Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-100A、150A、200-300A、400-800A、1000-1250A; accuracy combination 0.2S/5P、0.5S/5P with rated output 15VA/20VA/30VA. Short-time thermal current 150I₁ₙ, dynamic stable current 375I₁ₙ, net weight 23kg, operating ambient temperature -5℃~+40℃.
Indoor 10kV current transformer for protection and metering, rated secondary 5A/1A, epoxy cast, IEC 61869 compliant.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LFZJ3-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
connect primary in series with line. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground one point of secondary circuit. Insulation level: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What are the accuracy classes available?
A: 0.2S/5P and 0.5S/5P with rated outputs 15VA/20VA/30VA.
Q: What is the short-time thermal current rating?
A: 150I₁ₙ, with dynamic stable current 375I₁ₙ.
Q: Is it suitable for outdoor use?
A: No, it is designed for indoor applications only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) 0.2 (S) | Accuracy class & rated output (VA) 0.5 (S) | Accuracy class & rated output (VA) 5P10 | Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|
| 20-100 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 150/1r | 375/1r | 19 |
| 150 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 15 | 40 | 19 |
| 200-300 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 20 | 50 | 19 |
| 400-600 | 0.2(S)/5P 0.5(S)/5P | 10 | 10 | 15 | 31.5 | 80 | 19 |
| 1000-1250 | 0.2(S)/5P 0.5(S)/5P | 15 | 20 | 25 | 40 | 100 | 19 |
Dimension & outline drawing of LFZJ3-10 — click image to zoom / view original.
This is a 10 kV indoor single-phase epoxy resin cast current transformer, designed to step primary current down to a 5A/1A secondary for metering and protection inside switchgear such as KYN28 cubicles, ring-main units and substation bays. Its dry epoxy resin body and optimized structure layout keep the 23 kg unit compact enough to fit tight indoor compartments without wasting panel space.
Accuracy classes 0.2(S) and 0.5(S) are available with rated burdens of 10VA, 15VA, 20VA and 25VA, and the insulation level is 12/42/75kV for 50/60Hz service. The design follows the IEC 61869 series, and routine and type test documentation can be supplied [On Request]. Typical deployment covers infrastructure projects such as rail transit, data centres, hospitals and water utilities, where the ambient range of -5℃ to +40℃ applies.
Because it is an indoor unit, it must not be installed in open-air locations. During commissioning, check insulation resistance, polarity and ratio before energizing. Never open-circuit the secondary while the primary is energized. Ratio and accuracy-class variants, export packing and after-sales support are available; consult the nameplate and datasheet for figures not listed here.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.