中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTCGIS3818
CGIS3818 Current Transformer Applied to CGIS Gas Insulated Switchgear
12kVCGIS3818
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 12kV
Secondary Metering (1S1 - 1S2):5A or 1A (0.2FS10/0.5SFS10,0.5SFS10,5P10/10P10,5P20/10P20,5P30/10P30)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:CGIS3818

CGIS3818 Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS3818 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A or 1A, accuracy class 0.2FS10/0.5SFS10,0.5SFS10,5P10/10P10,5P20/10P20,5P30/10P30. Design: Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • Indoor epoxy resin casting current transformer for CGIS
  • extra large diameter split ring type
  • outer diameter Ø376mm max
  • inner diameter Ø180mm
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: CGIS3818

Electrical Parameters

Primary Rated Voltage (Un):12kV
Secondary Winding Currents:5A or 1A
Metering & Protection Class:0.2FS10/0.5SFS10,0.5SFS10,5P10/10P10,5P20/10P20,5P30/10P30
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor epoxy resin CT for CGIS, 12kV, 50/60Hz, multiple accuracy classes. Suitable for protection and metering in gas-insulated switchgear.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeCGIS3818Factory nameplate marking
Primary Voltage12kVRated voltage test (IEC 61869-1/3)
Secondary Current5A or 1ARatio check at rated frequency
Accuracy Class0.2FS10/0.5SFS10,0.5SFS10,5P10/10P10,5P20/10P20,5P30/10P30Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • CGIS gas insulated switchgear indoor applications
  • 12kV primary systems with secondary 5A or 1A
  • Metering and protection with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20, 10P20, 5P30, 10P30
  • Large conductor applications with inner diameter 180mm

Not Recommended For

  • Outdoor installations
  • Voltage transformation applications
  • Systems above 12kV
  • Non-gas-insulated switchgear retrofits without verification

Topology & Wiring

Connect primary through the window. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 and IEEE C57.13 conventions.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the maximum outer diameter?

A: Ø376mm max.

Q: What are the available accuracy classes?

A: 0.2FS10/0.5SFS10, 0.5SFS10, 5P10/10P10, 5P20/10P20, 5P30/10P30.

Q: Is it suitable for outdoor use?

A: No, it is designed for indoor CGIS applications.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

CGIS3818
14 cols · 29 rows

CGIS3818 Current Transformer for Gas-Insulated Switchgear — Technical Data

Accuracy classRated output (VA)75(h)75(h)100(h)125(h)150(h)200(h)250(h)300(h)400(h)500(h)600(h)750(h)
0.2FS102.5——51514136313131313131
0.2FS105——46515151483636313131
0.2FS107.5———515151515141363631
0.2FS1010———515151515151414641
0.2FS1015————5151515151484141
0.2FS1020————5151515151515151
0.5FS102.5——51413131313131313131
0.5FS105——46515151483636313131
0.5FS107.5———515151515141414136
0.5FS1010———515151515151514141
0.5FS1015————5151515151515151
0.5FS1020————5151515151515151
5P10/10P102.5855060403025202020202020
5P10/10P105—1551601106646352625202020
5P10/10P107.5—140155855540303025252525
5P10/10P1010—1701851107050403530303030
5P10/10P1015——18016010070504540353535
5P10/10P1020———16013090655545404040
5P10/10P1025———155160110756055505050
5P10/10P1030———185190130857065656565
5P20/10P202.51307055504035303030303030
5P20/10P205—1501601106555454035303030
5P20/10P207.5——1301559075655045403535
5P20/10P2010——17018511580655550454040
5P20/10P2015———1701651301108575656060
5P30/10P301.5856555454035303025252525
5P30/10P302.51309580655545403530303030
5P30/10P305—1451501209075655545454545
5P30/10P307.5——155170130105907565605555
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of CGIS3818 — click image to zoom / view original.

Product Overview

About This Product

CGIS3818

This is a 12kV indoor current transformer built on a dry epoxy resin casting, and that insulation choice is what lets it sit directly in CGIS gas insulated switchgear as a compact, maintenance-free measuring and protection element. The casting also carries the extra large diameter split ring format, with an outer diameter of Ø376mm max and an inner diameter of Ø180mm, so it fits around the primary conductor of the switchgear assembly.

For metering and protection the unit offers 0.2FS10 and 0.5FS10 classes with rated outputs from 2.5VA to 20VA, and protection classes 5P10/10P10, 5P20/10P20 and 5P30/10P30 for fault-current service at 50/60Hz. Because it is an indoor device, it is intended for switchgear and distribution panels in metallurgy, mining, cement and chemical plant substations rather than exposed outdoor yards. Secondary terminals must be wired per the nameplate diagram, earthed at one point, and the secondary must never be open-circuited while the primary is energized. It is not suitable for DC or non-standard frequencies. Ratio and class variants, OEM marking and the routine and type test documentation package are available on request, and [On Request] details are quoted at inquiry.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs