中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLFZJ9-10Q
LFZJ9-10Q Indoor Single-phase Epoxy Resin Casting Current Transformer
10kVLFZJ9-10Q
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LFZJ9-10Q

LFZJ9-10Q Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:5-150A、200-300A、400-500A、600-1000A、1250-1500A; accuracy combination 0.2S/10P10 & 0.5/10P10, rated output:0.2S 10VA, 0.5 10VA, 10P10 15VA. Corresponding short-time thermal current and dynamic stable current vary by current grade, net weight 21kg, ambient operating temperature -5℃~+40℃.

Key Engineering Advantages

  • 10kV flange-mounted epoxy cast CT
  • corrugated insulation structure
  • weight 21kg
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LFZJ9-10Q

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):12/42/75kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor 10kV epoxy cast CT for MV switchgear; suitable for metering and protection up to 1500A.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLFZJ9-10QFactory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)12/42/75kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 10kV indoor switchgear panels
  • Metering and protection applications
  • Epoxy resin insulated environments
  • 50/60Hz systems

Not Recommended For

  • Outdoor installations
  • Gas-insulated switchgear (GIS)
  • High-voltage transmission (above 10kV)
  • DC systems

Topology & Wiring

secondary terminals 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal conventions.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What are the available primary current ranges?

A: Optional ranges: 5-150A, 200-300A, 400-500A, 600-1000A, 1250-1500A.

Q: What accuracy combinations are offered?

A: 0.2S/10P10 and 0.5/10P10.

Q: What is the insulation level?

A: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LFZJ9-10Q
8 cols · 5 rows

LFZJ9-10Q Current Transformer

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA) COSΦ=0.8 0.2 (S)Accuracy class & rated output (VA) COSΦ=0.8 0.5Accuracy class & rated output (VA) COSΦ=0.8 10P10Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
5-1500.2(S)/10P10 0.5/10P10101015150 I1n375 I1n21
200-3000.2(S)/10P10 0.5/10P1010101531.58021
400-5000.2(S)/10P10 0.5/10P101010154510021
600-10000.2(S)/10P10 0.5/10P101010156313021
1250-15000.2(S)/10P10 0.5/10P101010158016021
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LFZJ9-10Q — click image to zoom / view original.

Product Overview

About This Product

LFZJ9-10Q

The LFZJ9-10Q is a 10kV indoor single-phase epoxy resin cast current transformer, built for revenue metering and protection duties where the 0.2(S) class supports accurate energy accounting across the load range, with a 10P10 protection core alongside.

Its dry epoxy resin body uses a corrugated insulation structure, and each unit is released against routine ratio and polarity checks, with test documentation available [On Request]. Accuracy is held to 0.2(S) and 10P10, with rated output 10VA for metering and 15VA for the 10P10 core, at 50/60Hz and insulation level 12/42/75kV. Short-time thermal current and dynamic ratings scale with the primary current selected, from 150 I1n and 375 I1n at the 5-150A range up to 80kA and 160kA at 1250-1500A; weight is 21kg throughout.

This unit is flange-mounted for indoor medium-voltage switchgear and ring-main units. Earth the secondary at one point and never open-circuit it while energized. It is not intended for DC or non-standard frequencies. Sample and type-test support, ratio and class customization, and the document package are quoted on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LFZJ9-10A Indoor Single-phase Epoxy Resin Casting Current Transformer
10kV
Current Transformer50/60Hz

LFZJ9-10A

Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:5-150A、200-300A、400-500A、600-1000A、1250-1500A; accuracy combination 0.2S/10P10、0.5/10P10 with rated output:0.2S class 10VA, 0.5 class 10VA, 10P10 class 15VA. Short-time thermal current 150I₁ₙ~80I₁ₙ and rated dynamic current 375I₁ₙ~160I₁ₙ corresponding to different current grades, net weight 21kg, operating ambient temperature -5℃~+40℃.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2010

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1765

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs