LZZQB8-35A Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor 35kV class CT for MV switchgear, metering and protection. Rated primary 10kV, secondary 5A/1A.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZQB8-35A | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 40.5/95/185kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
connect secondary terminals 1S1/1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 40.5/95/185kV, meaning 40.5kV system voltage, 95kV power-frequency withstand, 185kV lightning impulse withstand.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only.
Q: What secondary currents are available?
A: Secondary current is 5A or 1A, as specified.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 0.2 (S)/0.5S | Accuracy class & rated output (VA) COSφ=0.8 0.5 | Accuracy class & rated output (VA) COSφ=0.8 5P10 | Accuracy class & rated output (VA) COSφ=0.8 5P15 | Accuracy class & rated output (VA) COSφ=0.8 5P20 | Short-time thermal currentIth (kA/S) kA | Short-time thermal currentIth (kA/S) s | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 4 | 1 | 10 | 70 |
| 30-40 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 4 | 2 | 10 | 70 |
| 50 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 12 | 1 | 30 | 70 |
| 75 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 16 | 1 | 40 | 70 |
| 100-150 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 25 | 1 | 63 | 70 |
| 200-300 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 31.5 | 1 | 80 | 70 |
| 400-600 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 31.5 | 2 | 80 | 70 |
| 800-1600 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 31.5 | 4 | 130 | 70 |
| 2000-2500 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 15 | 31.5 | 4 | 130 | 70 |
Dimension & outline drawing of LZZQB8-35A — click image to zoom / view original.
The LZZQB8-35A is a 35kV indoor single-phase epoxy resin cast current transformer, built for revenue metering and protection on 50/60Hz systems where the accuracy class directly affects billing settlement. Its dry epoxy body and wound core construction suit panel interiors where space is at a premium, and the compact footprint helps simplify switchgear layout.
The unit is offered with 0.2, 0.5 and 5P accuracy classes, a rated burden of 10VA and a 40.5/95/185kV insulation level, with a mass of 70kg. Standard ratios cover 20A to 2500A; short-time thermal current reaches 31.5kA for 1 to 4 seconds and dynamic stability 130kA at the upper ratios, so protection cores resist saturation under fault current. Standard catalogue ratios are stocked; non-standard ratios and class combinations are quoted on request.
Compliance follows the GB/T 20840 series, with routine and type test evidence available [On Request]. Typical deployment is indoor wind, photovoltaic and storage step-up collection systems. Earth the secondary at one point and never open-circuit it while energized. Harmonic-rich loads may require derating; verify the nameplate before commissioning.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZQB8-35B Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZQB8-35-B) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 40.5/95/185kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Optional primary current covers 20–3150A; accuracy-class rated outputs:10VA(0.2S/0.5S),30VA(0.5),30VA(5P10),20VA(5P15),15VA(5P20); short-time thermal current ranges 4–31.5kA, rated dynamic stable current ranges 10–130kA; product weight:78kg; ambient operating temperature -5℃~+40℃.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZQB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZQB8-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.