中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTCGIS1780-I
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kVCGIS1780-I
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 35kV
Secondary Metering (1S1 - 1S2): ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:CGIS1780-I

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • Indoor epoxy resin casting current transformer for CGIS
  • outer diameter Φ168mm
  • inner diameter Φ80mm
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: CGIS1780-I

Electrical Parameters

Primary Rated Voltage (Un):35kV
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor CT for CGIS at 35kV; suitable for protection and metering in gas-insulated switchgear.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeCGIS1780-IFactory nameplate marking
Primary Voltage35kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 35kV gas-insulated switchgear (CGIS) applications
  • Indoor installation with dry epoxy resin insulation
  • Protection and metering circuits requiring multiple accuracy classes
  • 50/60Hz power systems

Not Recommended For

  • Outdoor installations without additional enclosure
  • Voltage transformation (not a PT)
  • Systems above 35kV
  • Oil or SF6 insulated equipment (not compatible)

Topology & Wiring

connect secondary terminals 1S1/1S2 for main metering/protection; if dual secondary, use 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The primary voltage is 35kV, but insulation level shorthand is not provided; please refer to detailed specs or contact us.

Q: Can this CT be used outdoors?

A: No, it is designed for indoor use within CGIS.

Q: What are the available accuracy classes?

A: Multiple accuracy classes are available; specific values are not listed in the provided data.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

CGIS1780-I
34 cols · 34 rows

CGIS1780 I Current Transformer for Gas-Insulated Switchgear — Technical Data

Accuracy classRated output (VA)4050607510012515020025030040050060075010001200
hlhlhlhlhlhlhlhlhlhlhlhlhlhlhlhl
0.2FS10 0.5FS102.5—————————————6555403530303030303035353535—————
0.2FS10 0.5FS105—————————————9580555035303030303035353535—————
0.2FS10 0.5FS1010—————————————1208060453535303035353535———————
0.2FS10 0.5FS1015—————————————17011075554540353535353535———————
0.2FS10 0.5FS1020—————————————1459065554540353540403535———————
0.2FS10 0.5FS1025—————————————1601107560504545403535—————————
0.2FS10 0.5FS1030———————————————125857055504545404040———————
0.52.5—————————————554540353030252525252525———————
0.55—————————————806550403030252525252525———————
0.510—————————————1259575554035302525252525———————
0.515—————————————1259570554540353025252525———————
0.520—————————————1208565555040303530252525———————
0.525———————————————95756555453530252525———————
0.530———————————————85706550403530252525———————
5(10)P102.513510085755545403535603030303030303030303030302525————————
5(10)P105———135120857055504540403535353535353535353030—————————
5(10)P1010—————145110958070606050454535353535353535353535———————
5(10)P1015———————155130110908065605045404040404040404040———————
5(10)P1020—————————14011510085706050454040404040404040———————
5(10)P1025———————————1401209580706055505050505050505050—————
5(10)P1030—————————————14013011095806560555555555555555555———
5(10)P202.5———145125907565605050504540404040404040404040404040404040404040
5(10)P205—————14511595907565555050505050505050505050505050505050505050
5(10)P2010———————150125110105857570605555555555555555555555555555555555
5(10)P2015—————————15014011510090757065656565656565656565656565656565
5(10)P2020———————————145125115908075707070707070707070707070707070
5(10)P2025—————————————150135105958585858585858585858585858585—
5(10)P2030———————————————15013510595858585858585858585858585—
5(10)P302.5—————13010590857570655555555555555555555555555555555555555555
5(10)P305———————145135115100958075757575757575757575757575757575757575
5(10)P3010—————————170155125115110908080808080808080808080808080808080
5(10)P3015———————————155140115100100100100100100100100100100100100100100100100100100
5(10)P3020——————————————140125115115115115115115115115115115115115115115115—
5(10)P3025—————————————————145145145145145145145145145145145145145145—
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of CGIS1780-I — click image to zoom / view original.

Product Overview

About This Product

CGIS1780-I

This is an indoor epoxy resin casting current transformer for 35kV CGIS gas insulated switchgear, mounted in the switchgear compartment to step primary current down to a measurable secondary signal for protection and metering.

The insulation is a dry cast epoxy resin body with an outer diameter of Φ168mm and an inner diameter of Φ80mm, built for 50/60Hz service. Accuracy classes 0.2FS10 and 0.5FS10 are available, with rated outputs spanning 2.5VA to 30VA depending on class and burden; for example, class 0.5 at 10VA delivers 125VA at 150h and 95VA at 200h, tapering to 25VA across the higher primary ratings. Because it carries no primary fuses, protection coordination relies on the upstream interrupting device rather than a CT-integral fuse, which suits switchgear where fault clearing is already handled elsewhere.

It is intended for medium-voltage switchgear and ring main unit applications indoors, never outdoor exposure. Before energising, verify insulation resistance, polarity and ratio; earth the secondary at one point and never open-circuit it while energised. Non-sinusoidal loads require derating [On Request]. Custom ratios, accuracy classes, documentation packages and export packing are quoted on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1780 II Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-II

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 II Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-II) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS2070 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2070-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2070 I is an indoor epoxy resin casting current transformer designed for CGIS gas-insulated switchgear at 35kV. It is available with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20 and 10P20. The epoxy casting has an outer diameter of Ø205mm and a through (inner) diameter of Ø70mm for busbar installation, and is rated for 50/60Hz operation. Metering classes (0.2FS10, 0.5SFS10) and protection classes (5P10, 10P10, 5P20, 10P20) cover both measurement and relay protection inside CGIS panels.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1765

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs