CGIS2806 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A or 1A, accuracy class 0.2FS10/0.5SFS10,0.5,5P10/10P10,5P20/10P20,5P30/10P30. Design: Dry Epoxy Resin, 50/60Hz operation.
Indoor CT for CGIS at 12kV; multiple accuracy classes for metering and protection.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS2806 | Factory nameplate marking |
| Primary Voltage | 12kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A or 1A | Ratio check at rated frequency |
| Accuracy Class | 0.2FS10/0.5SFS10,0.5,5P10/10P10,5P20/10P20,5P30/10P30 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
connect primary through window; secondary terminals 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point only.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating?
A: 12kV.
Q: What accuracy classes are available?
A: 0.2FS10, 0.5SFS10, 0.5, 5P10/10P10, 5P20/10P20, 5P30/10P30.
Q: What is the secondary current rating?
A: 5A or 1A.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | 75(h) | 75(h) | 100(h) | 125(h) | 150(h) | 200(h) | 250(h) | 300(h) | 400(h) | 500(h) | 600(h) | 750(h) | 1000(h) | 1200(h) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 0.2F510 | 2.5 | — | — | — | — | — | 65 | 50 | 40 | 30 | 30 | 30 | 30 | 35 | 35 |
| 0.2F510 | 5 | — | — | — | — | — | 95 | 665 | 50 | 35 | 30 | 30 | 30 | 35 | 35 |
| 0.2F510 | 10 | — | — | — | — | — | 155 | 95 | 75 | 50 | 35 | 30 | 30 | 35 | 35 |
| 0.2F510 | 15 | — | — | — | — | — | 130 | 100 | 65 | 45 | 40 | 35 | 35 | 35 | 35 |
| 0.2F510 | 20 | — | — | — | — | — | 185 | 125 | 75 | 50 | 45 | 40 | 40 | 40 | 35 |
| 0.2F510 | 25 | — | — | — | — | — | — | 150 | 90 | 60 | 50 | 40 | 40 | 40 | 40 |
| 0.2F510 | 30 | — | — | — | — | — | — | — | 105 | 70 | 55 | 45 | 45 | 45 | 40 |
| 0.5F510 | 2.5 | — | 90 | 70 | 55 | 40 | 35 | 30 | 30 | 30 | 30 | 20 | 25 | 25 | — |
| 0.5F510 | 5 | — | 140 | 105 | 80 | 55 | 40 | 35 | 30 | 30 | 30 | 20 | 25 | 25 | — |
| 0.5F510 | 10 | — | — | — | 85 | 60 | 45 | 40 | 35 | 30 | 25 | 25 | 25 | 25 | — |
| 0.5F510 | 15 | — | — | — | 115 | 75 | 60 | 45 | 40 | 35 | 30 | 25 | 25 | 25 | — |
| 0.5F510 | 20 | — | — | — | 145 | 95 | 70 | 55 | 45 | 40 | 30 | 30 | 30 | 25 | — |
| 0.5F510 | 25 | — | — | — | — | 115 | 85 | 65 | 55 | 45 | 35 | 30 | 30 | 30 | — |
| 0.5F510 | 30 | — | — | — | — | 150 | 95 | 70 | 60 | 55 | 40 | 30 | 30 | 30 | — |
| 10P10 | 2.5 | — | 90 | 60 | 55 | 45 | 35 | 30 | 25 | 25 | 25 | 20 | 20 | 20 | — |
| 10P10 | 5 | 145 | 95 | 90 | 70 | 50 | 45 | 40 | 35 | 30 | 30 | 25 | 25 | 25 | — |
| 10P10 | 10 | — | 165 | 155 | 115 | 85 | 70 | 55 | 50 | 45 | 40 | 35 | 30 | 30 | — |
| 10P10 | 15 | — | — | 165 | 115 | 90 | 75 | 70 | 55 | 50 | 45 | 35 | 35 | 30 | — |
| 10P10 | 20 | — | — | 150 | 115 | 95 | 85 | 70 | 60 | 50 | 45 | 40 | 35 | 35 | — |
| 10P10 | 25 | — | — | 180 | 140 | 115 | 100 | 85 | 70 | 60 | 50 | 45 | 40 | 35 | — |
| 10P10 | 30 | — | — | — | 165 | 135 | 120 | 100 | 80 | 70 | 70 | 55 | 50 | 40 | — |
| 10P20 | 2.5 | 140 | 105 | 90 | 75 | 60 | 50 | 40 | 35 | 35 | 30 | 30 | 30 | 30 | — |
| 10P20 | 5 | — | 165 | 140 | 115 | 85 | 70 | 60 | 50 | 45 | 40 | 40 | 35 | 35 | — |
| 10P20 | 10 | — | — | — | 145 | 115 | 100 | 90 | 75 | 65 | 60 | 50 | 50 | 40 | — |
| 10P20 | 15 | — | — | — | — | 160 | 135 | 125 | 105 | 90 | 75 | 65 | 60 | 50 | — |
| 10P20 | 20 | — | — | — | — | 175 | 160 | 130 | 110 | 95 | 80 | 70 | 65 | 60 | — |
| 10P20 | 25 | — | — | — | — | — | — | 160 | 135 | 115 | 95 | 85 | 75 | 70 | — |
| 10P20 | 30 | — | — | — | — | — | — | 185 | 160 | 130 | 110 | 95 | 85 | 75 | — |
| 10P30 | 2.5 | — | 150 | 125 | 105 | 80 | 70 | 60 | 55 | 45 | 45 | 40 | 40 | 40 | — |
| 10P30 | 5 | — | — | 170 | 125 | 105 | 90 | 85 | 75 | 65 | 60 | 55 | 50 | 50 | — |
| 10P30 | 10 | — | — | — | 175 | 150 | 135 | 115 | 100 | 85 | 75 | 70 | 60 | 55 | — |
| 10P30 | 15 | — | — | — | — | 190 | 155 | 135 | 115 | 100 | 85 | 75 | 70 | 60 | — |
| 10P30 | 20 | — | — | — | — | — | 170 | 145 | 125 | 110 | 95 | 85 | 75 | 70 | — |
| 10P30 | 25 | — | — | — | — | — | — | 175 | 150 | 130 | 115 | 100 | 90 | 80 | — |
| 10P30 | 30 | — | — | — | — | — | — | — | — | 175 | 150 | 130 | 115 | 100 | — |
Dimension & outline drawing of CGIS2806 — click image to zoom / view original.
The CGIS2806 is an indoor epoxy resin casting current transformer for 12 kV gas insulated switchgear, stepping primary current down to a 5 A or 1 A secondary for metering and protection. Its dry epoxy resin body and rectangular housing with rectangular window suit the CGIS cubicle, and the 250 mm width is fixed by that housing. Each unit is routine-tested before dispatch, with ratio and polarity checks and insulation screening, and test records are available [On Request].
Accuracy classes span 0.2FS10/0.5SFS10, 0.5, 5P10/10P10, 5P20/10P20 and 5P30/10P30 at 50/60 Hz, with rated outputs in VA from the parameter table. Compared with oil-immersed or SF6 designs, dry epoxy casting removes liquid and gas handling from the indoor cubicle. Compliance follows the GB/T 20840 series, with type and routine test documentation supplied on request.
Deployment is in medium-voltage switchgear, ring main units and central cubicles. Observe P1/P2 and H1/H2 orientation, earth the secondary at one point, and never open-circuit the secondary while energized. This indoor unit must not be installed outdoors. Ratio and class customization, export packing and after-sales support are quoted on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.