中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTCGIS3411
CGIS3411 Current Transformer Applied to CGIS Gas Insulated Switchgear
12kVCGIS3411
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 12kV
Secondary Metering (1S1 - 1S2):5A or 1A (0.2FS10/0.5SFS10,0.5,5(10)P10,5(10)P20,5(10)P30)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:CGIS3411

CGIS3411 Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS3411 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A or 1A, accuracy class 0.2FS10/0.5SFS10,0.5,5(10)P10,5(10)P20,5(10)P30. Design: Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • Indoor epoxy resin casting current transformer for CGIS
  • large rectangular housing
  • 340mm width
  • high current rating
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: CGIS3411

Electrical Parameters

Primary Rated Voltage (Un):12kV
Secondary Winding Currents:5A or 1A
Metering & Protection Class:0.2FS10/0.5SFS10,0.5,5(10)P10,5(10)P20,5(10)P30
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor epoxy resin CT for CGIS switchgear, 12kV system, multiple accuracy classes including protection classes.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeCGIS3411Factory nameplate marking
Primary Voltage12kVRated voltage test (IEC 61869-1/3)
Secondary Current5A or 1ARatio check at rated frequency
Accuracy Class0.2FS10/0.5SFS10,0.5,5(10)P10,5(10)P20,5(10)P30Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • CGIS gas insulated switchgear indoor applications
  • 12kV power systems
  • Metering and protection with accuracy 0.2FS10/0.5SFS10
  • Protection with class 5(10)P10, 5(10)P20, 5(10)P30
  • 50/60Hz networks

Not Recommended For

  • Outdoor installations
  • Voltage transformers
  • Systems above 12kV
  • Oil or SF6 insulated CT applications
  • DC systems

Topology & Wiring

Connect primary through bushing. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 and IEEE C57.13 conventions.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation type?

A: Dry epoxy resin.

Q: What are the available accuracy classes?

A: 0.2FS10/0.5SFS10, 0.5, 5(10)P10, 5(10)P20, 5(10)P30.

Q: What is the primary voltage rating?

A: 12kV.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

CGIS3411
9 cols · 32 rows

CGIS3411 Current Transformer for Gas-Insulated Switchgear — Technical Data

Accuracy classRated output (VA)Rated primary current (A)
400500600800100012001500
0.2FS102.530303025252525
0.2FS10535353030302525
0.2FS107.545403535353025
0.2FS101050454040353020
0.2FS101565555045403520
0.2FS102080706055504530
0.2FS102595807065555035
0.2FS1030110958070605540
0.5FS102.530303025252525
0.5FS10535353020202020
0.5FS107.545403525202020
0.5FS101050454025252020
0.5FS101565555030302525
0.5FS102080706035302525
0.5FS102595807040353025
0.5FS1030110958045403025
5P10/10P102.530252530252530
5P10/10P10540353035353535
5P10/10P107.550454045404040
5P10/10P101080555555454545
5P10/10P101585706070606065
5P10/10P1020105907585757065
5P10/10P102513010590105908075
5P10/10P1030125105125100958585
5P20/10P202.550454035303535
5P20/10P20575655545404545
5P20/10P207.595807060505550
5P20/10P20101201008570606560
5P20/10P20151401209580857575
5P20/10P2020———12010011090
5P20/10P2025———140120120105
5P20/10P2030———140140125125
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of CGIS3411 — click image to zoom / view original.

Product Overview

About This Product

CGIS3411

This is an indoor dry epoxy resin cast current transformer for 12 kV gas insulated switchgear, converting primary current to a 5 A or 1 A secondary for metering and protection. The solid cast insulation removes the oil or gas dielectric from the current path, so the unit is a sealed, maintenance-free component inside the CGIS enclosure.

The epoxy body is a large rectangular housing 340 mm wide, sized to carry high primary currents. Accuracy classes cover 0.2FS10/0.5SFS10 metering and 0.5, 5(10)P10, 5(10)P20 and 5(10)P30 protection, at 50/60 Hz. From the parameter table, 0.2FS10 at 5 VA holds 35 VA at 400 A and 500 A, 30 VA at 600 A and 800 A, and 25 VA at 1200 A and 1500 A; higher burdens are listed per row. Standard ratios are stocked; non-standard ratios and classes are built to order.

Datasheets, outline drawings and type test reports are available [On Request]. The secondary must never be open-circuited while energized; earth it at one point and verify secondary burden before energizing. Indoor service only.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs