35kV W1 outdoor pillar type epoxy resin cast current transformer. Rated insulation level 40.5/95/185kV, 50/60Hz, secondary current 5A or 1A. Multiple accuracy class combinations: 0.2S/0.5S/10P10/10P25. Compliant with IEC 61869 and GB/T 20840 standards. Vacuum epoxy casting, high mechanical strength, excellent insulation performance. Rated primary current 50-1600A, short-time thermal current up to 50kA/4s. Suitable for 35kV power systems, customizable ratio and accuracy.
Suitable for 35kV outdoor power distribution systems requiring high accuracy metering and protection, with a rated insulation level of 40.5kV system, power-frequency withstand 95kV, lightning impulse withstand 185kV peak.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869, GB/T 20840 |
| Model Code | LZZBJ4-35W1 | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A or 1A | Ratio check at rated frequency |
| Accuracy Class | 0.2S, 0.5S, 10P10, 10P25 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 40.5/95/185kV | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869, GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | W1 outdoor pillar type epoxy resin cast | Per datasheet limits |
Ideal For
Not Recommended For
Connect secondary terminals 1S1/1S2 for metering winding, and 2S1/2S2 for protection winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure shorting links are closed before removing the burden. Follow IEC 61869 terminal markings.
Compliant with: IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 40.5kV system; power-frequency withstand 95kV; lightning impulse withstand 185kV peak.
Q: What accuracy classes are available?
A: It offers 0.2S, 0.5S for metering, and 10P10, 10P25 for protection.
Q: Can it be used indoors?
A: No, it is designed for outdoor use (W1 outdoor pillar type).
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) 0.2/0.5 | Accuracy class & rated output (VA) 0.5 | Accuracy class & rated output (VA) 10P10 | Accuracy class & rated output (VA) 10P15 | Accuracy class & rated output (VA) 10P20 | Short-time thermal current Ith (kA/s) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|
| 50;100 | 0.2/0.5/5P/10P/10P | 10 | 20 | 25 | 15 | — | 50;1/4 | 125;1/4 | 75 |
| 150;200 | 0.2/5/5P/10P/10P | 10 | 20 | 25 | 15 | — | 20;2 | 50 | 75 |
| 300;400 | 0.2/5/5P/10P/10P | 10 | 20 | 25 | 15 | — | 31.5;4 | 80 | 75 |
| 600;800 | 0.2/5/5P/10P/10P | 10 | 20 | 25 | 15 | — | 40;4 | 100 | 75 |
| 1000 | 0.2/5/5P/10P/10P | 10 | 20 | 25 | 15 | — | 50;4 | 100 | 75 |
Dimension & outline drawing of LZZBJ4-35W1 — click image to zoom / view original.
The LZZBJ4-35W1 is a 35kV outdoor post-type current transformer built to IEC 61869 and GB/T 20840, intended for metering and protection in 35kV power distribution systems. Its dry epoxy resin cast insulation, rated 40.5/95/185kV, and W1 outdoor pillar construction suit it to exposed switchyard service without an oil-filled tank.
Each unit is factory-checked through routine tests, ratio and polarity verification before dispatch. Accuracy classes 0.2S, 0.5S, 10P10 and 10P25 are available with rated output 10VA, and the parameter table lists 10VA at 0.2/0.5 and 25VA at 10P10 for the 50–1000A primary current rows. Short-time thermal current reaches 50kA/1s at 50A and 50kA/4s at 1000A, with dynamic current up to 125kA; weight is 75kg.
Deployment targets 35kV distribution and renewable-energy collector substations, where the unit is mounted on the primary pillar with P1/P2 orientation observed and the secondary earthed at one point. The secondary must never be open-circuited while energized. It is not intended for circuits above its 40.5kV insulation class. Ratio and winding configurations, documentation packages and lead times are quoted on request.
Same product family, different ratings — compare before you specify.
35kV Outdoor Epoxy Cast Post-Type Current Transformer with Protection Winding
35kV W2 outdoor pillar type epoxy resin cast current transformer. Rated insulation level 40.5/95/185kV, 50/60Hz, secondary current 5A or 1A. Multiple accuracy class combinations: 0.2S/0.5S/10P10/10P25. Compliant with IEC 61869 and GB/T 20840 standards. Vacuum epoxy casting, high mechanical strength, excellent insulation performance. Rated primary current 50-1600A, short-time thermal current up to 50kA/4s. Suitable for 35kV power systems, customizable ratio and accuracy.
35kV Indoor Epoxy Cast Post-Type Current Transformer with Protection Winding
35kV A indoor pillar type epoxy resin cast current transformer. Rated insulation level 40.5/95/185kV, 50/60Hz, secondary current 5A or 1A. Multiple accuracy class combinations: 0.2S/0.5S/10P10/10P25. Compliant with IEC 61869 and GB/T 20840 standards. Vacuum epoxy casting, high mechanical strength, excellent insulation performance. Rated primary current 50-1600A, short-time thermal current up to 50kA/4s. Suitable for 35kV power systems, customizable ratio and accuracy.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2070 I is an indoor epoxy resin casting current transformer designed for CGIS gas-insulated switchgear at 35kV. It is available with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20 and 10P20. The epoxy casting has an outer diameter of Ø205mm and a through (inner) diameter of Ø70mm for busbar installation, and is rated for 50/60Hz operation. Metering classes (0.2FS10, 0.5SFS10) and protection classes (5P10, 10P10, 5P20, 10P20) cover both measurement and relay protection inside CGIS panels.