中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLA-10Q
LA-10Q Indoor Single-phase Epoxy Resin Casting Current Transformer
10kVLA-10Q
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A (0.2S/0.5S)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LA-10Q

LA-10Q Indoor Single-phase Epoxy Resin Casting Current Transformer

LA-10Q Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A, accuracy class 0.2S/0.5S, rated burden 5VA. Design: Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • 10kV cast-type CT
  • embedded installation design
  • weight 14.5kg
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LA-10Q

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A
Metering & Protection Class:0.2S/0.5S
Rated Output Burden:5VA
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor 10kV cast-resin current transformer for MV switchgear, 0.66kV primary, 5A secondary, accuracy 0.2S/0.5S.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLA-10QFactory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5ARatio check at rated frequency
Accuracy Class0.2S/0.5SAccuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden5VABurden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium voltage switchgear panels
  • Metering and protection applications up to 12kV
  • Embedded installation in RMU or switchgear
  • Revenue metering with 0.2S accuracy
  • 50/60Hz systems

Not Recommended For

  • Outdoor substations or pole-mounted installations
  • High voltage transmission networks above 12kV
  • Gas-insulated switchgear (GIS) without adapter
  • DC systems or non-sinusoidal waveforms
  • Ambient temperatures outside -5°C to +40°C

Topology & Wiring

For current transformer (CT) wiring: connect primary terminals in series with the line. Secondary terminals are 1S1/1S2 for the metering winding (0.2S/0.5S) and 2S1/2S2 for the protection winding (10P10). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure rated burden does not exceed 10VA for metering and 15VA for protection. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The insulation level is 12/42/75kV, meaning 12kV highest voltage for equipment, 42kV power-frequency withstand, and 75kV lightning impulse withstand.

Q: Can this CT be used for both metering and protection?

A: Yes, it has dual accuracy classes: 0.2S/0.5S for metering and 10P10 for protection, with separate secondary windings.

Q: What is the short-time thermal current rating?

A: The short-time thermal current is 90 times the rated primary current (90I₁ₙ), and the dynamic stable current is 160I₁ₙ.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LA-10Q
11 cols · 12 rows

LA (J)-10 (Q) Series Current Transformer — Technical Data

ModelRated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA) COSφ=0.3 0.2S/0.5SAccuracy class & rated output (VA) COSφ=0.3 0.2Accuracy class & rated output (VA) COSφ=0.3 0.5Accuracy class & rated output (VA) COSφ=0.3 10P10Accuracy class & rated output (VA) COSφ=0.3 10P15Short-time thermal current I1th (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
LA-10(Q)20-2000.2(S)/10P10 0.5(S)/10P1010101015—90 I1n160 I1n14.5
LA-10(Q)3000.2(S)/10P10 0.5(S)/10P1010101015—22.540.514.5
LA-10(Q)400-6000.2(S)/10P10 0.5(S)/10P1010101015—305514.5
LA-10(Q)8000.2(S)/10P10 0.5(S)/10P1010101015—407214.5
LA-10(Q)10000.2(S)/10P10 0.5(S)/10P1010101015—509014.5
LAJ-10(Q)20-2000.2(S)/10P15 0.5(S)/10P1510101015—120 I1n215 I1n23.5
LAJ-10(Q)3000.2(S)/10P15 0.5(S)/10P1510101015—305523.5
LAJ-10(Q)400-5000.2(S)/10P15 0.5(S)/10P1510101015—407223.5
LAJ-10(Q)6000.2(S)/10P15 0.5(S)/10P1510101015—407223.5
LAJ-10(Q)8000.2(S)/10P15 0.5(S)/10P1510101015—407223.5
LAJ-10(Q)1000-15000.2(S)/10P15 0.5(S)/10P1510202025—50/23.5
LAJ-10(Q)2000-31500.2(S)/10P15 0.5(S)/10P1510202025—50/23.5
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LA-10Q — click image to zoom / view original.

Product Overview

About This Product

LA-10Q

This is an indoor single-phase epoxy resin cast current transformer for 10kV systems, converting primary current to a 5A secondary for metering and protection. The dry epoxy cast insulation removes oil handling and fire risk, while the embedded installation design allows compact switchgear integration. The casting encapsulates the winding for a maintenance-free, pollution-resistant indoor unit.

Accuracy classes 0.2S/0.5S are available with rated output 5VA at 50/60Hz. The parameter table lists 10VA for 0.2S/0.5S and 15VA for 10P10 at COSφ=0.3, with short-time thermal current from 22.5kA to 50kA depending on primary rating and dynamic current from 40.5kA to 90kA. The 14.5kg weight suits panel mounting. Compared with oil-immersed or SF6 designs, this cast unit avoids fluid handling and gas monitoring, though it is strictly for indoor service.

Type and routine test reports support verification; [On Request] for specific test certificates. Typical deployment includes renewable energy collection and storage step-up stations. Mount on the primary busbar, earth the secondary at one point, and never open-circuit the secondary while energized. It is not for outdoor exposure. Ratio and accuracy customization, export packing, and after-sales support are available on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LAJ-10Q Indoor Single-phase Epoxy Resin Casting Current Transformer
10kV
Current Transformer50/60Hz

LAJ-10Q

Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-200A、300A、400-500A、600A、800A、1000-1500A、2000-3150A; accuracy combination 0.2S/10P15、0.5S/10P15, multi-grade rated output including 10VA/20VA/25VA. Matched thermal and dynamic withstand parameters for different specifications, net weight 23.5kg, operating ambient temperature -5℃~+40℃.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2010

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1765

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs