Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-100A、150A、200-300A、400-800A、1000-1250A; accuracy combination 0.2S/5P、0.5S/5P with rated output 15VA/20VA/30VA. Short-time thermal current 150I₁ₙ, dynamic stable current 375I₁ₙ, net weight 25kg, operating ambient temperature -5℃~+40℃.
Indoor 10kV current transformer for MV switchgear, suitable for metering and protection with 0.2S/5P accuracy.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LFZJ2-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, and 75kV lightning impulse withstand.
Q: Can this CT be used for both metering and protection?
A: Yes, it offers accuracy combination 0.2S/5P, suitable for both metering (0.2S) and protection (5P).
Q: What are the available primary current ranges?
A: Optional primary currents: 20-100A, 150A, 200-300A, 400-800A, 1000-1250A.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) 0.2 (S) | Accuracy class & rated output (VA) 0.5 (S) | Accuracy class & rated output (VA) 5P10 | Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|
| 20-100 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 150*I*n | 375*I*n | 19 |
| 150 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 16 | 40 | 19 |
| 200-300 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 20 | 50 | 19 |
| 400-600 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 31.5 | 80 | 19 |
| 1000-1250 | 0.2(S)/5P 0.5(S)/5P | 15 | 20 | 25 | 40 | 100 | 19 |
Dimension & outline drawing of LFZJ2-10 — click image to zoom / view original.
This is a 10 kV indoor single-phase epoxy resin cast current transformer, the LFZJ2-10, intended to step primary current down to a 5 A or 1 A secondary for metering and protection within switchgear and substation bays. Its dry epoxy resin body is produced by vacuum casting or automatic pressure gelation, giving a solid, air-gap-free insulation system that helps the unit withstand the 12/42/75 kV insulation level in indoor service. Accuracy classes 0.2(S) and 0.5(S) are available with rated burdens of 10 VA, 15 VA, 20 VA or 25 VA at 50/60 Hz, and the design is positioned as a single-core metering or metering-plus-protection choice where a larger mounting dimension and a 25 kg mass suit the panel. Compliance evidence and test documentation are available on request. Typical deployment covers infrastructure such as rail, data centres, hospitals and water works. Earth the secondary at one point and never open-circuit it while energised.
Do not over-specify accuracy class beyond the application; doing so adds cost without benefit. Ratio and accuracy customisation, export packing and after-sales support are offered, with delivery and documentation scope confirmed at enquiry.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.