 3150 A primary with 20/20/25/20/15 VA in the lower bands and 30/30/40/30/20 VA from 800 A upward, carrying accuracy 0.2(5)/0.5/5P/5P across four secondary cores.
The electrical data is identical to the 195b and 225b; what changes is the cast body and therefore the panel depth and phase spacing the unit fits into. That is why the three are printed on a single datasheet page: an engineer selects the frame from the switchgear drawing, then reads the ratings from one common table.
If you are replacing an existing 198b, order by frame code rather than by rating, since a 195b or 225b with the same ratio will not necessarily bolt into the same space. Thermal performance is unchanged across the three: up to 100 kA short-time and 160 kA dynamic at the top of the ratio range, 82 kg in all cases.
Keluarga produk sama, rating berbeda — bandingkan sebelum menentukan spesifikasi.
Transformator Arus Cetakan Epoksi Satu Fasa Dalam Ruangan 12kV
Transformator arus resin epoksi cor satu fasa dalam ruangan, sesuai dengan GB/T20840.1/2 & IEC61869-1/2, tingkat isolasi 12/42/75kV, 50/60Hz, arus sekunder 5A/1A. Rentang arus primer opsional: 20-200A, 300-400A, 500-600A, 800-1000A, 1200-1250A, 1500-3150A; opsi keluaran nominal lebih kaya untuk belitan proteksi, berat bersih 80kg, suhu operasi -5°C hingga +40°C.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan, 12kV
Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2. Tingkat isolasi: 12/42/75kV, frekuensi 50/60Hz, arus sekunder 5A atau 1A. Rentang arus primer opsional: 5-100A、150A、200-300A、400-600A、800-1200A、1500-2500A. Berbagai kombinasi kelas akurasi termasuk 0,2S/0,5S dan kelas proteksi, dengan arus tahan termal & dinamis jangka pendek yang sesuai untuk setiap rentang, cocok untuk pengukuran dan proteksi relai pada kabinet switchgear tegangan menengah. Suhu operasi lingkungan: -5°C hingga +40°C, berat bersih 25kg.
Transformator Arus Resin Epoksi Cor Satu Fasa Dalam Ruangan
Transformator arus resin epoksi cor satu fasa dalam ruangan yang sesuai dengan standar GB/T20840.1/2 dan IEC61869-1/2; tingkat isolasi nominal 24/65/125kV, frekuensi nominal 50/60Hz, arus sekunder nominal 5A atau 1A. Arus primer opsional mencakup 20–2000A; keluaran nominal kelas akurasi: 10VA untuk 0,2(S)/0,5(S), 15VA untuk 10P15; arus termal jangka pendek berkisar 31,5–100kA, arus tahan dinamis nominal berkisar 80–160kA; berat produk: 36,5kg; suhu operasi lingkungan -5°C hingga +40°C.