Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards; rated insulation level 40.5/95/185kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Optional primary current covers 20–3150A; accuracy-class rated outputs:10VA(0.2S/0.5S),30VA(0.5),30VA(5P10),20VA(5P15),15VA(5P20); short-time thermal current ranges 4–31.5kA, rated dynamic stable current ranges 10–130kA; product weight:78kg; ambient operating temperature -5℃~+40℃.
Indoor 35kV epoxy cast CT for MV switchgear metering and protection; rated insulation 40.5kV system, power-frequency withstand 95kV, lightning impulse 185kV peak.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZQB8-35-G | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 for metering, 2S1-2S2 for protection (if applicable). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: Rated insulation level is 40.5/95/185kV, meaning 40.5kV system voltage, 95kV power-frequency withstand, 185kV lightning impulse withstand.
Q: Can it be used outdoors?
A: No, it is designed for indoor use only due to epoxy resin construction.
Q: What secondary currents are available?
A: Rated secondary current is 5A or 1A, as specified.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSΦ=0.8 (0.2/0.5S) | Accuracy class & rated output (VA) COSΦ=0.8 (0.5) | Accuracy class & rated output (VA) COSΦ=0.8 (5P10) | Accuracy class & rated output (VA) COSΦ=0.8 (5P15) | Accuracy class & rated output (VA) COSΦ=0.8 (5P20) | Short-time thermal current Ith (kA/S) (kA) | Short-time thermal current Ith (kA/S) (s) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 0.2(S)/0.5(S) | 10 | 30 | 30 | 20 | 15 | 4 | 1 | 10 | 78 |
| 30-40 | 0.2(S)/5P | 10 | 30 | 30 | 20 | 15 | 4 | 2 | 10 | 78 |
| 50 | 0.5(S)/5P | 10 | 30 | 30 | 20 | 15 | 12 | 1 | 30 | 78 |
| 75 | 0.5(S)/5P | 10 | 30 | 30 | 20 | 15 | 16 | 1 | 40 | 78 |
| 100-150 | 0.2(S)/0.5(S)/5P | 10 | 30 | 30 | 20 | 15 | 25 | 1 | 63 | 78 |
| 200-300 | 0.2(S)/5P/5P | 10 | 30 | 30 | 20 | 15 | 31.5 | 1 | 80 | 78 |
| 400-600 | 0.5(S)/5P/5P | 10 | 30 | 30 | 20 | 15 | 31.5 | 2 | 80 | 78 |
| 800-1600 | [On Request] | 10 | 30 | 30 | 20 | 15 | 31.5 | 4 | 130 | 78 |
| 2000-3150 | [On Request] | 10 | 30 | 30 | 20 | 15 | [On Request] | [On Request] | [On Request] | 78 |
Dimension & outline drawing of LZZQB8-35-G — click image to zoom / view original.
This is a 35 kV indoor single-phase current transformer whose dry epoxy resin casting is the defining feature: the solid insulation removes the oil-handling and leakage concerns of liquid-filled designs and suits it to enclosed switchgear. The winding architecture covers metering and protection duties, with accuracy classes 0.2(S), 0.5(S) and 5P available and a rated burden of 10 VA at 50/60 Hz.
Selection within the range turns on winding count: a single metering core, a metering-plus-protection combination, or a residual-voltage winding where earth-fault detection is needed. Compliance evidence and test documentation are available [On Request]. Typical deployment is in indoor substation bays for current measurement and protection.
Before energising, verify insulation resistance, polarity and ratio by handover test, earth the secondary at one point and follow the nameplate terminal diagram. The secondary must never be open-circuited while the primary is energised. DC or non-standard frequencies are outside its intended use. Ratio and accuracy-class variants, OEM branding and document packages are quoted on request, with weight and short-time ratings confirmed against the nameplate.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZQB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZQB8-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZQB8-35A Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZQB8-35B Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZQB8-35-B) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.