中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLDZB7-35
LDZB7-35 Indoor Single-phase Epoxy Resin Casting Current Transformer
35kVLDZB7-35
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 35kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LDZB7-35

LDZB7-35 Indoor Single-phase Epoxy Resin Casting Current Transformer

LDZB7-35 Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • 35kV indoor epoxy casting current transformer
  • multiple current grades and rich accuracy collocation schemes
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LDZB7-35

Electrical Parameters

Primary Rated Voltage (Un):35kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):40.5/95/185kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor 35kV class current transformer for medium-voltage switchgear, suitable for metering and protection up to 40.5kV systems.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLDZB7-35Factory nameplate marking
Primary Voltage35kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)40.5/95/185kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium-voltage switchgear panels
  • Revenue metering with 0.2S/0.5S accuracy
  • Protection applications with 5P10/5P20 classes
  • Systems with rated frequency 50/60Hz

Not Recommended For

  • Outdoor installations without additional enclosure
  • High-voltage transmission networks above 40.5kV
  • DC systems or non-sinusoidal waveforms
  • Ambient temperatures outside -5°C to +40°C

Topology & Wiring

Connect primary through the bushing. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The rated insulation level is 40.5/95/185kV, meaning 40.5kV system voltage, 95kV power-frequency withstand, and 185kV lightning impulse withstand.

Q: What accuracy classes are available?

A: Optional accuracy classes include 0.2S/0.5S for metering and 5P10/5P20 for protection, with rated outputs from 10-30VA.

Q: Can this CT be used outdoors?

A: No, it is designed for indoor use only. Outdoor installation would require additional weatherproofing.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LDZB7-35
9 cols · 7 rows

LDZBJ-35 Current Transformer

Rated primary current I1n (A)Accuracy classCombined0.2(S)/0.5(S)0.55P105P20Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
3000.2(S)/0.5(S)/5P/5P 0.2(S)/5P/5P/5P 0.5(S)/5P/5P/5P1015151031.58091
4000.2(S)/0.5(S)/5P/5P 0.2(S)/5P/5P/5P 0.5(S)/5P/5P/5P1015201545112.591
5000.2(S)/0.5(S)/5P/5P 0.2(S)/5P/5P/5P 0.5(S)/5P/5P/5P202515205313091
6000.2(S)/0.5(S)/5P/5P 0.2(S)/5P/5P/5P 0.5(S)/5P/5P/5P303030308016091
8000.2(S)/0.5(S)/5P/5P 0.2(S)/5P/5P/5P 0.5(S)/5P/5P/5P303030308016091
1000-12000.2(S)/0.5(S)/5P/5P 0.2(S)/5P/5P/5P 0.5(S)/5P/5P/5P3030303010016091
1500-31500.2(S)/0.5(S)/5P/5P 0.2(S)/5P/5P/5P 0.5(S)/5P/5P/5P3030303010016091
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LDZB7-35 — click image to zoom / view original.

Product Overview

About This Product

LDZB7-35

The LDZB7-35 is a 35 kV indoor single-phase epoxy resin cast current transformer, typically installed in switchgear bays and ring-main units to step primary current down to 5A/1A for metering and protection. Its dry epoxy resin body insulates the primary and secondary windings, and each unit is routine-tested at the factory for ratio and polarity before dispatch, with test records available [On Request].

The rated output window and accuracy class combinations are confirmed on the nameplate and official datasheet, allowing the secondary burden to be matched to the connected relays and meters. The insulation level is 40.5/95/185kV at 50/60Hz, and the ambient range is -5℃~+40℃. Compliance follows the GB/T 20840 series, with type and routine test documentation supplied as part of the delivery package.

This unit is for indoor service only and must not be installed in outdoor exposed locations. Primary connections follow the P1/P2 markings, with the secondary earthed at one point; the secondary must never be open-circuited while energized. OEM and private-label options, customized ratios and accuracy classes, and the routine test report package are available on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs