The International Electrotechnical Commission standard IEC 61869-3 establishes global specifications for inductive voltage transformers used in electrical measurement and protection systems.

It is the part of the IEC 61869 family that replaced IEC 60044-2. An engineer specifying a voltage transformer for a project outside China should quote it directly — GB/T 20840.3 is aligned with it, so a unit type-tested to one is normally acceptable under the other.

IEC 61869-3 fixes accuracy, burden and insulation / partial-discharge requirements. A quotation that lists only the accuracy class is incomplete: always ask for the rated burden window, the voltage factor and the partial-discharge level as well.

When specifying potential transformers for international utility projects, engineering firms must pay close attention to three core parameters:

1. Rated Burden & Accuracy Class: Burden represents the total apparent power (VA) connected to the secondary winding. Operating a Class 0.2 PT outside its specified burden window (e.g. 25% to 100% of rated VA) will cause ratio error drift beyond class limits.

The classes that can appear on an inductive VT nameplate, and the limits they stand for:

ClassTypical applicationRatio error at 80–120% UnPhase displacement
0.1Laboratory and reference metering±0.1%±5 min
0.2Revenue metering±0.2%±10 min
0.5Commercial and industrial metering±0.5%±20 min
1.0Indication only±1.0%±40 min
3PProtection±3% at rated voltage factorNot specified
6PProtection±6% at rated voltage factorNot specified

The S suffix (0.2S, 0.5S) belongs to current transformers, defined in IEC 61869-2, where accuracy must hold down to 1% of rated current. Inductive voltage transformers have no S class; the same intent is expressed by Class 0.2 plus the burden range over which it has to hold.

2. Voltage Factor (Vf) & Duration: For effectively grounded systems, the voltage factor is typically 1.2 continuous and 1.5 for 30 seconds. For ungrounded or resonant grounded networks, a voltage factor of 1.9 Un for 8 hours is required to survive ground faults.

System earthingContinuousFault conditionDuration
Effectively (solidly) earthed1.2 Un1.5 Un30 s
Non-effectively earthed / resonant earthed1.2 Un1.9 Un8 h

3. Partial Discharge (PD) Testing: PD in cast resin or paper-oil insulation indicates microscopic void formation. PotentialTransformers.com tests 100% of production units in our high-voltage Faraday cage, guaranteeing PD < 5pC at 1.2 Un.

JDZX11-35R 35 kV indoor epoxy resin cast voltage transformer
JDZX11-35R — 35 kV indoor epoxy-resin cast VT. Every unit is PD-tested at 1.2 Um/√3 in a shielded enclosure before shipment.

Temperature rise: the requirement that shows up years later

Temperature rise is verified at rated voltage and the burden that produces the highest losses, held until thermal equilibrium. The standard limits the rise, not an absolute temperature, because a substation ambient is not fixed — which is why two units with identical nameplate data can age very differently. For cast-resin VTs the hot spot sits inside the primary winding; for oil-immersed units it is the top-oil temperature. A design that passes ratio and PD but runs hot will drift out of class within a few years, so request the type-test report together with the routine-test report.

Test programme at a glance (IEC 61869-3)
TestWhat it provesRoutine (100%)Type test
Power-frequency withstandInsulation integrity of primary and secondaryYes—
Partial discharge at 1.2 Um/√3Absence of voids and delaminationYes—
Ratio and phase error at 80 / 100 / 120% UnAccuracy class and burden windowYes—
Temperature rise at rated voltage and burdenThermal design margin—Yes
Voltage factor 1.9 Un for 8 hSurvival of an earth fault on an isolated system—Yes
Lightning impulseInsulation coordination with the system BIL—Yes

By selecting KEMA-certified PTs manufactured under IEC 61869-3 guidelines, utility operators ensure reliable revenue billing and protection relay performance for decades.