Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-200A、300A、400-500A、600A、800A、1000-1500A、2000-3150A; accuracy combination 0.2S/10P15、0.5S/10P15, multi-grade rated output including 10VA/20VA/25VA. Matched thermal and dynamic withstand parameters for different specifications, net weight 23.5kg, operating ambient temperature -5℃~+40℃.
Indoor 10kV current transformer for medium-voltage switchgear, suitable for metering and protection with dual accuracy classes.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LAJ-10Q | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the bushing. Secondary terminals: 1S1/1S2 for metering winding, 2S1/2S2 for protection winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point only. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, and 75kV lightning impulse withstand.
Q: What accuracy classes are available?
A: Available accuracy combinations are 0.2S/10P15 and 0.5S/10P15, suitable for metering and protection.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only, with an ambient temperature range of -5°C to +40°C.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.3 0.2S | Accuracy class & rated output (VA) COSφ=0.3 0.2 | Accuracy class & rated output (VA) COSφ=0.3 0.5 | Accuracy class & rated output (VA) COSφ=0.3 10P10 | Accuracy class & rated output (VA) COSφ=0.3 10P15 | Short-time thermal current I1th (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| LA-10(Q) | 20-200 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 90 I1n | 160 I1n | 14.5 |
| LA-10(Q) | 300 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 22.5 | 40.5 | 14.5 |
| LA-10(Q) | 400-600 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 30 | 55 | 14.5 |
| LA-10(Q) | 800 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 40 | 72 | 14.5 |
| LA-10(Q) | 1000 | 0.2(S)/10P10 0.5(S)/10P10 | 10 | 10 | 10 | 15 | — | 50 | 90 | 14.5 |
| LAJ-10(Q) | 20-200 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 120 I1n | 215 I1n | 23.5 |
| LAJ-10(Q) | 300 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 30 | 55 | 23.5 |
| LAJ-10(Q) | 400-500 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 40 | 72 | 23.5 |
| LAJ-10(Q) | 600 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 40 | 72 | 23.5 |
| LAJ-10(Q) | 800 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 10 | 10 | 15 | — | 40 | 72 | 23.5 |
| LAJ-10(Q) | 1000-1500 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 20 | 20 | 25 | — | 50 | / | 23.5 |
| LAJ-10(Q) | 2000-3150 | 0.2(S)/10P15 0.5(S)/10P15 | 10 | 20 | 20 | 25 | — | 50 | / | 23.5 |
Dimension & outline drawing of LAJ-10Q — click image to zoom / view original.
The LAJ-10Q is a 10kV indoor single-phase current transformer built on a dry epoxy resin casting, a construction that removes oil handling and gives a compact, maintenance-free barrier between primary and secondary. It is intended for metering and protection duties on 10kV indoor switchgear, stepping primary current down to a 5A/1A secondary for instruments and relays.
Electrical performance covers accuracy classes 0.2(S) and 0.5(S) with 10P15 protection, rated outputs of 10VA for metering and 15VA for protection, and short-time thermal and dynamic ratings that scale with primary current. Insulation is rated 12/42/75kV at 50/60Hz, and the unit weighs 23.5kg. For new energy collection and booster stations, this unit suits indoor cubicles where a standard 0.2S/10P15 combination is adequate; non-standard ratios or classes are available [On Request].
Compliance evidence, including calibration certificates for metering, is available [On Request]. Install per the nameplate terminal diagram, observing P1/P2 and H1/H2 orientation, and earth the secondary at one point. Never open-circuit the secondary while energized. Ambient range is -5℃~+40℃, indoor only.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.