中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZBJ9-12-198b-4s
LZZBJ9-12/198b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV
12kVLZZBJ9-12-198b-4s
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 12kV
Secondary Metering (1S1 - 1S2): (0.5/1.0/3.0)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZBJ9-12-198b-4s

LZZBJ9-12/198b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV

LZZBJ9-12/198b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-198b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, accuracy class 0.5/1.0/3.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Key Engineering Advantages

  • 12kV insulation
  • epoxy casting
  • larger current coverage
  • weight 78kg
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZBJ9-12-198b-4s

Electrical Parameters

Primary Rated Voltage (Un):12kV
Metering & Protection Class:0.5/1.0/3.0
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Standards Conformance:IEC 61869 / GB/T 20840
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

12 kV four-core epoxy-cast CT, 200–3150 A, one of three dimensional variants sharing the 195b/225b datasheet, 82 kg.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 61869 / GB/T 20840
Model CodeLZZBJ9-12-198b-4sFactory nameplate marking
Primary Voltage12kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class0.5/1.0/3.0Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 61869 / GB/T 20840Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium voltage switchgear panels
  • Revenue metering with accuracy class 0.5
  • Protection schemes requiring class 3.0
  • Primary currents from 20A to 3150A
  • 50/60Hz power systems

Not Recommended For

  • Outdoor installations without additional enclosure
  • Gas-insulated switchgear (GIS) applications
  • High-voltage transmission systems above 12kV
  • DC systems
  • High altitude above 1000m without derating

Topology & Wiring

Connect primary through the bushing. Secondary terminals: 1S1 and 1S2 for metering winding; if protection winding exists, use 2S1 and 2S2. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point only. Follow IEC 61869-2 for terminal markings and safety clearances.

Standards & Compliance

Compliant with: IEC 61869 / GB/T 20840

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What distinguishes the 198b from the 195b and 225b?

A: Only the cast body dimensions. All three carry the same 200–3150 A, 0.2(5)/0.5/5P/5P ratings and the same 82 kg mass.

Q: Which model should be used for a replacement?

A: The same frame code as the original, because the three variants are not mechanically interchangeable even though their electrical data matches.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZBJ9-12-198b-4s
6 cols · 6 rows

LZZBJ9-12/198b/4s Current Transformer — Technical Data

Rated primary current (A)Accuracy classCombinedAccuracy class & rated output (VA) COSφ=0.8Short-time thermal current (kA/S)Rated dynamic current (kA)Weight (kg)
2000.2(5)/0.5/5P/5P20 20 25 20 1515037582
3000.2(5)/0.5/5P/5P20 20 25 20 1531.58082
4000.2(5)/0.5/5P/5P20 20 25 20 1545112.582
500-6000.2(5)/0.5/5P/5P20 20 25 20 156313082
800-10000.2(5)/0.5/5P/5P30 30 40 30 208016082
1200-31500.2(5)/0.5/5P/5P30 30 40 30 2010016082
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZBJ9-12-198b-4s — click image to zoom / view original.

Product Overview

About This Product

LZZBJ9-12-198b-4s

LZZBJ9-12/198b/4s is one of three dimensional variants (195b, 198b, 225b) of the same 12 kV four-core design. It covers 200 A to 3150 A primary with 20/20/25/20/15 VA in the lower bands and 30/30/40/30/20 VA from 800 A upward, carrying accuracy 0.2(5)/0.5/5P/5P across four secondary cores.

The electrical data is identical to the 195b and 225b; what changes is the cast body and therefore the panel depth and phase spacing the unit fits into. That is why the three are printed on a single datasheet page: an engineer selects the frame from the switchgear drawing, then reads the ratings from one common table.

If you are replacing an existing 198b, order by frame code rather than by rating, since a 195b or 225b with the same ratio will not necessarily bolt into the same space. Thermal performance is unchanged across the three: up to 100 kA short-time and 160 kA dynamic at the top of the ratio range, 82 kg in all cases.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV
12kV
Current Transformer50/60Hz

LZZBJ9-12-225b-4s

Indoor Single-phase Epoxy Cast Current Transformer 12kV

LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-225b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.2/0.5/1.0
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV
12kV
Current Transformer50/60Hz

LZZBJ9-12GY2

Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV

LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV is designed for metering and protection in power systems. Key ratings: primary voltage 12kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceGB/T 17201
View Specs
LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer
20kV
Current Transformer50/60Hz

LZZBJ9-20-180b-3

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-20/180b/3 Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-20-180b-3) is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, secondary voltage 5A/1A. Design: insulation level 24/65/125kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs