CGIS9817S Current Transformer for Inflatable Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
CGIS9817S is a three-phase integrated current transformer for 35kV inflatable switchgear, offering customizable accuracy and primary current ranges. Suitable for metering and protection in RMU applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | CGIS9817S | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
For current transformers (CT), secondary terminals are designated 1S1/1S2 for the main winding, and 2S1/2S2 for the protection winding if present. Never open-circuit the secondary of a CT while energized – hazardous voltage may occur. Ground the secondary circuit at one point only, in accordance with IEC 61869-2 and IEEE C57.13. Ensure shorting links are provided before disconnecting the secondary wiring.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating of the CGIS9817S?
A: The primary voltage is 35kV, suitable for 35kV systems.
Q: Can the CGIS9817S be used for outdoor installations?
A: No, it is designed for indoor inflatable switchgear (CGIS) and ring main units.
Q: What are the available accuracy classes?
A: Multiple accuracy grades are available, but specific classes are [On Request].
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Accuracy classCombined | Rated primary current (A) | 200 | 300 | 400 | 500 | 600 | 700 | 800 |
|---|---|---|---|---|---|---|---|---|
| 0.2/5P10 | 2.5 | 30 | 40 | 50 | 60 | 70 | 80 | — |
| 5 | 60 | 70 | 80 | 90 | 100 | 110 | — | |
| 7.5 | 85 | 100 | 115 | 130 | 145 | 160 | — | |
| 10 | 105 | 125 | 145 | 165 | 185 | 205 | — | |
| 15 | 135 | 160 | 185 | 210 | 235 | 260 | — | |
| 20 | 165 | 195 | 225 | 255 | 285 | 315 | — | |
| 25 | 195 | 230 | 265 | 300 | 335 | 370 | — | |
| 0.5/5P10 | 2.5 | 30 | 40 | 50 | 60 | 70 | 80 | — |
| 5 | 60 | 70 | 80 | 90 | 100 | 110 | — | |
| 7.5 | 85 | 100 | 115 | 130 | 145 | 160 | — | |
| 10 | 105 | 125 | 145 | 165 | 185 | 205 | — | |
| 15 | 135 | 160 | 185 | 210 | 235 | 260 | — | |
| 20 | 165 | 195 | 225 | 255 | 285 | 315 | — | |
| 25 | 195 | 230 | 265 | 300 | 335 | 370 | — | |
| 5P10/5P10 | 2.5 | 30 | 40 | 50 | 60 | 70 | 80 | — |
| 5 | 60 | 70 | 80 | 90 | 100 | 110 | — | |
| 7.5 | 85 | 100 | 115 | 130 | 145 | 160 | — | |
| 10 | 105 | 125 | 145 | 165 | 185 | 205 | — | |
| 15 | 135 | 160 | 185 | 210 | 235 | 260 | — | |
| 20 | 165 | 195 | 225 | 255 | 285 | 315 | — | |
| 25 | 195 | 230 | 265 | 300 | 335 | 370 | — | |
| 5P15/5P15 | 2.5 | 30 | 40 | 50 | 60 | 70 | 80 | — |
| 5 | 60 | 70 | 80 | 90 | 100 | 110 | — | |
| 7.5 | 85 | 100 | 115 | 130 | 145 | 160 | — | |
| 10 | 105 | 125 | 145 | 165 | 185 | 205 | — | |
| 15 | 135 | 160 | 185 | 210 | 235 | 260 | — | |
| 20 | 165 | 195 | 225 | 255 | 285 | 315 | — | |
| 25 | 195 | 230 | 265 | 300 | 335 | 370 | — | |
| 5P20/5P20 | 2.5 | 30 | 40 | 50 | 60 | 70 | 80 | — |
| 5 | 60 | 70 | 80 | 90 | 100 | 110 | — | |
| 7.5 | 85 | 100 | 115 | 130 | 145 | 160 | — | |
| 10 | 105 | 125 | 145 | 165 | 185 | 205 | — | |
| 15 | 135 | 160 | 185 | 210 | 235 | 260 | — | |
| 20 | 165 | 195 | 225 | 255 | 285 | 315 | — | |
| 25 | 195 | 230 | 265 | 300 | 335 | 370 | — |
Dimension & outline drawing of CGIS9817S — click image to zoom / view original.
This 35 kV current transformer addresses the engineering pain of CT saturation and space constraints inside inflatable switchgear, where conventional units may not fit or may distort measurement under light load. Its three-phase integrated structure and exclusive dimension design reduce the footprint within the gas-insulated enclosure, helping to preserve clearances and simplify panel layout.
Dry epoxy resin insulation supports reliable dielectric performance at 50/60Hz, and the available accuracy classes—0.2FS10, 0.5FS10, 5P10, 10P10, 5P15 and 10P15—cover both metering and protection duties. Rated output and short-time thermal data are marked on the nameplate or available in the official datasheet. Within the family, selection between these classes depends on whether revenue metering or overcurrent protection governs the application.
Compliance follows IEEE C57.13, with type-test evidence and routine reports available [On Request]. Typical deployment includes rail transit, data centres, hospitals and water utilities. Before energising, verify the secondary burden in VA against the rated output and earth the secondary at one point. This indoor unit is not for outdoor open-air installation, and the secondary must never be open-circuited while energised. Sample support and type-test documentation are offered for project approval.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.