CGIS3815 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A or 1A, accuracy class 0.2FS10/0.5SFS10,0.5FS10,5P10/10P10,5P15/10P15,5P20/10P20. Design: Dry Epoxy Resin, 50/60Hz operation.
Indoor epoxy resin casting current transformer for CGIS gas insulated switchgear, suitable for 12kV systems with multiple accuracy classes and burdens.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS3815 | Factory nameplate marking |
| Primary Voltage | 12kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A or 1A | Ratio check at rated frequency |
| Accuracy Class | 0.2FS10/0.5SFS10,0.5FS10,5P10/10P10,5P15/10P15,5P20/10P20 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the maximum primary current rating?
A: The primary current rating is not specified in the provided data; it is [On Request].
Q: What are the available accuracy classes?
A: Accuracy classes include 0.2FS10, 0.5SFS10, 0.5FS10, 5P10/10P10, 5P15/10P15, and 5P20/10P20.
Q: Is this CT suitable for outdoor use?
A: No, it is designed for indoor use within CGIS gas-insulated switchgear.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | Rated primary current (A) | (75) h | (75) h | (100) h | (100) h | 125 h | 125 h | 150 h | 150 h | 200 h | 200 h | 250 h | 250 h | 300 h | 300 h | 400 h | 400 h | 500 h | 500 h | 600 h | 600 h | 750 h | 750 h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 0.2FS10 | 2.5 | — | — | 51 | — | 51 | — | 41 | — | 36 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 |
| 0.2FS10 | 5 | — | — | 46 | — | 51 | — | 51 | — | 46 | — | 36 | — | 36 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 |
| 0.2FS10 | 7.5 | — | — | — | — | 51 | — | 51 | — | 51 | — | 51 | — | 41 | — | 36 | — | 36 | — | 31 | — | 31 | — | 31 |
| 0.2FS10 | 10 | — | — | — | — | — | — | 51 | — | 51 | — | 51 | — | 51 | — | 41 | — | 46 | — | 41 | — | 36 | — | 31 |
| 0.2FS10 | 15 | — | — | — | — | — | — | — | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 |
| 0.2FS10 | 20 | — | — | — | — | — | — | — | — | — | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 |
| 0.5FS10 | 2.5 | — | — | 51 | — | 41 | — | 41 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 | — | 31 |
| 0.5FS10 | 5 | — | — | 46 | — | 51 | — | 51 | — | 51 | — | 46 | — | 36 | — | 36 | — | 31 | — | 31 | — | 31 | — | 31 |
| 0.5FS10 | 7.5 | — | — | — | — | 51 | — | 51 | — | 51 | — | 51 | — | 46 | — | 41 | — | 41 | — | 36 | — | 31 | — | — |
| 0.5FS10 | 10 | — | — | — | — | — | — | 51 | — | 46 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | — |
| 0.5FS10 | 15 | — | — | — | — | — | — | — | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 |
| 0.5FS10 | 20 | — | — | — | — | — | — | — | — | — | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 | — | 51 |
| 5P10/10P10 | 2.5 | 85 | 50 | 50 | 40 | 30 | 25 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
| 5P10/10P10 | 5 | 155 | 100 | 110 | 65 | 45 | 35 | 25 | 25 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
| 5P10/10P10 | 7.5 | 140 | 155 | 85 | 55 | 40 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 |
| 5P10/10P10 | 10 | 170 | 185 | 110 | 70 | 50 | 40 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
| 5P10/10P10 | 15 | — | — | 180 | 160 | 100 | 70 | 50 | 45 | 40 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 |
| 5P10/10P10 | 20 | — | — | — | — | 180 | 130 | 90 | 65 | 55 | 45 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 |
| 5P10/10P10 | 25 | — | — | — | — | 155 | 160 | 110 | 75 | 60 | 55 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| 5P10/10P10 | 30 | — | — | — | — | 185 | 190 | 130 | 85 | 70 | 65 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 |
| 5P20/10P20 | 2.5 | 130 | 70 | 55 | 50 | 40 | 35 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
| 5P20/10P20 | 5 | 150 | 160 | 110 | 65 | 55 | 45 | 40 | 35 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
| 5P20/10P20 | 7.5 | — | — | 130 | 155 | 90 | 55 | 65 | 50 | 45 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 |
| 5P20/10P20 | 10 | — | — | 170 | 180 | 115 | 85 | 80 | 65 | 55 | 50 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 |
| 5P20/10P20 | 15 | — | — | — | — | 170 | 165 | 130 | 110 | 85 | 75 | 65 | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 |
| 5P20/10P20 | 7.5 | 85 | 65 | 55 | 45 | 40 | 35 | 30 | 30 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 |
| 5P30/10P30 | 2.5 | 130 | 95 | 80 | 65 | 55 | 45 | 40 | 35 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
| 5P30/10P30 | 5 | 145 | 150 | 120 | 90 | 75 | 65 | 55 | 45 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 |
| 5P30/10P30 | 7.5 | — | — | 135 | 175 | 130 | 105 | 90 | 75 | 65 | 60 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 | 55 |
Dimension & outline drawing of CGIS3815 — click image to zoom / view original.
This is an indoor dry epoxy resin cast current transformer for 12 kV CGIS gas insulated switchgear, converting primary current to a 5 A or 1 A secondary for metering and protection. Its extra large diameter split ring construction, with an outer diameter of Ø376 mm max and an inner diameter of Ø150 mm, helps solve the problem of fitting a large aperture CT into a confined switchgear compartment without occupying unnecessary panel space.
The accuracy class range covers 0.2FS10/0.5SFS10, 0.5FS10, 5P10/10P10, 5P15/10P15 and 5P20/10P20, with rated outputs from 2.5 VA to 20 VA, so the secondary burden can be matched to the connected relay and meter load. It is intended for indoor installation only and must not be used in outdoor open-air locations. Typical deployment includes wind, photovoltaic collector stations and energy storage step-up systems. Before commissioning, verify the secondary burden in VA against the nameplate, earth the secondary at one point and never open-circuit the secondary while energized. Type and routine test reports are available [On Request]. Ratio and accuracy class combinations can be customized; the document package and delivery terms are confirmed at inquiry.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.