KEMA & ISO 9001/14001 Certified|Exporting to 50+ Countries (IEC 61869-3 / IEEE C57.13)
24/7 Global Engineering Hotline: 86 18852046268|sales@potentialtransformers.com
中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTCGIS3206
CGIS3206 Current Transformer Applied to CGIS Gas Insulated Switchgear
12kVCGIS3206
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 12kV
Secondary Metering (1S1 - 1S2):5A or 1A (0.2S FS10/0.2 FS10/0.5S FS10,0.5FS10,5P10/10P10,5P20/10P20)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:CGIS3206

CGIS3206 Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS3206 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A or 1A, accuracy class 0.2S FS10/0.2 FS10/0.5S FS10,0.5FS10,5P10/10P10,5P20/10P20. Design: Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • Indoor epoxy resin casting current transformer for CGIS
  • large rectangular housing with rectangular window
  • 290mm width
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: CGIS3206

Electrical Parameters

Primary Rated Voltage (Un):12kV
Secondary Winding Currents:5A or 1A
Metering & Protection Class:0.2S FS10/0.2 FS10/0.5S FS10,0.5FS10,5P10/10P10,5P20/10P20
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor epoxy resin CT for CGIS, 12kV system, suitable for protection and metering with multiple accuracy classes.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeCGIS3206Factory nameplate marking
Primary Voltage12kVRated voltage test (IEC 61869-1/3)
Secondary Current5A or 1ARatio check at rated frequency
Accuracy Class0.2S FS10/0.2 FS10/0.5S FS10,0.5FS10,5P10/10P10,5P20/10P20Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • CGIS gas insulated switchgear indoor applications
  • 12kV power systems
  • Metering with 0.2S/0.5S accuracy
  • Protection with 5P/10P classes
  • 50/60Hz networks

Not Recommended For

  • Outdoor installations
  • Voltage transformation
  • High voltage above 12kV
  • Oil or gas insulated CTs
  • DC systems

Topology & Wiring

secondary terminals 1S1/1S2 for main winding, 2S1-2S2 for protection winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary voltage rating?

A: 12kV

Q: What accuracy classes are available?

A: 0.2S, 0.2, 0.5S, 0.5, 5P10, 10P10, 5P20, 10P20

Q: Is it suitable for outdoor use?

A: No, it is designed for indoor CGIS applications.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

CGIS3206
28 cols · 35 rows

CGIS3206 Current Transformer for Gas-Insulated Switchgear — Technical Data

Accuracy classRated output (VA)7510012515020025030040050060075010001200
hlhlhlhlhlhlhlhlhlhlhlhlhl
0.2FS102.5————————655040303030303030353535353535353535
0.5FS105————————9565503530303030303535353535353535—
10————————15595756035303030303535353535353535—
15————————130100854540353535353535353535353535—
20————————185125755045404040403535353535353535—
25————————15090605040404040404040404040404040—
30————————————105705545404040404040404040—
0.5FS102.5—90705540353030303030303030303030303030303030303030
5—1401058055403530303030303030303030303030303030303030
10————85604540353030303030303030303030303030303030
15————115756045403530303030303030303030303030303030
20————145957055454030303030303030303030303030303030
25————115856555453530303030303030303030303030303030
30————130957060554540303030303030303030303030303030
10P102.59060554535303030252525252525252525252525252525252525
514595907050454035303030303030303030303030303030303030
101651551158570555045403530303030303030303030303030303030
15——16511590757055504540353535353535353535353535353535
20——15011595757060504540404040404040404040404040404040
25——1801401151008570605045404040404040404040404040404040
30————185135120100807055505050505050505050505050505050
10P202.5140105907560504040353530303030303030303030303030303030
51651401158570606050454035353535353535353535353535353535
10————14511510080756560505050505050505050505050505050
15————180135125105907585606060606060606060606060606060
20————175160130110958070707070707070707070707070707070
25————————1801351159585858585858585858585858585—
30————————18516013010595959595959595959595959595—
10P302.51501251058070606050504540404040404040404040404040404040
5——170125105908575656055505050505050505050505050505050
10————1751501351151008575707070707070707070707070707070
15——————190155135115100909090909090909090909090909090
20————————170145125110110110110110110110110110110110110110110—
25—————————175150135135135135135135135135135135135135135135—
30——————————175150150150150150150150150150150150150150150—
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of CGIS3206 — click image to zoom / view original.

Product Overview

About This Product

CGIS3206

This is a 12 kV indoor epoxy resin cast current transformer, built for CGIS gas insulated switchgear to step primary current down to 5 A or 1 A for metering and protection. Its large rectangular housing, 290 mm wide with a rectangular window, fits the busbar and cable compartment of medium voltage switchgear, ring main units and central-position cubicles.

The insulation is dry epoxy resin, cast around the core and windings to form a solid, void-free body. Accuracy classes cover 0.2S FS10, 0.5S FS10, 0.5 FS10, 5P10/10P10 and 5P20/10P20, with rated outputs from 2.5 VA to 30 VA depending on class and burden; for example, the 0.2FS10 row gives 65 VA at 200(h) and 30 VA from 250(h) to 400(h). Protection cores are specified by composite error and FS10 or ALF, so they hold accuracy under fault current.

This unit is for indoor service only and must not be installed in outdoor or exposed locations. The secondary must never be open-circuited while energized. Before commissioning, check insulation resistance, polarity and ratio. Type and routine test reports are available [On Request]. Ratio, class and winding configuration can be customized.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs