JLSZV6-10W Outdoor Three-phase Epoxy Resin Casting Combined Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.
Outdoor combined transformer for 10kV three-phase metering and protection; epoxy resin insulation, pollution class IV.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Combined Instrument Transformer | GB/T 17201 |
| Model Code | JLSZV6-10W | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Windings | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | GB/T 17201 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
For combined transformer: ground the secondary winding at one point. For CT: never open-circuit the secondary while energized - hazardous voltage. For VT: never short-circuit the secondary while energized - dangerous overcurrent. Terminal naming: CT secondary 1S1/1S2 (protection winding 2S1-2S2), VT secondary 1a/1n. Follow IEC 61869 / IEEE C57.13 conventions.
Compliant with: GB/T 17201
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation type and pollution class?
A: Dry epoxy resin, pollution class IV.
Q: What is the primary voltage rating?
A: 10kV.
Q: Is it suitable for outdoor installation?
A: Yes, designed for outdoor use with anti-UV properties.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated current ratio (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSΦ=0.8 0.2 (S) | Accuracy class & rated output (VA) COSΦ=0.8 0.5 | Rated Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|---|
| 5/5-75/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 100I1n | 250I1n | 75 |
| 100/5-200/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 150I1n | 375I1n | 75 |
| 300/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 31.5 | 80 | 75 |
| 400/5-600/5 | 0.2(S) 0.5 | 10 or 15 | 10 or 15 | 63 | 130 | 75 |

Dimension & outline drawing of JLSZV6-10W — click image to zoom / view original.
The JLSZV6-10W is a 10kV outdoor three-phase combined instrument transformer that integrates current and voltage measurement functions in one epoxy resin cast body, and its design and testing follow GB/T 17201. Because it occupies a single compact footprint instead of separate CT and VT units, it helps free panel and switchyard space in distribution layouts where room is tight.
The unit is available with current ratios from 5/5-75/5 up to 400/5-600/5, accuracy classes 0.2(S) and 0.5, and rated outputs of 10 or 15 VA at COSΦ=0.8; short-time thermal and dynamic ratings scale with the selected ratio, and each unit weighs 75 kg. It is intended for outdoor pole-mounted or box-substation service on 10kV distribution lines, with pollution class IV suited to exposed locations. Before energizing, verify insulation resistance, polarity and ratio, earth the secondary at one point, and never short-circuit the voltage secondary while energized.
Ratios and accuracy classes can be customized, and export packing with after-sales support is available; consult the nameplate and official datasheet for [On Request] details. ⚠️ Safety: Follow the nameplate terminal diagram and ground the secondary winding at one point.
Same product family, different ratings — compare before you specify.
Outdoor Three-phase Epoxy Resin Casting Combined Transformer 10kV
JLSZV8-10W Outdoor Three-phase Epoxy Resin Casting Combined Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.
Outdoor Single-phase Epoxy Resin Casting Combined Transformer 10kV
Outdoor single-phase epoxy resin casting combined transformer current + voltage integrated, 10kV rated, for metering and protection in single-phase power distribution systems. Complies with GB/T 17201 standard. Epoxy resin construction, good weather resistance, anti-UV, pollution class IV, suitable for outdoor installation. Integrated CT and VT design, compact structure. Customizable ratios and accuracy classes.