中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLDJ1-35
LDJ1-35 Indoor Single-phase Epoxy Resin Casting Current Transformer
35kVLDJ1-35
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 35kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LDJ1-35

LDJ1-35 Indoor Single-phase Epoxy Resin Casting Current Transformer

LDJ1-35 Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • 35kV indoor epoxy cast current transformer
  • abundant current specifications
  • multi-winding accuracy collocation options
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LDJ1-35

Electrical Parameters

Primary Rated Voltage (Un):35kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):40.5/95/185kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

LDJ1-35 is a 35kV indoor epoxy resin cast current transformer, suitable for medium voltage switchgear applications requiring accurate current measurement and protection.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLDJ1-35Factory nameplate marking
Primary Voltage35kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)40.5/95/185kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium voltage switchgear panels
  • Current measurement and protection in 35kV systems
  • Revenue metering with 0.2S accuracy
  • Applications requiring multi-winding configurations

Not Recommended For

  • Outdoor installations
  • High voltage transmission systems above 35kV
  • Gas-insulated switchgear (GIS) without adaptation
  • DC systems

Topology & Wiring

Connect primary in series with the line. Secondary terminals: 1S1/1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure shorting and grounding before disconnecting secondary wiring.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of LDJ1-35?

A: The insulation level is 40.5kV system; power-frequency withstand 95kV; lightning impulse withstand 185kV peak.

Q: What are the available secondary currents?

A: Secondary current options are 5A or 1A.

Q: What accuracy classes are available?

A: Accuracy classes include 0.2S, 0.2, 0.5, and 10P10 with various rated outputs.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LDJ1-35
7 cols · 7 rows

LDJ1-35 Current Transformer — Technical Data

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA)COSφ=0.8Rated secondary currentShort-time thermal current I1th (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
30-3000.5/10P15 15 20 30 20/205A or 1A150 I1n375 I1n70
4000.5/10P15 15 20 40 20/205A or 1A6313070
5000.2/10P15 15 20 40 25/255A or 1A6313070
600-8000.25/10P20 20 30 50 30/305A or 1A6313070
1000-12000.2/520 20 30 50 40/405A or 1A6313070
150010P/10P20 30 50 50 40/405A or 1A8016070
2000—20 30 50 50 50/505A or 1A8016070
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LDJ1-35 — click image to zoom / view original.

Product Overview

About This Product

LDJ1-35

The LDJ1-35 is a 35kV indoor single-phase epoxy resin cast current transformer, used to step primary current down to a 5A or 1A secondary for metering and protection in medium-voltage switchgear. Its dry epoxy body is produced by vacuum casting or automatic pressure gelation, giving a solid, void-free insulation system rather than an oil or gas dielectric.

The unit is available across a wide primary current range, with accuracy class combinations spanning 0.2, 0.25, 0.5 and 10P and rated outputs from 15VA to 50VA depending on the ratio ordered; short-time thermal and dynamic ratings scale with the primary current, and the mass is 70kg. Insulation is rated 40.5/95/185kV at 50/60Hz. Standard catalogue ratios suit routine projects, while non-standard ratios and accuracy combinations are quoted to order.

It is intended for indoor installation in heavy-industry distribution — metallurgy, mining, cement and chemical plants — and is commissioned with insulation resistance, polarity and ratio checks. The secondary must never be open-circuited while the primary is energized. Calibration certificates and routine test documentation are available [On Request], and export packing and after-sales support are arranged at quotation.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs