中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLJZ-75-110-125
LJZ-Φ75/110/125 10kV Outdoor Three-Phase Integrated Current Transformer with Zero-Sequence for Pole-Mounted Circuit Breaker
Up to 35kVLJZ-75-110-125
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — Up to 35kV
Secondary Metering (1S1 - 1S2): ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LJZ-75-110-125

LJZ-Φ75/110/125 10kV Outdoor Three-Phase Integrated Current Transformer with Zero-Sequence for Pole-Mounted Circuit Breaker

Zero sequence current transformer for 35kV and below voltage systems. Used for cable ground protection in small grounding current systems. Rated frequency 50Hz or 60Hz. Available in Φ75, Φ110, Φ125 inner diameter sizes. Primary insulation guaranteed by cable, secondary winding insulation tested. Compliant with IEC 61869 and GB/T 20840 standards. Matching relay model DL-11/0.2, epoxy resin cast construction.

Key Engineering Advantages

  • 35kV zero sequence CT
  • Φ75/Φ110/Φ125 sizes
  • cable ground protection
  • IEC compliant
  • epoxy cast
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LJZ-75-110-125

Electrical Parameters

Primary Rated Voltage (Un):Up to 35kV
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Environmental Class:Epoxy resin cast
Standards Conformance:IEC 61869, GB/T 20840
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

Cable ground fault protection
GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Zero-sequence current transformer for 35kV and below systems, designed for cable ground fault protection in small grounding current systems. Suitable for outdoor pole-mounted circuit breaker applications.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 61869, GB/T 20840
Model CodeLJZ-75-110-125Factory nameplate marking
Primary VoltageUp to 35kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 61869, GB/T 20840Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentEpoxy resin castPer datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 35kV and below cable ground fault protection
  • Small grounding current systems
  • Outdoor pole-mounted circuit breaker installations
  • Zero-sequence current measurement

Not Recommended For

  • Indoor switchgear applications
  • High-voltage transmission lines above 35kV
  • Revenue metering applications

Topology & Wiring

Connect secondary terminals 1S1 and 1S2 to the protection relay. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure the primary cable passes through the CT window (Φ75/Φ110/Φ125) and is properly insulated for the system voltage.

Standards & Compliance

Compliant with: IEC 61869, GB/T 20840

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary voltage rating?

A: Up to 35kV.

Q: What are the available inner diameters?

A: Φ75, Φ110, and Φ125.

Q: What standards does it comply with?

A: IEC 61869 and GB/T 20840.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LJZ-75-110-125
5 cols · 1 rows

LJZ-φ75, 110, 125 Series Zero-Sequence Current Transformer

Connecting lead resistance (Ω)Total secondary external impedance (Ω)Relay pickup current (A)Sensitivity (A)Relay scale (A)
1≤100.1≤100.1-0.2
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LJZ-75-110-125 — click image to zoom / view original.

Product Overview

About This Product

LJZ-75-110-125

The LJZ-Φ75/110/125 is a 10 kV outdoor three-phase integrated current transformer with zero-sequence detection, built to the IEC 61869 and GB/T 20840 standards framework and intended for cable ground-fault protection on pole-mounted circuit breakers. Its dry epoxy resin cast body is suited to outdoor service, where the insulation system must tolerate the environmental exposure of an overhead installation; specific protection figures are [On Request].

The unit is a zero-sequence CT for systems up to 35 kV, offered in Φ75, Φ110 and Φ125 cable-passing sizes, and is positioned for cable ground protection rather than metering-class duties. For the matched sensitivity row, the secondary external total impedance is ≤10 Ω with a relay pickup current of 0.1 A and a sensitivity of ≤10 A at a relay setting of 0.1-0.2 A; accuracy class and rated output are [On Request].

Deployment is on pole-mounted breakers in cable ground-fault protection, with secondary wiring per the nameplate terminal diagram and the secondary earthed at one point. The secondary must never be open-circuited while energized. Ratios and accuracy classes can be customized, and export packing and after-sales support are available on inquiry.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LJZN1-10 10kV Indoor Epoxy Cast Metering Current Transformer
10kV
Current Transformer50/60Hz

LJZN1-10

10kV Indoor Epoxy Cast Metering Current Transformer

10kV indoor epoxy resin cast current transformer specially designed for grid energy metering. Dual windings support 0.2S high-precision metering and protection. Rated output 10-15VA, primary current range 20A to 2000A. Compliant with IEC 61869 and GB/T 20840 standards. Ultra-low partial discharge design ensures metering accuracy. Vacuum epoxy casting process, moisture and salt-spray resistant. Suitable for State Grid metering applications, customizable ratio.

Accuracy Class0.2S metering class
Insulation TypeDry Epoxy Resin
Rated Burden10-15VA
ComplianceIEC 61869
View Specs
LJZN1-35 35kV Indoor Epoxy Cast Current Transformer for Grid Metering
35kV
Current Transformer50/60Hz

LJZN1-35

35kV Indoor Epoxy Cast Current Transformer for Grid Metering

35kV indoor epoxy resin cast current transformer for power grid metering. Dual windings for 0.2S high-precision metering and protection. Rated output 10-15VA, wide primary current range. Compliant with IEC 61869 and GB/T 20840 standards. Ultra-low partial discharge ensures long-term metering accuracy. Vacuum epoxy casting, compact pillar design, excellent insulation performance. Suitable for 35kV grid metering applications, customizable ratio.

Accuracy Class0.2S metering class
Insulation TypeDry Epoxy Resin
Rated Burden10-15VA
ComplianceIEC 61869
View Specs
CGIS2070 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2070-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2070 I is an indoor epoxy resin casting current transformer designed for CGIS gas-insulated switchgear at 35kV. It is available with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20 and 10P20. The epoxy casting has an outer diameter of Ø205mm and a through (inner) diameter of Ø70mm for busbar installation, and is rated for 50/60Hz operation. Metering classes (0.2FS10, 0.5SFS10) and protection classes (5P10, 10P10, 5P20, 10P20) cover both measurement and relay protection inside CGIS panels.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs