Professional current transformer dedicated to CGIS inflatable switchgear with multiple accuracy grades and rich primary current specifications; secondary lead length and stacked mounting height support customized production.
CGIS6508 is a dry epoxy resin current transformer for 35kV inflatable switchgear, offering multi-grade accuracy and customizable secondary leads.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS6508 | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the bushing; secondary terminals are 1S1/1S2 for the main winding, and 2S1/2S2 for the protection winding if present. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 for accuracy and burden.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation type of CGIS6508?
A: Dry epoxy resin.
Q: What is the primary voltage rating?
A: 35kV.
Q: Can the secondary lead length be customized?
A: Yes, secondary lead parameters are customizable.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | 750/5 | 1000/5 | 1500/5 | 2000/5 | 2500/5 | 3000/5 | 4000/5 |
|---|---|---|---|---|---|---|---|---|
| 0.2S FS10 0.2 FS10 0.5S FS10 | 5 | 30 | 30 | 30 | 30 | 25 | 25 | 25 |
| 10 | 40 | 35 | 30 | 30 | 25 | 25 | 25 | |
| 15 | 50 | 40 | 30 | 30 | 30 | 25 | 25 | |
| 20 | 60 | 45 | 30 | 30 | 30 | 30 | 30 | |
| 25 | 65 | 50 | 35 | 30 | 30 | 30 | 30 | |
| 30 | 70 | 55 | 40 | 35 | 30 | 30 | 30 | |
| 0.5FS10 | 5 | 30 | 30 | 30 | 30 | 25 | 25 | 25 |
| 10 | 30 | 30 | 30 | 25 | 25 | 25 | 25 | |
| 15 | 35 | 35 | 30 | 25 | 25 | 25 | 25 | |
| 20 | 35 | 35 | 30 | 25 | 25 | 25 | 25 | |
| 25 | 40 | 35 | 35 | 30 | 25 | 25 | 25 | |
| 30 | 45 | 40 | 40 | 35 | 30 | 25 | 25 | |
| 5P10 10P10 | 5 | 30 | 30 | 30 | 25 | 25 | 25 | 25 |
| 10 | 40 | 30 | 30 | 25 | 25 | 25 | 25 | |
| 15 | 45 | 35 | 30 | 30 | 25 | 25 | 25 | |
| 20 | 55 | 40 | 40 | 30 | 30 | 25 | 25 | |
| 25 | 60 | 50 | 45 | 30 | 30 | 30 | 25 | |
| 30 | 65 | 55 | 50 | 35 | 30 | 30 | 25 | |
| 5P15 10P15 | 5 | 40 | 30 | 30 | 30 | 25 | 25 | 25 |
| 10 | 50 | 35 | 30 | 30 | 25 | 25 | 25 | |
| 15 | 65 | 50 | 40 | 35 | 30 | 30 | 25 | |
| 20 | 75 | 60 | 45 | 40 | 30 | 30 | 25 | |
| 25 | 90 | 70 | 50 | 45 | 40 | 35 | 30 | |
| 30 | 95 | 80 | 60 | 50 | 45 | 40 | 30 | |
| 5P20 10P20 | 5 | 50 | 45 | 35 | 35 | 30 | 30 | 30 |
| 10 | 65 | 55 | 40 | 40 | 35 | 35 | 30 | |
| 15 | 85 | 70 | 45 | 45 | 40 | 40 | 35 | |
| 20 | 100 | 80 | 50 | 50 | 45 | 40 | 40 | |
| 25 | 120 | 95 | 70 | 55 | 50 | 45 | 40 | |
| 30 | 130 | 105 | 80 | 65 | 55 | 50 | 45 | |
| 5P30 10P30 | 5 | 75 | 60 | 55 | 50 | 45 | 45 | 40 |
| 10 | 105 | 80 | 65 | 60 | 55 | 55 | 45 | |
| 15 | 130 | 100 | 80 | 70 | 60 | 60 | 50 | |
| 20 | 135 | 120 | 95 | 80 | 70 | 65 | 55 | |
| 25 | 150 | 140 | 105 | 90 | 75 | 70 | 60 | |
| 30 | 160 | 120 | 100 | 85 | 75 | 65 | — |
Dimension & outline drawing of CGIS6508 — click image to zoom / view original.
The CGIS6508 is a 35 kV dry epoxy resin current transformer built for inflatable switchgear, where limited cubicle space and the risk of CT saturation under light-load metering make conventional designs difficult to apply. Its cast-resin insulation and winding architecture are designed for 50/60 Hz service, with multi-grade precision available across the accuracy classes listed on the nameplate.
Electrical performance covers 0.2S FS10, 0.2 FS10, 0.5S FS10, 0.5FS10 and protection classes from 5P10 through 10P20. Rated outputs in VA are assigned per ratio and class in the parameter table, so the exact burden for a given ratio must be read from the official datasheet. Short-time thermal and dynamic withstand figures are [On Request]. This unit sits in the indoor, space-constrained segment of the range; outdoor types are not interchangeable with it.
Typical deployment is heavy-industry distribution in metallurgy, mining, cement and chemical plants. Earth the secondary at one point and never open-circuit it while energized. Over-specifying accuracy class adds cost without benefit. Ratio and class customization, documentation and delivery schedules are quoted on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.