CGIS1255 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, accuracy class 0.2,0.5,1.0, rated burden 30VA / 60VA / 150VA. Design: insulation level 24/65/125kV,18/55/105kV, Dry Epoxy Resin, 50Hz or 60Hz operation.
CGIS1255 is a 20kV indoor epoxy resin current transformer for CGIS, ideal for metering and protection up to 24kV systems.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS1255 | Factory nameplate marking |
| Primary Voltage | 20kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | 0.2,0.5,1.0 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 30VA / 60VA / 150VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 24/65/125kV,18/55/105kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50Hz or 60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 and IEEE C57.13 terminal conventions.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of CGIS1255?
A: The insulation level is 24/65/125kV, meaning 24kV maximum system voltage, 65kV power-frequency withstand, and 125kV lightning impulse withstand. An alternative 18/55/105kV is also available.
Q: What are the available accuracy classes?
A: Accuracy classes 0.2, 0.5, and 1.0 are available, suitable for metering and protection.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only, specifically for CGIS gas insulated switchgear.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 800 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 0.2FS10/0.5FS10 | 2.5 | — | — | 105 | 75 | 50 | 40 | 35 | 30 | 35 | 35 |
| 5 | — | — | 120 | 70 | 55 | 45 | 35 | 35 | 35 | 35 | |
| 7.5 | — | — | 95 | 70 | 55 | 45 | 45 | 45 | 40 | 40 | |
| 10 | — | — | 115 | 80 | 65 | 50 | 50 | 50 | 45 | 45 | |
| 15 | — | — | 110 | 90 | 65 | 60 | 60 | 60 | 55 | 55 | |
| 20 | — | — | 140 | 110 | 75 | 70 | 65 | 65 | 65 | 65 | |
| 25 | — | — | 135 | 90 | 80 | 70 | 70 | 70 | 70 | 70 | |
| 30 | — | — | 105 | 85 | 80 | 80 | 80 | 80 | 80 | 80 | |
| 0.5FS10 | 2.5 | — | 80 | 60 | 50 | 45 | 35 | 35 | 25 | 25 | 25 |
| 5 | — | 130 | 90 | 75 | 60 | 45 | 40 | 30 | 30 | 25 | |
| 7.5 | — | — | 120 | 100 | 75 | 60 | 50 | 40 | 35 | 30 | |
| 10 | — | — | 125 | 95 | 75 | 80 | 45 | 35 | 30 | 30 | |
| 15 | — | — | 125 | 105 | 80 | 65 | 55 | 55 | 55 | 55 | |
| 20 | — | — | 130 | 100 | 75 | 55 | 40 | 40 | 40 | 40 | |
| 25 | — | — | 120 | 90 | 65 | 45 | 45 | 45 | 45 | 45 | |
| 30 | — | — | 105 | 75 | 60 | 50 | 50 | 50 | 50 | 50 | |
| 5P10/10P10 | 2.5 | 110 | 80 | 70 | 60 | 45 | 40 | 35 | 40 | 35 | 35 |
| 5 | — | 130 | 110 | 90 | 70 | 60 | 50 | 45 | 45 | 45 | |
| 7.5 | — | — | 125 | 95 | 75 | 70 | 65 | 60 | 50 | 50 | |
| 10 | — | — | 115 | 95 | 85 | 80 | 70 | 60 | 60 | 60 | |
| 15 | — | — | 135 | 115 | 110 | 90 | 80 | 80 | 80 | 80 | |
| 20 | — | — | 135 | 115 | 110 | 90 | 80 | 80 | 80 | 80 | |
| 25 | — | — | 135 | 115 | 110 | 90 | 80 | 80 | 80 | 80 | |
| 30 | — | — | 135 | 115 | 110 | 90 | 80 | 80 | 80 | 80 | |
| 5P15/10P15 | 2.5 | — | 110 | 95 | 80 | 65 | 55 | 50 | 50 | 45 | 45 |
| 5 | — | — | 125 | 100 | 85 | 75 | 70 | 65 | 60 | 60 | |
| 7.5 | — | — | 135 | 115 | 100 | 95 | 85 | 85 | 75 | 75 | |
| 10 | — | — | 125 | 115 | 100 | 85 | 85 | 85 | 85 | 85 | |
| 15 | — | — | 135 | 115 | 100 | 85 | 85 | 85 | 85 | 85 | |
| 5P20/10P20 | 2.5 | — | 140 | 130 | 110 | 85 | 75 | 70 | 65 | 60 | 55 |
| 5 | — | — | 135 | 115 | 100 | 95 | 85 | 85 | 75 | 75 | |
| 7.5 | — | — | 125 | 115 | 95 | 85 | 85 | 85 | 85 | 85 | |
| 10 | — | — | 140 | 115 | 95 | 85 | 85 | 85 | 85 | 85 |
Dimension & outline drawing of CGIS1255 — click image to zoom / view original.
This is an indoor epoxy resin cast current transformer for 20 kV gas insulated switchgear, converting primary current to a measurable secondary signal. The dry epoxy body provides the insulation, with an outer diameter of Φ125mm and an inner diameter of Φ55mm for busbar passage. Accuracy classes 0.2, 0.5 and 1.0 are available with rated burdens of 30VA, 60VA and 150VA, and the insulation level is 24/65/125kV or 18/55/105kV at 50Hz or 60Hz. The 0.2FS10/0.5FS10 rows show composite metering and protection performance, with burden capability extending across the tabulated current range.
This unit is intended for indoor installation in medium-voltage switchgear and ring-main units, not for outdoor service. Primary connections follow the P1/P2 polarity marks, and the secondary circuit must be earthed at one point and never open-circuited while energized. Before commissioning, verify ratio, polarity and wiring against the nameplate terminal diagram. Compliance follows the GB/T 20840 series, with test certificates and routine reports available [On Request].
Ratios and accuracy classes can be customized to the switchgear scheme, and the documentation package is quoted with the order. Delivery schedules and formal quotations are provided on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.