KEMA & ISO 9001/14001 Certified|Exporting to 50+ Countries (IEC 61869-3 / IEEE C57.13)
24/7 Global Engineering Hotline: 86 18852046268|sales@potentialtransformers.com
中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLJZN1-10
LJZN1-10 10kV Indoor Epoxy Cast Metering Current Transformer
10kVLJZN1-10
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A or 1A (0.2S metering class)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LJZN1-10

LJZN1-10 10kV Indoor Epoxy Cast Metering Current Transformer

10kV indoor epoxy resin cast current transformer specially designed for grid energy metering. Dual windings support 0.2S high-precision metering and protection. Rated output 10-15VA, primary current range 20A to 2000A. Compliant with IEC 61869 and GB/T 20840 standards. Ultra-low partial discharge design ensures metering accuracy. Vacuum epoxy casting process, moisture and salt-spray resistant. Suitable for State Grid metering applications, customizable ratio.

Key Engineering Advantages

  • 10kV metering dedicated CT
  • 0.2S high accuracy
  • ultra-low partial discharge
  • dual windings
  • IEC 61869 compliant
  • State Grid standard
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LJZN1-10

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A or 1A
Metering & Protection Class:0.2S metering class
Rated Output Burden:10-15VA
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Environmental Class:Indoor epoxy resin cast
Standards Conformance:IEC 61869, GB/T 20840
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

Power grid energy metering
GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

LJZN1-10 is a 10kV indoor epoxy cast current transformer with 0.2S accuracy, ideal for high-precision energy metering in State Grid applications.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 61869, GB/T 20840
Model CodeLJZN1-10Factory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5A or 1ARatio check at rated frequency
Accuracy Class0.2S metering classAccuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden10-15VABurden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 61869, GB/T 20840Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentIndoor epoxy resin castPer datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 10kV indoor switchgear and panels
  • Energy metering with 0.2S accuracy
  • State Grid standardized metering points
  • Dual winding applications (metering and protection)
  • Indoor environments with moisture and salt-spray exposure

Not Recommended For

  • Outdoor installations
  • High-voltage systems above 10kV
  • Protection-only applications requiring high accuracy class
  • Gas-insulated switchgear (GIS) without adapter
  • DC systems

Topology & Wiring

connect primary in series with the line. Secondary terminals: 1S1/1S2 for metering winding, 2S1/2S2 for protection winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 terminal markings.

Standards & Compliance

Compliant with: IEC 61869, GB/T 20840

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the accuracy class of LJZN1-10?

A: 0.2S metering class.

Q: What is the primary current range?

A: 20A to 2000A.

Q: What standards does it comply with?

A: IEC 61869 and GB/T 20840.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LJZN1-10
6 cols · 14 rows

State Grid metering Current Transformer — Technical Data

Voltage class (kV)Rated primary current (A)Accuracy classCombinedRated output (VA)Rated Secondary thermal limit output (VA)Rated dynamic current (kA)
10, 20200.2S1052 12.5
10, 20300.2S1052 20
10, 20400.2S1052 20
10, 20500.2S1052 40
10, 20750.2S1052 40
10, 20100-2000.2S10520 65
10, 20300-5000.2S10525 4 63
10, 20600-8000.2S10531.5 4 80
10, 201000-20000.2S10540 4 100
10, 20500.2S1558 0
10, 201000.2S15516 0
10, 20150-2000.2S15531.5 4 80
10, 20300-5000.2S15525 4 63
10, 20600-8000.2S15531.5 4 80
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LJZN1-10 — click image to zoom / view original.

Product Overview

About This Product

LJZN1-10

The LJZN1-10 is a 10 kV indoor epoxy-cast current transformer for power grid energy metering, converting primary current to a 5 A or 1 A secondary for revenue meters and instruments. Its dry epoxy resin body insulates the primary and dual secondary windings, with dielectric design and creepage details for the 10 kV class available in the official datasheet.

Accuracy is 0.2S metering class with rated burden of 10–15 VA at 50/60 Hz, suited to tariff metering where low current accuracy matters; short-time thermal and dynamic ratings are stated on the nameplate. As an indoor unit it is not a substitute for outdoor types, and it must not be applied above its 10 kV rating.

Compliance follows IEC 61869 and GB/T 20840, with routine and type test evidence and documentation on request. Typical deployment is utility substations, new-energy collector stations and storage step-up metering. Observe P1/P2 and secondary polarity, earth the secondary at one point, and never open-circuit the secondary while energized. OEM branding, ratio and class variants, and delivery schedules are quoted on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LJZN1-35 35kV Indoor Epoxy Cast Current Transformer for Grid Metering
35kV
Current Transformer50/60Hz

LJZN1-35

35kV Indoor Epoxy Cast Current Transformer for Grid Metering

35kV indoor epoxy resin cast current transformer for power grid metering. Dual windings for 0.2S high-precision metering and protection. Rated output 10-15VA, wide primary current range. Compliant with IEC 61869 and GB/T 20840 standards. Ultra-low partial discharge ensures long-term metering accuracy. Vacuum epoxy casting, compact pillar design, excellent insulation performance. Suitable for 35kV grid metering applications, customizable ratio.

Accuracy Class0.2S metering class
Insulation TypeDry Epoxy Resin
Rated Burden10-15VA
ComplianceIEC 61869
View Specs
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2010

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1765

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs