Indoor low voltage split-core open type current transformer, 0.66kV rated, for current measurement and protection in low voltage distribution systems. Complies with IEC 61869 and GB/T 20840 standards. Split-core design, can be directly installed on existing busbars without power interruption. Easy installation, wide range of current ratios available. Customizable ratios and specifications.
KCT-0.66 is a low-voltage split-core current transformer for indoor use, enabling installation without power interruption. Suitable for current measurement and protection in LV distribution systems.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869 / GB/T 20840 |
| Model Code | KCT-0.66 | Factory nameplate marking |
| Primary Voltage | 0.66kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A | Ratio check at rated frequency |
| Accuracy Class | 0.2S/0.5S/0.5/1.0 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869 / GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary conductor through the window. Secondary terminals are 1S1 and 1S2 (for protection winding, 2S1-2S2 if applicable). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 / GB/T 20840 for installation.
Compliant with: IEC 61869 / GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: Can this CT be installed without power outage?
A: Yes, the split-core design allows installation on existing busbars without de-energizing the circuit.
Q: What accuracy classes are available?
A: Accuracy classes include 0.2S, 0.5S, 0.5, and 1.0, suitable for various metering and protection needs.
Q: What is the rated secondary current?
A: The secondary current is 5A, as specified.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated current ratio | burden (VA) cosφ=0.8 | |||||||
|---|---|---|---|---|---|---|---|---|---|
| 0.2 | 0.2 | 0.5 | 0.5 | 0.8 | 0.8 | 1 | 1 | ||
| KCT-23 | 100/5 | — | — | — | — | 1.5 | — | 1 | — |
| KCT-23 | 200/5 | — | — | — | — | 1.5 | — | 1 | — |
| KCT-23 | 400/5 | — | — | — | — | 2.5 | — | 2 | — |
| KCT-23 | 500/5 | — | — | — | — | 2.5 | — | 2 | — |
| KCT-58 | 300/1 | — | — | — | — | 5 | — | 5 | — |
| KCT-58 | 500/1 | — | — | — | — | 5 | — | 5 | — |
| KCT-58 | 1000/1 | 5 | — | — | — | 15 | — | 15 | — |
| KCT-58 | 200/5 | 5 | — | — | — | 5 | — | 5 | — |
| KCT-58 | 400/5 | 5 | — | — | — | 5 | — | 5 | — |
| KCT-58 | 500/5 | — | — | — | — | 10 | — | 10 | — |
| KCT-58 | 1000/5 | — | — | — | — | 20 | — | 20 | — |
| KCT-410 | 500/1 | 5 | — | — | — | 10 | — | 10 | — |
| KCT-410 | 1000/1 | 10 | — | — | — | 25 | — | 25 | — |
| KCT-410 | 1500/1 | 15 | — | — | — | 25 | — | 25 | — |
| KCT-410 | 500/5 | — | — | — | — | 10 | — | 10 | — |
| KCT-410 | 1000/5 | — | — | — | — | 25 | — | 25 | — |
| KCT-410 | 1500/5 | — | — | — | — | 25 | — | 25 | — |
| KCT-610 | 600/1 | — | — | — | — | 5 | — | 5 | — |
| KCT-610 | 1000/1 | — | — | — | — | 10 | — | 10 | — |
| KCT-610 | 1500/1 | — | — | — | — | 20 | — | 20 | — |
| KCT-610 | 600/5 | — | — | — | — | 5 | — | 5 | — |
| KCT-610 | 1000/5 | — | — | — | — | 10 | — | 10 | — |
| KCT-610 | 1500/5 | — | — | — | — | 20 | — | 20 | — |
| KCT-810 | 1000/1 | 10 | — | — | — | 20 | — | 20 | — |
| KCT-810 | 1500/1 | 20 | — | — | — | 30 | — | 30 | — |
| KCT-810 | 2000/1 | 30 | — | — | — | 40 | — | 40 | — |
| KCT-810 | 1000/5 | — | — | — | — | 20 | — | 20 | — |
| KCT-810 | 1500/5 | — | — | — | — | 30 | — | 30 | — |
| KCT-810 | 2000/5 | — | — | — | — | 40 | — | 40 | — |
| KCT-23 | 300/5 | — | — | — | — | 2.5 | — | 2 | — |
| KCT-23 | 400/5 | — | — | — | — | 2.5 | — | 2 | — |
| KCT-23 | 500/5 | — | — | — | — | 2.5 | — | 2 | — |
| KCT-58 | 200/5 | — | — | — | — | 2.5 | — | 2.5 | — |
| KCT-58 | 500/5 | — | — | — | — | 5 | — | 5 | — |
| KCT-58 | 1000/5 | — | — | — | — | 10 | — | 10 | — |
| KCT-58 | 2000/5 | — | — | — | — | 20 | — | 20 | — |
| KCT-410 | 500/5 | — | — | — | — | 10 | — | 10 | — |
| KCT-410 | 1000/5 | — | — | — | — | 20 | — | 20 | — |
| KCT-410 | 1500/5 | — | — | — | — | 25 | — | 25 | — |
| KCT-410 | 2000/5 | — | — | — | — | 25 | — | 25 | — |
| KCT-610 | 600/5 | — | — | — | — | 5 | — | 5 | — |
| KCT-610 | 1000/5 | — | — | — | — | 10 | — | 10 | — |
| KCT-610 | 1500/5 | — | — | — | — | 20 | — | 20 | — |
| KCT-610 | 2000/5 | — | — | — | — | 30 | — | 30 | — |
| KCT-810 | 1000/5 | — | — | — | — | 20 | — | 20 | — |
| KCT-810 | 1500/5 | — | — | — | — | 30 | — | 30 | — |
| KCT-810 | 2000/5 | — | — | — | — | 40 | — | 40 | — |
| KCT-1010 | 1500/5 | — | — | — | — | 30 | — | 30 | — |
| KCT-1010 | 2000/5 | — | — | — | — | 40 | — | 40 | — |
| KCT-1010 | 3000/5 | — | — | — | — | 50 | — | 50 | — |
| KCT-1210 | 1500/5 | — | — | — | — | 30 | — | 30 | — |
| KCT-1210 | 2000/5 | — | — | — | — | 40 | — | 40 | — |
| KCT-1210 | 3000/5 | — | — | — | — | 50 | — | 50 | — |
| KCT-1610 | 1500/5 | — | — | — | — | 40 | — | 40 | — |
| KCT-1610 | 2000/5 | — | — | — | — | 50 | — | 50 | — |
| KCT-1610 | 3000/5 | — | — | — | — | 60 | — | 60 | — |
Dimension & outline drawing of KCT-0.66 — click image to zoom / view original.
The KCT-0.66 is an indoor, low-voltage split-core current transformer built to the IEC 61869 and GB/T 20840 standard family, rated 0.66kV with a 5A secondary and intended for current measurement in low-voltage distribution circuits at 50/60Hz. It is an open-type unit whose split core allows it to be placed around existing conductors.
Insulation is dry epoxy resin, giving a solid cast body around the core and windings. Accuracy classes 0.2S, 0.5S, 0.5 and 1.0 are offered, so metering and general measurement duties can be matched to the required class; rated burden in VA is stated on the nameplate and datasheet. The split-core format means installation does not require a power outage, which suits retrofits and live LV boards.
It is intended for indoor service only and must not be installed in outdoor or exposed locations. Secondary terminals must never be open-circuited while the primary is energized. Before commissioning, verify polarity, ratio and insulation resistance, and earth the secondary at one point per the terminal diagram. Custom ratios and accuracy classes are available; request the document package and lead time with your enquiry. [On Request] for weight and dimensions.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.