KEMA & ISO 9001/14001 Certified|Exporting to 50+ Countries (IEC 61869-3 / IEEE C57.13)
24/7 Global Engineering Hotline: 86 18852046268|sales@potentialtransformers.com
中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTCGIS1580
CGIS1580 Current Transformer Applied to CGIS Gas Insulated Switchgear
20kVCGIS1580
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 20kV
Secondary Metering (1S1 - 1S2): (0.2/0.5/6P(3P))
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:CGIS1580

CGIS1580 Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1580 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, accuracy class 0.2/0.5/6P(3P), rated burden 15VA / 20VA / 100VA. Design: insulation level 24/65/125kV,18/55/105kV, Dry Epoxy Resin, 50Hz or 60Hz operation.

Key Engineering Advantages

  • Indoor epoxy resin casting current transformer for CGIS
  • outer diameter Φ145mm
  • inner diameter Φ80mm
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: CGIS1580

Electrical Parameters

Primary Rated Voltage (Un):20kV
Metering & Protection Class:0.2/0.5/6P(3P)
Rated Output Burden:15VA / 20VA / 100VA
Rated Frequency:50Hz or 60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):24/65/125kV,18/55/105kV
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor epoxy resin CT for CGIS at 20kV, 50/60Hz, with multiple accuracy and burden options.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeCGIS1580Factory nameplate marking
Primary Voltage20kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class0.2/0.5/6P(3P)Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden15VA / 20VA / 100VABurden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)24/65/125kV,18/55/105kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50Hz or 60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • CGIS gas insulated switchgear
  • Indoor medium voltage switchgear
  • Metering and protection applications
  • 20kV systems

Not Recommended For

  • Outdoor installations
  • High voltage above 24kV
  • Oil-immersed transformers
  • DC systems

Topology & Wiring

Connect primary through the window. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The insulation level is 24/65/125kV and 18/55/105kV, meaning for 24kV system, power-frequency withstand 65kV and lightning impulse 125kV peak; for 18kV system, 55kV and 105kV respectively.

Q: Can this CT be used outdoors?

A: No, it is designed for indoor use with epoxy resin insulation, suitable for CGIS switchgear.

Q: What are the available accuracy classes?

A: Accuracy classes include 0.2, 0.5, and 6P(3P) for metering and protection.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

CGIS1580
13 cols · 33 rows

CGIS1580 Current Transformer for Gas-Insulated Switchgear — Technical Data

Accuracy classRated output (VA)75100125150200250300400600600750
0.2FS10/0.5FS102.5——13510565454030303030
0.2FS10/0.5FS105————65655040353530
0.2FS10/0.5FS107.5———13085655040403530
0.2FS10/0.5FS1010———10580605045404035
0.2FS10/0.5FS1015———140105806050554540
0.2FS10/0.5FS1020—————1309575655550
0.2FS10/0.5FS1025——————11590756560
0.2FS10/0.5FS1030——————135100857065
0.5FS102.5—105705545352525252525
0.5FS105——1108560504535303025
0.5FS107.5——1057560554035302525
0.5FS1010——1308075654540353025
0.5FS1015———125100856050453030
0.5FS1020————1251057565503535
0.5FS1025—————1259075554040
0.5FS1030——————10585654545
5P10/10P102.512590806550454035353030
5P10/10P105—14012510575655545404040
5P10/10P107.5———10585706055504540
5P10/10P1010———130105857070605545
5P10/10P1015————1401209580707060
5P10/10P1020—————120115100858080
5P10/10P1025——————1351151008585
5P10/10P1030———————135115100100
5P20/10P202.5—1401209580706060505050
5P20/10P205———120105908575656060
5P20/10P207.5————14012011095858080
5P20/10P2010——————135115115100100
5P20/10P2015———————135115115100
5P30/10P301.5——14011095807570656060
5P30/10P302.5———120105958585757070
5P30/10P305——————130110100100100
5P30/10P307.5———————145130120120
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of CGIS1580 — click image to zoom / view original.

Product Overview

About This Product

CGIS1580

The CGIS1580 is an indoor epoxy resin cast current transformer for 20 kV CGIS gas insulated switchgear, measuring primary current for protection and metering in medium-voltage switchboards. Its dry epoxy body carries the primary and secondary windings, with accuracy classes 0.2/0.5/6P(3P) and rated burdens of 15VA, 20VA and 100VA, at 50Hz or 60Hz. Insulation levels are 24/65/125kV and 18/55/105kV, and the ring measures Φ145mm outer and Φ80mm inner.

Secondary current, terminal designations and the ratio schedule are stated on the nameplate and datasheet [On Request]. Select this model when the switchgear bay needs a compact ring-type CT with 20 kV class insulation; other ratios and classes in the family are chosen per the ratio table. Documentation includes the datasheet, outline drawing and type test reports [On Request].

Typical deployment is indoor collector and booster stations for wind, photovoltaic and storage, inside CGIS cubicles. Earth the secondary at one point, follow the terminal diagram, and never open-circuit the secondary while energized. It is not for outdoor open-air installation. Ratio and class customization, samples and type test support are available on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs