Special current transformer for CGIS inflatable cabinets, multiple accuracy grades and primary current specifications available, customizable lead length and stackable product height.
CGIS1455 is a dry-type current transformer for 35kV inflatable switchgear, ideal for metering and protection in RMU applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS1455 | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect secondary terminals 1S1/1S2 for main metering/protection winding; if dual ratio, use 2S1-2S2 for additional winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point only to avoid circulating currents.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating?
A: The primary voltage is 35kV.
Q: Can the secondary lead length be customized?
A: Yes, the secondary outgoing length is customizable.
Q: Is this CT suitable for outdoor use?
A: No, it is designed for indoor inflatable switchgear (CGIS) applications.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | Rated primary current (A) | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 40 | 50 | 60 | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | ||
| 0.2FS10/0.5FS10 | 2.5 | — | — | — | — | — | 85 | 80 | 50 | 35 | 30 | 30 | 30 | 30 |
| 0.2FS10/0.5FS10 | 5 | — | — | — | — | — | 130 | 90 | 70 | 50 | 40 | 35 | 30 | 30 |
| 0.2FS10/0.5FS10 | 10 | — | — | — | — | — | — | 150 | 115 | 75 | 55 | 45 | 35 | 30 |
| 0.2FS10/0.5FS10 | 15 | — | — | — | — | — | — | — | 160 | 100 | 70 | 55 | 45 | 40 |
| 0.2FS10/0.5FS10 | 20 | — | — | — | — | — | — | — | 125 | 85 | 55 | 45 | 35 | 35 |
| 0.2FS10/0.5FS10 | 25 | — | — | — | — | — | — | — | — | 105 | 70 | 55 | 45 | 40 |
| 0.2FS10/0.5FS10 | 30 | — | — | — | — | — | — | — | — | 120 | 85 | 70 | 55 | 50 |
| 0.5FS10 | 2.5 | — | — | 115 | 80 | 50 | 40 | 35 | 30 | 30 | 25 | 25 | 25 | — |
| 0.5FS10 | 5 | — | — | — | 120 | 75 | 60 | 45 | 35 | 30 | 30 | 25 | 25 | — |
| 0.5FS10 | 10 | — | — | — | — | 120 | 90 | 70 | 50 | 40 | 35 | 30 | 30 | — |
| 0.5FS10 | 15 | — | — | — | — | — | 120 | 90 | 65 | 55 | 45 | 35 | 30 | — |
| 0.5FS10 | 20 | — | — | — | — | — | — | 115 | 80 | 55 | 50 | 40 | 35 | 35 |
| 0.5FS10 | 25 | — | — | — | — | — | — | — | 140 | 90 | 75 | 65 | 55 | 45 |
| 0.5FS10 | 30 | — | — | — | — | — | — | — | 160 | 105 | 85 | 70 | 65 | 50 |
| 5P10/10P10 | 2.5 | 135 | 100 | 85 | 75 | 55 | 45 | 40 | 35 | 30 | 30 | 30 | 30 | 30 |
| 5P10/10P10 | 5 | 235 | 170 | 135 | 120 | 85 | 70 | 55 | 50 | 45 | 40 | 40 | 35 | 35 |
| 5P10/10P10 | 10 | — | — | — | 235 | 210 | 145 | 110 | 95 | 80 | 80 | 60 | 50 | 45 |
| 5P10/10P10 | 15 | — | — | — | — | — | 205 | 155 | 130 | 110 | 90 | 80 | 85 | 60 |
| 5P10/10P10 | 20 | — | — | — | — | — | 265 | 200 | 165 | 140 | 115 | 100 | 95 | 80 |
| 5P10/10P10 | 25 | — | — | — | — | — | — | 245 | 200 | 170 | 140 | 120 | 115 | 80 |
| 5P10/10P10 | 30 | — | — | — | — | — | — | — | 235 | 200 | 185 | 140 | 130 | 110 |
| 5P15/10P15 | 2.5 | 170 | 135 | 115 | 95 | 75 | 60 | 50 | 40 | 40 | 40 | 35 | 35 | 35 |
| 5P15/10P15 | 5 | 220 | 185 | 145 | 115 | 90 | 75 | 70 | 60 | 55 | 55 | 45 | 45 | 45 |
| 5P15/10P15 | 10 | — | — | — | — | 270 | 200 | 160 | 130 | 115 | 95 | 85 | 70 | 60 |
| 5P15/10P15 | 15 | — | — | — | — | — | 220 | 180 | 150 | 135 | 115 | 110 | 90 | 80 |
| 5P15/10P15 | 20 | — | — | — | — | — | — | 230 | 205 | 170 | 145 | 135 | 110 | 100 |
| 5P15/10P15 | 25 | — | — | — | — | — | — | — | 255 | 205 | 175 | 160 | 130 | 115 |
| 5P15/10P15 | 30 | — | — | — | — | — | — | — | — | 240 | 205 | 190 | 155 | 130 |
| 5P20/10P20 | 2.5 | 220 | 175 | 145 | 125 | 90 | 75 | 85 | 60 | 50 | 50 | 50 | 45 | 40 |
| 5P20/10P20 | 5 | — | — | 235 | 200 | 145 | 115 | 90 | 75 | 70 | 65 | 55 | 50 | 45 |
| 5P20/10P20 | 10 | — | — | — | — | 255 | 200 | 165 | 150 | 125 | 110 | 105 | 85 | 75 |
| 5P20/10P20 | 15 | — | — | — | — | — | — | — | 235 | 215 | 175 | 150 | 140 | 115 |
| 5P20/10P20 | 20 | — | — | — | — | — | — | — | — | 225 | 195 | 175 | 145 | 125 |
| 5P20/10P20 | 25 | — | — | — | — | — | — | — | — | — | 235 | 215 | 175 | 150 |
| 5P20/10P20 | 30 | — | — | — | — | — | — | — | — | — | — | 250 | 205 | 175 |
| 5P30/10P30 | 2.5 | — | — | 250 | 205 | 175 | 130 | 105 | 90 | 85 | 75 | 70 | 65 | 55 |
| 5P30/10P30 | 5 | — | — | — | 265 | 210 | 165 | 145 | 135 | 115 | 110 | 95 | 80 | 75 |
| 5P30/10P30 | 10 | — | — | — | — | — | — | 255 | 235 | 195 | 170 | 155 | 125 | 115 |
| 5P30/10P30 | 15 | — | — | — | — | — | — | — | — | 265 | 245 | 215 | 170 | 155 |
| 5P30/10P30 | 20 | — | — | — | — | — | — | — | — | — | 275 | 215 | 195 | — |
| 5P30/10P30 | 25 | — | — | — | — | — | — | — | — | — | — | 270 | 235 | — |
| 5P30/10P30 | 30 | — | — | — | — | — | — | — | — | — | — | — | 275 | — |
Dimension & outline drawing of CGIS1455 — click image to zoom / view original.
This current transformer is built for inflatable switchgear at 35 kV, measuring primary current for protection and metering in compact ring-main and medium-voltage cubicles. Its dry epoxy resin insulation and stackable coil construction let the height grow with the number of cores, so the unit occupies minimal panel space in dense switchrooms.
Accuracy classes 0.2FS10/0.5FS10 and 0.5FS10 are available with rated outputs from 2.5 VA to 30 VA; for example, 0.2FS10/0.5FS10 at 5 VA is rated 130 A at 125 A primary and 30 A at 600 A primary. Within the family, choose the 0.2FS10/0.5FS10 rows where dual-class metering and protection are needed, and 0.5FS10 rows for metering alone. Compliance follows IEC 61869; test certificates and routine reports are available [On Request].
Typical deployment is in medium-voltage switchgear, ring-main units and centre-mounted cubicles. Earth the secondary at one point and bond it to the cubicle earth; never open-circuit the secondary while energized. DC or non-standard frequencies are not applicable. Ratios, secondary lead length and documentation packages are customized; quote and lead time follow inquiry.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.