CGIS1580 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, accuracy class 0.2/0.5/6P(3P), rated burden 15VA / 20VA / 100VA. Design: insulation level 24/65/125kV,18/55/105kV, Dry Epoxy Resin, 50Hz or 60Hz operation.
Indoor epoxy resin CT for CGIS at 20kV, 50/60Hz, with multiple accuracy and burden options.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS1580 | Factory nameplate marking |
| Primary Voltage | 20kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | 0.2/0.5/6P(3P) | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 15VA / 20VA / 100VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 24/65/125kV,18/55/105kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50Hz or 60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the window. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 24/65/125kV and 18/55/105kV, meaning for 24kV system, power-frequency withstand 65kV and lightning impulse 125kV peak; for 18kV system, 55kV and 105kV respectively.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use with epoxy resin insulation, suitable for CGIS switchgear.
Q: What are the available accuracy classes?
A: Accuracy classes include 0.2, 0.5, and 6P(3P) for metering and protection.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 600 | 600 | 750 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 0.2FS10/0.5FS10 | 2.5 | — | — | 135 | 105 | 65 | 45 | 40 | 30 | 30 | 30 | 30 |
| 0.2FS10/0.5FS10 | 5 | — | — | — | — | 65 | 65 | 50 | 40 | 35 | 35 | 30 |
| 0.2FS10/0.5FS10 | 7.5 | — | — | — | 130 | 85 | 65 | 50 | 40 | 40 | 35 | 30 |
| 0.2FS10/0.5FS10 | 10 | — | — | — | 105 | 80 | 60 | 50 | 45 | 40 | 40 | 35 |
| 0.2FS10/0.5FS10 | 15 | — | — | — | 140 | 105 | 80 | 60 | 50 | 55 | 45 | 40 |
| 0.2FS10/0.5FS10 | 20 | — | — | — | — | — | 130 | 95 | 75 | 65 | 55 | 50 |
| 0.2FS10/0.5FS10 | 25 | — | — | — | — | — | — | 115 | 90 | 75 | 65 | 60 |
| 0.2FS10/0.5FS10 | 30 | — | — | — | — | — | — | 135 | 100 | 85 | 70 | 65 |
| 0.5FS10 | 2.5 | — | 105 | 70 | 55 | 45 | 35 | 25 | 25 | 25 | 25 | 25 |
| 0.5FS10 | 5 | — | — | 110 | 85 | 60 | 50 | 45 | 35 | 30 | 30 | 25 |
| 0.5FS10 | 7.5 | — | — | 105 | 75 | 60 | 55 | 40 | 35 | 30 | 25 | 25 |
| 0.5FS10 | 10 | — | — | 130 | 80 | 75 | 65 | 45 | 40 | 35 | 30 | 25 |
| 0.5FS10 | 15 | — | — | — | 125 | 100 | 85 | 60 | 50 | 45 | 30 | 30 |
| 0.5FS10 | 20 | — | — | — | — | 125 | 105 | 75 | 65 | 50 | 35 | 35 |
| 0.5FS10 | 25 | — | — | — | — | — | 125 | 90 | 75 | 55 | 40 | 40 |
| 0.5FS10 | 30 | — | — | — | — | — | — | 105 | 85 | 65 | 45 | 45 |
| 5P10/10P10 | 2.5 | 125 | 90 | 80 | 65 | 50 | 45 | 40 | 35 | 35 | 30 | 30 |
| 5P10/10P10 | 5 | — | 140 | 125 | 105 | 75 | 65 | 55 | 45 | 40 | 40 | 40 |
| 5P10/10P10 | 7.5 | — | — | — | 105 | 85 | 70 | 60 | 55 | 50 | 45 | 40 |
| 5P10/10P10 | 10 | — | — | — | 130 | 105 | 85 | 70 | 70 | 60 | 55 | 45 |
| 5P10/10P10 | 15 | — | — | — | — | 140 | 120 | 95 | 80 | 70 | 70 | 60 |
| 5P10/10P10 | 20 | — | — | — | — | — | 120 | 115 | 100 | 85 | 80 | 80 |
| 5P10/10P10 | 25 | — | — | — | — | — | — | 135 | 115 | 100 | 85 | 85 |
| 5P10/10P10 | 30 | — | — | — | — | — | — | — | 135 | 115 | 100 | 100 |
| 5P20/10P20 | 2.5 | — | 140 | 120 | 95 | 80 | 70 | 60 | 60 | 50 | 50 | 50 |
| 5P20/10P20 | 5 | — | — | — | 120 | 105 | 90 | 85 | 75 | 65 | 60 | 60 |
| 5P20/10P20 | 7.5 | — | — | — | — | 140 | 120 | 110 | 95 | 85 | 80 | 80 |
| 5P20/10P20 | 10 | — | — | — | — | — | — | 135 | 115 | 115 | 100 | 100 |
| 5P20/10P20 | 15 | — | — | — | — | — | — | — | 135 | 115 | 115 | 100 |
| 5P30/10P30 | 1.5 | — | — | 140 | 110 | 95 | 80 | 75 | 70 | 65 | 60 | 60 |
| 5P30/10P30 | 2.5 | — | — | — | 120 | 105 | 95 | 85 | 85 | 75 | 70 | 70 |
| 5P30/10P30 | 5 | — | — | — | — | — | — | 130 | 110 | 100 | 100 | 100 |
| 5P30/10P30 | 7.5 | — | — | — | — | — | — | — | 145 | 130 | 120 | 120 |
Dimension & outline drawing of CGIS1580 — click image to zoom / view original.
The CGIS1580 is an indoor epoxy resin cast current transformer for 20 kV CGIS gas insulated switchgear, measuring primary current for protection and metering in medium-voltage switchboards. Its dry epoxy body carries the primary and secondary windings, with accuracy classes 0.2/0.5/6P(3P) and rated burdens of 15VA, 20VA and 100VA, at 50Hz or 60Hz. Insulation levels are 24/65/125kV and 18/55/105kV, and the ring measures Φ145mm outer and Φ80mm inner.
Secondary current, terminal designations and the ratio schedule are stated on the nameplate and datasheet [On Request]. Select this model when the switchgear bay needs a compact ring-type CT with 20 kV class insulation; other ratios and classes in the family are chosen per the ratio table. Documentation includes the datasheet, outline drawing and type test reports [On Request].
Typical deployment is indoor collector and booster stations for wind, photovoltaic and storage, inside CGIS cubicles. Earth the secondary at one point, follow the terminal diagram, and never open-circuit the secondary while energized. It is not for outdoor open-air installation. Ratio and class customization, samples and type test support are available on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.