Outdoor single-phase epoxy resin casting combined transformer current + voltage integrated, 10kV rated, for metering and protection in single-phase power distribution systems. Complies with GB/T 17201 standard. Epoxy resin construction, good weather resistance, anti-UV, pollution class IV, suitable for outdoor installation. Integrated CT and VT design, compact structure. Customizable ratios and accuracy classes.
Outdoor combined CT+VT for 10kV single-phase systems; suitable for metering and protection in outdoor distribution.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Combined Instrument Transformer | GB/T 17201 |
| Model Code | JLDZ6-10W | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Windings | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | GB/T 17201 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
For combined transformer: ground the secondary winding at one point. For CT: never open-circuit the secondary while energized - hazardous voltage. For VT: never short-circuit the secondary while energized - dangerous overcurrent. CT secondary terminals: 1S1/1S2 (protection winding 2S1-2S2). VT secondary terminals: 1a/1n. Follow IEC 61869 / IEEE C57.13 conventions.
Compliant with: GB/T 17201
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this transformer?
A: The primary voltage is 10kV; insulation level details are [On Request].
Q: Can it be used indoors?
A: No, it is designed for outdoor installation with weather-resistant epoxy resin.
Q: What standards does it comply with?
A: It complies with GB/T 17201.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated current ratio (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSΦ=0.8 (0.2 (S)) | Accuracy class & rated output (VA) COSΦ=0.8 (0.5) | Rated Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|---|
| 5/5-75/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 100I1n | 250I1n | 75 |
| 100/5-200/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 150I1n | 375I1n | 75 |
| 300/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 31.5 | 80 | 75 |
| 400/5-600/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 63 | 130 | 75 |

Dimension & outline drawing of JLDZ6-10W — click image to zoom / view original.
This is a 10 kV outdoor single-phase combined instrument transformer that integrates current and voltage functions in one epoxy-resin-cast unit, feeding metering and protection circuits in distribution switchgear and substations. Its dry epoxy resin insulation and cast construction suit outdoor service, with a pollution class IV creepage profile for exposed locations.
The unit delivers accuracy classes 0.2 and 0.5 with a rated burden of 0.2 VA at 50/60 Hz, so secondary cabling and meter loads must be matched to that window. It follows GB/T 17201, and type and routine test reports are available [On Request]. Typical deployment is on outdoor distribution lines, pole-mounted or in box substations.
Earth the secondary at one point and bond the case; never open-circuit the current secondary or short-circuit the voltage secondary while energized. Verify polarity and ratio before energization. Custom ratios, accuracy classes and documentation packages are quoted on request, with lead time confirmed at inquiry. ⚠️ Safety: Follow the nameplate terminal diagram and ground the secondary winding at one point.
Same product family, different ratings — compare before you specify.
Outdoor Three-phase Epoxy Resin Casting Combined Transformer 10kV
JLSZV6-10W Outdoor Three-phase Epoxy Resin Casting Combined Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.
Outdoor Three-phase Epoxy Resin Casting Combined Transformer 10kV
JLSZV8-10W Outdoor Three-phase Epoxy Resin Casting Combined Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.