Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current:20-50A、75A、100A、150A、200A、300A; accuracy combinations:0.2S/0.5、0.2S/10P、0.5/10P, rated output:0.2S10VA、0.5 15VA、10P15 20VA、10P20 25VA. Matched short-time thermal current & dynamic stable current for each gear, net weight 35kg, ambient operating temperature -5℃~+40℃.
Indoor 10kV cast-resin current transformer for MV switchgear, metering and protection. Suitable for 50/60Hz systems up to 12kV.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LFZZB5-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.
Q: What accuracy combinations are available?
A: 0.2S/0.5, 0.2S/10P, and 0.5/10P.
Q: Can it be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) | Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 20-80 | 0.2(5)/0.5 0.2(5)/0.5P 0.5/10P | 0.2(5): 10, 0.5: 15, 10P15: 20, 10P20: 25 | 80/1In | 200/1In | 35 |
| 100 | 0.2(5)/0.5 0.2(5)/0.5P 0.5/10P | 0.2(5): 10, 0.5: 15, 10P15: 20, 10P20: 25 | 6 | 15 | 35 |
| 150 | 0.2(5)/0.5 0.2(5)/0.5P 0.5/10P | 0.2(5): 10, 0.5: 15, 10P15: 20, 10P20: 25 | 8 | 20 | 35 |
| 200 | 0.2(5)/0.5 0.2(5)/0.5P 0.5/10P | 0.2(5): 10, 0.5: 15, 10P15: 20, 10P20: 25 | 12 | 30 | 35 |
| 300 | 0.2(5)/0.5 0.2(5)/0.5P 0.5/10P | 0.2(5): 10, 0.5: 15, 10P15: 20, 10P20: 25 | 16 | 40 | 35 |
| 400 | 0.2(5)/0.5 0.2(5)/0.5P 0.5/10P | 0.2(5): 10, 0.5: 15, 10P15: 20, 10P20: 25 | 24 | 60 | 35 |
Dimension & outline drawing of LFZZB5-10 — click image to zoom / view original.
The LFZZB5-10 is a 10 kV indoor single-phase current transformer built with a dry epoxy resin casting, a construction that removes the need for oil handling and gives the winding a solid dielectric. Its rectangular form suits panel layouts where space is tight, and the unit weighs 35 kg.
The secondary is available as 5 A or 1 A, and the accuracy combinations cover metering and protection duties: 0.2(5) at 10 VA, 0.5 at 15 VA, 10P15 at 20 VA and 10P20 at 25 VA. Short-time thermal current and rated dynamic stability scale with the primary rating, reaching 80/1In and 200/1In respectively at the lowest primary currents. Insulation is rated 12/42/75kV at 50/60 Hz. This indoor unit is not for outdoor open-air installation, and the secondary must never be open-circuited while energized. Compliance follows the GB/T 20840 series, with type-test evidence and routine documents available [On Request]. Typical deployment is in wind, photovoltaic and storage step-up collection systems, where the unit is installed indoors. Before energization, check insulation resistance, polarity and ratio. Custom ratios and accuracy classes, sample support and the document package are quoted on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.