LA-10Q Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A, accuracy class 0.2S/0.5S, rated burden 5VA. Design: Dry Epoxy Resin, 50/60Hz operation.
Indoor 10kV cast-resin current transformer for MV switchgear, 0.66kV primary, 5A secondary, accuracy 0.2S/0.5S.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LA-10Q | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A | Ratio check at rated frequency |
| Accuracy Class | 0.2S/0.5S | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 5VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
For current transformer (CT) wiring: connect primary terminals in series with the line. Secondary terminals are 1S1/1S2 for the metering winding (0.2S/0.5S) and 2S1/2S2 for the protection winding (10P10). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure rated burden does not exceed 10VA for metering and 15VA for protection. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 12/42/75kV, meaning 12kV highest voltage for equipment, 42kV power-frequency withstand, and 75kV lightning impulse withstand.
Q: Can this CT be used for both metering and protection?
A: Yes, it has dual accuracy classes: 0.2S/0.5S for metering and 10P10 for protection, with separate secondary windings.
Q: What is the short-time thermal current rating?
A: The short-time thermal current is 90 times the rated primary current (90I₁ₙ), and the dynamic stable current is 160I₁ₙ.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.3 0.2S/0.5S | Accuracy class & rated output (VA) COSφ=0.3 0.2 | Accuracy class & rated output (VA) COSφ=0.3 0.5 | Accuracy class & rated output (VA) COSφ=0.3 10P10 | Accuracy class & rated output (VA) COSφ=0.3 10P15 | Short-time thermal current I1th (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| LA-10(Q) | 20-200 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 90 I1n | 160 I1n | 14.5 |
| LA-10(Q) | 300 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 22.5 | 40.5 | 14.5 |
| LA-10(Q) | 400-600 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 30 | 55 | 14.5 |
| LA-10(Q) | 800 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 40 | 72 | 14.5 |
| LA-10(Q) | 1000 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 50 | 90 | 14.5 |
| LAJ-10(Q) | 20-200 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 120 I1n | 215 I1n | 23.5 |
| LAJ-10(Q) | 300 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 30 | 55 | 23.5 |
| LAJ-10(Q) | 400-500 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 40 | 72 | 23.5 |
| LAJ-10(Q) | 600 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 40 | 72 | 23.5 |
| LAJ-10(Q) | 800 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 40 | 72 | 23.5 |
| LAJ-10(Q) | 1000-1500 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 20 | 20 | 25 | — | 50 | / | 23.5 |
| LAJ-10(Q) | 2000-3150 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 20 | 20 | 25 | — | 50 | / | 23.5 |
Dimension & outline drawing of LA-10Q — click image to zoom / view original.
This is an indoor single-phase epoxy resin cast current transformer for 10kV systems, converting primary current to a 5A secondary for metering and protection. The dry epoxy cast insulation removes oil handling and fire risk, while the embedded installation design allows compact switchgear integration. The casting encapsulates the winding for a maintenance-free, pollution-resistant indoor unit.
Accuracy classes 0.2S/0.5S are available with rated output 5VA at 50/60Hz. The parameter table lists 10VA for 0.2S/0.5S and 15VA for 10P10 at COSφ=0.3, with short-time thermal current from 22.5kA to 50kA depending on primary rating and dynamic current from 40.5kA to 90kA. The 14.5kg weight suits panel mounting. Compared with oil-immersed or SF6 designs, this cast unit avoids fluid handling and gas monitoring, though it is strictly for indoor service.
Type and routine test reports support verification; [On Request] for specific test certificates. Typical deployment includes renewable energy collection and storage step-up stations. Mount on the primary busbar, earth the secondary at one point, and never open-circuit the secondary while energized. It is not for outdoor exposure. Ratio and accuracy customization, export packing, and after-sales support are available on request.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-200A、300A、400-500A、600A、800A、1000-1500A、2000-3150A; accuracy combination 0.2S/10P15、0.5S/10P15, multi-grade rated output including 10VA/20VA/25VA. Matched thermal and dynamic withstand parameters for different specifications, net weight 23.5kg, operating ambient temperature -5℃~+40℃.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.