中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTCGIS9817S
CGIS9817S Current Transformer for Inflatable Switchgear
35kVCGIS9817S
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 35kV
Secondary Metering (1S1 - 1S2): ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:CGIS9817S

CGIS9817S Current Transformer for Inflatable Switchgear

CGIS9817S Current Transformer for Inflatable Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • Three-phase integrated structure
  • exclusive dimension design
  • customizable outgoing wire parameters
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: CGIS9817S

Electrical Parameters

Primary Rated Voltage (Un):35kV
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

CGIS9817S is a three-phase integrated current transformer for 35kV inflatable switchgear, offering customizable accuracy and primary current ranges. Suitable for metering and protection in RMU applications.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeCGIS9817SFactory nameplate marking
Primary Voltage35kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 35kV ring main units (RMU) and inflatable switchgear
  • Indoor GIS applications requiring compact, integrated CTs
  • Revenue metering and protection schemes with multiple accuracy classes
  • Custom secondary lead configurations and stacked height requirements

Not Recommended For

  • Outdoor substations or open-terminal applications
  • Voltage transformation or potential indication
  • High-voltage transmission lines above 35kV
  • Oil-filled or SF6-insulated CT replacements without adaptation

Topology & Wiring

For current transformers (CT), secondary terminals are designated 1S1/1S2 for the main winding, and 2S1/2S2 for the protection winding if present. Never open-circuit the secondary of a CT while energized – hazardous voltage may occur. Ground the secondary circuit at one point only, in accordance with IEC 61869-2 and IEEE C57.13. Ensure shorting links are provided before disconnecting the secondary wiring.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary voltage rating of the CGIS9817S?

A: The primary voltage is 35kV, suitable for 35kV systems.

Q: Can the CGIS9817S be used for outdoor installations?

A: No, it is designed for indoor inflatable switchgear (CGIS) and ring main units.

Q: What are the available accuracy classes?

A: Multiple accuracy grades are available, but specific classes are [On Request].

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

CGIS9817S
9 cols · 35 rows

CGIS7515S, 9817S, 1021S Current Transformer for Gas-Insulated Switchgear — Technical Data

Accuracy classCombinedRated primary current (A)200300400500600700800
0.2/5P102.5304050607080—
560708090100110—
7.585100115130145160—
10105125145165185205—
15135160185210235260—
20165195225255285315—
25195230265300335370—
0.5/5P102.5304050607080—
560708090100110—
7.585100115130145160—
10105125145165185205—
15135160185210235260—
20165195225255285315—
25195230265300335370—
5P10/5P102.5304050607080—
560708090100110—
7.585100115130145160—
10105125145165185205—
15135160185210235260—
20165195225255285315—
25195230265300335370—
5P15/5P152.5304050607080—
560708090100110—
7.585100115130145160—
10105125145165185205—
15135160185210235260—
20165195225255285315—
25195230265300335370—
5P20/5P202.5304050607080—
560708090100110—
7.585100115130145160—
10105125145165185205—
15135160185210235260—
20165195225255285315—
25195230265300335370—
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of CGIS9817S — click image to zoom / view original.

Product Overview

About This Product

CGIS9817S

This 35 kV current transformer addresses the engineering pain of CT saturation and space constraints inside inflatable switchgear, where conventional units may not fit or may distort measurement under light load. Its three-phase integrated structure and exclusive dimension design reduce the footprint within the gas-insulated enclosure, helping to preserve clearances and simplify panel layout.

Dry epoxy resin insulation supports reliable dielectric performance at 50/60Hz, and the available accuracy classes—0.2FS10, 0.5FS10, 5P10, 10P10, 5P15 and 10P15—cover both metering and protection duties. Rated output and short-time thermal data are marked on the nameplate or available in the official datasheet. Within the family, selection between these classes depends on whether revenue metering or overcurrent protection governs the application.

Compliance follows IEEE C57.13, with type-test evidence and routine reports available [On Request]. Typical deployment includes rail transit, data centres, hospitals and water utilities. Before energising, verify the secondary burden in VA against the rated output and earth the secondary at one point. This indoor unit is not for outdoor open-air installation, and the secondary must never be open-circuited while energised. Sample support and type-test documentation are offered for project approval.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs