CGIS2180 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Indoor epoxy resin CT for 35kV CGIS switchgear; multiple accuracy and burden options.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS2180 | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2 if applicable). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 and IEEE C57.13 terminal conventions.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating?
A: 35kV.
Q: What is the insulation type?
A: Dry epoxy resin.
Q: What are the dimensions?
A: Outer diameter Φ210mm, inner diameter Ø80mm.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | Rated primary current (A) | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 40 | 50 | 60 | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 750 | 1000 | 1200 | ||
| 0.2S FS10 | 2.5 | — | — | — | — | 85 | 60 | 50 | 35 | 30 | 30 | 30 | 30 | 35 | 35 | 35 | 35 |
| 0.2 FS10 | 5 | — | — | — | — | 130 | 90 | 70 | 50 | 40 | 35 | 30 | 30 | 30 | 35 | 35 | 35 |
| 0.5 FS10 | 10 | — | — | — | — | — | 150 | 115 | 75 | 55 | 45 | 35 | 35 | 30 | 35 | 35 | 35 |
| 0.5 FS10 | 15 | — | — | — | — | — | 160 | 100 | 70 | 55 | 45 | 40 | 35 | 35 | 35 | 35 | 35 |
| 0.5 FS10 | 2.5 | — | — | 115 | 80 | 50 | 40 | 35 | 30 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | — |
| 0.5 FS10 | 5 | — | — | 120 | 75 | 60 | 45 | 35 | 30 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | — |
| 0.5 FS10 | 10 | — | — | — | 120 | 90 | 70 | 50 | 40 | 35 | 30 | 25 | 25 | 25 | 25 | 25 | — |
| 0.5 FS10 | 15 | — | — | — | 120 | 90 | 65 | 55 | 45 | 40 | 35 | 30 | 25 | 25 | 25 | 25 | — |
| 5P10 | 2.5 | 135 | 100 | 85 | 75 | 55 | 45 | 40 | 35 | 30 | 30 | 30 | 30 | 30 | 25 | 25 | 25 |
| 5P10 | 5 | — | — | 135 | 120 | 85 | 70 | 55 | 50 | 45 | 40 | 40 | 35 | 35 | 30 | 30 | 30 |
| 10P10 | 10 | — | — | — | 145 | 110 | 95 | 80 | 70 | 60 | 60 | 50 | 45 | 45 | 35 | 35 | 35 |
| 10P10 | 15 | — | — | — | — | 155 | 130 | 110 | 90 | 80 | 80 | 65 | 60 | 50 | 45 | 40 | 40 |
| 5P20 | 2.5 | — | — | 145 | 125 | 90 | 75 | 65 | 60 | 50 | 50 | 50 | 45 | 40 | 40 | 35 | 35 |
| 5P20 | 5 | — | — | — | 145 | 115 | 95 | 90 | 75 | 70 | 65 | 55 | 50 | 50 | 45 | 40 | 40 |
| 10P20 | 10 | — | — | — | — | — | — | 150 | 125 | 110 | 105 | 85 | 75 | 70 | 60 | 55 | 55 |
| 10P20 | 15 | — | — | — | — | — | — | — | 150 | 140 | 115 | 100 | 90 | 75 | 70 | 70 | 70 |
| 5P30 | 2.5 | — | — | 155 | 135 | 100 | 85 | 75 | 70 | 60 | 60 | 55 | 50 | 50 | 45 | 45 | — |
| 5P30 | 5 | — | — | — | 155 | 125 | 105 | 100 | 85 | 80 | 75 | 65 | 60 | 60 | 55 | 50 | — |
| 10P30 | 10 | — | — | — | — | — | — | 160 | 135 | 120 | 115 | 95 | 85 | 80 | 70 | 65 | 65 |
| 10P30 | 15 | — | — | — | — | — | — | — | 160 | 150 | 125 | 115 | 110 | 100 | 85 | 80 | 80 |
Dimension & outline drawing of CGIS2180 — click image to zoom / view original.
This is a 35 kV indoor current transformer for CGIS gas insulated switchgear, used to step primary current down to a measurable secondary level for metering and protection. Its 0.2S FS10 and 0.5S FS10 metering cores support revenue settlement, while the 5P and 10P protection cores with FS10 factors carry fault current without early saturation.
Metering and protection windings are cast in dry epoxy resin in a round housing with a base, Φ210 mm outer diameter and Ø80 mm inner diameter. Accuracy classes span 0.2S FS10, 0.2 FS10, 0.5S FS10, 0.5 FS10, 5P10, 10P10, 5P20, 10P20, 5P30 and 10P30 at 50/60 Hz. Rated outputs reach 160 VA for 0.5 FS10 and 155 VA for 10P10, depending on primary current.
Because it is an indoor epoxy-cast unit, it is not for outdoor open-air installation; moisture and UV exposure can degrade the casting. It suits wind, photovoltaic and storage collector substations. Earth the secondary at one point and never open-circuit it while energized. Type test evidence and sample support are available [On Request]; custom ratios and classes are quoted on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.