Special current transformer designed for CGIS inflatable switchgear with multiple accuracy grades and abundant primary current specifications; secondary lead length and stacked product height support customized production.
CGIS7516 is a dry epoxy resin current transformer for 35kV inflatable switchgear, offering multiple accuracy grades and customizable secondary leads.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS7516 | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect secondary terminals 1S1/1S2 for main metering/protection winding; additional windings (e.g., 2S1-2S2) for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point per IEC 61869-2.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating of CGIS7516?
A: It is rated for 35kV systems.
Q: Can the secondary lead length be customized?
A: Yes, secondary lead parameters are customizable.
Q: Is this CT suitable for outdoor use?
A: No, it is designed for indoor inflatable switchgear (RMU).
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy class | Rated output (VA) | Rated primary current (A) | |||||
|---|---|---|---|---|---|---|---|
| 1000/5 | 1500/5 | 2000/5 | 2500/5 | 3000/5 | 4000/5 | ||
| 0.2 5P10 0.2 5P20 0.5 5P10 | 5 | 30 | 30 | 30 | 30 | 30 | 25 |
| 10 | 35 | 30 | 30 | 30 | 30 | 25 | |
| 15 | 35 | 30 | 30 | 30 | 30 | 30 | |
| 20 | 40 | 40 | 40 | 35 | 30 | 30 | |
| 25 | 40 | 40 | 40 | 35 | 30 | 30 | |
| 30 | 45 | 45 | 45 | 40 | 35 | 30 | |
| 0.5 5P10 | 5 | 30 | 25 | 25 | 25 | 25 | 25 |
| 10 | 30 | 25 | 25 | 25 | 25 | 25 | |
| 15 | 30 | 30 | 30 | 25 | 25 | 25 | |
| 20 | 30 | 30 | 30 | 25 | 25 | 25 | |
| 25 | 35 | 30 | 30 | 25 | 25 | 25 | |
| 30 | 35 | 30 | 30 | 30 | 30 | 25 | |
| 5P10 10P10 | 5 | 30 | 25 | 25 | 25 | 25 | 25 |
| 10 | 30 | 25 | 25 | 25 | 25 | 25 | |
| 15 | 30 | 30 | 30 | 25 | 25 | 25 | |
| 20 | 35 | 30 | 30 | 25 | 25 | 25 | |
| 25 | 40 | 30 | 30 | 25 | 25 | 25 | |
| 30 | 40 | 35 | 35 | 30 | 30 | 25 | |
| 5P15 10P15 | 5 | 30 | 25 | 25 | 25 | 30 | 25 |
| 10 | 35 | 30 | 25 | 25 | 30 | 25 | |
| 15 | 45 | 35 | 30 | 30 | 30 | 25 | |
| 20 | 50 | 35 | 35 | 30 | 30 | 25 | |
| 25 | 55 | 40 | 35 | 30 | 30 | 25 | |
| 30 | 60 | 45 | 40 | 35 | 30 | 30 | |
| 5P20 10P20 | 5 | 35 | 30 | 30 | 30 | 30 | 25 |
| 10 | 45 | 40 | 35 | 30 | 30 | 30 | |
| 15 | 50 | 45 | 35 | 35 | 30 | 30 | |
| 20 | 60 | 50 | 40 | 40 | 35 | 30 | |
| 25 | 70 | 55 | 45 | 40 | 35 | 30 | |
| 30 | 80 | 60 | 50 | 45 | 40 | 35 | |
| 5P30 10P30 | 5 | 80 | 45 | 40 | 40 | 35 | 35 |
| 10 | 70 | 55 | 50 | 45 | 40 | 40 | |
| 15 | 80 | 65 | 55 | 50 | 45 | 40 | |
| 20 | 100 | 75 | 60 | 55 | 50 | 45 | |
| 25 | 110 | 85 | 70 | 60 | 55 | 50 | |
| 30 | 120 | 95 | 80 | 70 | 65 | 55 | |
Dimension & outline drawing of CGIS7516 — click image to zoom / view original.
This current transformer is designed for 35 kV inflatable switchgear, where it steps primary current down to a metered or protected secondary for the cabinet's instrumentation and relays. Its dry epoxy resin insulation and wound core construction suit the sealed gas compartment, and the stacked coil height can be adjusted to match the busbar arrangement.
Accuracy options span 0.2S FS10, 0.2 FS10, 0.5S FS10, 0.5FS10, 5P10, 10P10, 5P15, 10P15, 5P20 and 10P20, with rated outputs from 5 VA to 30 VA depending on the ratio and class selected. For example, at 1000/5 A a 0.2 5P10 unit is rated 5 VA, while a 30 VA row is available at the same ratio. Short-time thermal and dynamic ratings, insulation level and weight are stated on the nameplate and the official datasheet [On Request].
The secondary must never be open-circuited while the primary is energized. Earth the secondary at one point, follow the terminal diagram, and verify the connected burden in VA before commissioning. This indoor unit is not for outdoor open-air installation. Ratio and accuracy combinations are customizable; request the test report package and delivery schedule with your inquiry.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.