10kV indoor epoxy resin cast current transformer specially designed for grid energy metering. Dual windings support 0.2S high-precision metering and protection. Rated output 10-15VA, primary current range 20A to 2000A. Compliant with IEC 61869 and GB/T 20840 standards. Ultra-low partial discharge design ensures metering accuracy. Vacuum epoxy casting process, moisture and salt-spray resistant. Suitable for State Grid metering applications, customizable ratio.
LJZN1-10 is a 10kV indoor epoxy cast current transformer with 0.2S accuracy, ideal for high-precision energy metering in State Grid applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869, GB/T 20840 |
| Model Code | LJZN1-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A or 1A | Ratio check at rated frequency |
| Accuracy Class | 0.2S metering class | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 10-15VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869, GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Indoor epoxy resin cast | Per datasheet limits |
Ideal For
Not Recommended For
connect primary in series with the line. Secondary terminals: 1S1/1S2 for metering winding, 2S1/2S2 for protection winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 terminal markings.
Compliant with: IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the accuracy class of LJZN1-10?
A: 0.2S metering class.
Q: What is the primary current range?
A: 20A to 2000A.
Q: What standards does it comply with?
A: IEC 61869 and GB/T 20840.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Voltage class (kV) | Rated primary current (A) | Accuracy classCombined | Rated output (VA) | Rated Secondary thermal limit output (VA) | Rated dynamic current (kA) |
|---|---|---|---|---|---|
| 10, 20 | 20 | 0.2S | 10 | 5 | 2 12.5 |
| 10, 20 | 30 | 0.2S | 10 | 5 | 2 20 |
| 10, 20 | 40 | 0.2S | 10 | 5 | 2 20 |
| 10, 20 | 50 | 0.2S | 10 | 5 | 2 40 |
| 10, 20 | 75 | 0.2S | 10 | 5 | 2 40 |
| 10, 20 | 100-200 | 0.2S | 10 | 5 | 20 65 |
| 10, 20 | 300-500 | 0.2S | 10 | 5 | 25 4 63 |
| 10, 20 | 600-800 | 0.2S | 10 | 5 | 31.5 4 80 |
| 10, 20 | 1000-2000 | 0.2S | 10 | 5 | 40 4 100 |
| 10, 20 | 50 | 0.2S | 15 | 5 | 8 0 |
| 10, 20 | 100 | 0.2S | 15 | 5 | 16 0 |
| 10, 20 | 150-200 | 0.2S | 15 | 5 | 31.5 4 80 |
| 10, 20 | 300-500 | 0.2S | 15 | 5 | 25 4 63 |
| 10, 20 | 600-800 | 0.2S | 15 | 5 | 31.5 4 80 |
Dimension & outline drawing of LJZN1-10 — click image to zoom / view original.
The LJZN1-10 is a 10 kV indoor epoxy-cast current transformer for power grid energy metering, converting primary current to a 5 A or 1 A secondary for revenue meters and instruments. Its dry epoxy resin body insulates the primary and dual secondary windings, with dielectric design and creepage details for the 10 kV class available in the official datasheet.
Accuracy is 0.2S metering class with rated burden of 10–15 VA at 50/60 Hz, suited to tariff metering where low current accuracy matters; short-time thermal and dynamic ratings are stated on the nameplate. As an indoor unit it is not a substitute for outdoor types, and it must not be applied above its 10 kV rating.
Compliance follows IEC 61869 and GB/T 20840, with routine and type test evidence and documentation on request. Typical deployment is utility substations, new-energy collector stations and storage step-up metering. Observe P1/P2 and secondary polarity, earth the secondary at one point, and never open-circuit the secondary while energized. OEM branding, ratio and class variants, and delivery schedules are quoted on request.
Same product family, different ratings — compare before you specify.
35kV Indoor Epoxy Cast Current Transformer for Grid Metering
35kV indoor epoxy resin cast current transformer for power grid metering. Dual windings for 0.2S high-precision metering and protection. Rated output 10-15VA, wide primary current range. Compliant with IEC 61869 and GB/T 20840 standards. Ultra-low partial discharge ensures long-term metering accuracy. Vacuum epoxy casting, compact pillar design, excellent insulation performance. Suitable for 35kV grid metering applications, customizable ratio.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.