Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-100A、150A、200-300A、400-800A、1000-1250A; accuracy combination 0.2S/10P、0.5S/10P with rated output 10VA/15VA/20VA/25VA. Short-time thermal current 150I₁ₙ, dynamic stable current 375I₁ₙ, net weight 19kg, operating ambient temperature -5℃~+40℃.
Indoor 10kV cast resin current transformer for MV switchgear, suitable for metering and protection up to 1250A.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LFZJ1-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
connect primary through the window; secondary terminals are 1S1/1S2 for metering, and 2S1/2S2 for protection if applicable. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.
Q: What are the available accuracy combinations?
A: 0.2S/10P and 0.5S/10P with rated outputs 10VA, 15VA, 20VA, or 25VA.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 | Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 20-100 | 0.2(S)/5P10 | 10 10 15 | 150 1r | 375 1r | 19 |
| 150 | 0.2(S)/5P10 | 10 10 15 | 16 | 40 | 19 |
| 200-300 | 0.2(S)/5P10 | 10 10 15 | 20 | 50 | 19 |
| 400 | 0.2(S)/5P10 | 10 10 15 | 31.5 | 80 | 19 |
| 600 | 0.2(S)/5P10 | 10 10 15 | 40 | 100 | 19 |
| 1000-1250 | 0.2(S)/5P10 | 15 20 25 | 60 | 150 | 19 |
Dimension & outline drawing of LFZJ1-10 — click image to zoom / view original.
The LFZJ1-10 is a 10 kV indoor single-phase epoxy resin cast current transformer that addresses two common medium-voltage metering problems: saturation under high through-fault currents and space constraints inside switchgear cubicles. Its circular mounting structure and dry cast construction suit compact panel layouts.
The primary conductor and secondary windings are encapsulated in cast epoxy resin, giving a dry insulation system rated 12/42/75 kV. Secondary output is 5A/1A, with accuracy classes 0.2(S)/0.5(S) and rated burdens of 10VA, 15VA, 20VA, 25VA at 50/60Hz. Each unit is routine-tested for ratio and polarity before dispatch, with type-test evidence available [On Request].
Intended for indoor service between -5℃ and +40℃, it is installed in medium-voltage switchgear and ring-main units. Earth the secondary at one point and verify the connected burden in VA before energisation. Never open-circuit the secondary while the primary is energised; the resulting voltage can destroy insulation and endanger personnel. Standard ratios ship from stock; non-standard ratios, accuracy classes and documentation packages are quoted on request. The unit weighs 19kg.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.