Split-core zero sequence current transformer specially designed for 6kV-35kV indoor cable head outlets. Can be installed without power interruption - split into two halves and bolted together. Rated frequency 50Hz or 60Hz. Inner diameter range Φ100 to Φ250, suitable for various cable sizes. Compliant with IEC 61869 and GB/T 20840 standards. Hot-line installation capability saves downtime and maintenance cost. Epoxy resin cast construction, reliable performance.
Split-core zero-sequence CT for 6-35kV indoor cable head outlets, installable without power interruption.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869, GB/T 20840 |
| Model Code | LKZB-100-250 | Factory nameplate marking |
| Primary Voltage | 6kV-35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869, GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Epoxy resin cast | Per datasheet limits |
Ideal For
Not Recommended For
For current transformers, never open-circuit the secondary while energized - hazardous voltage. Terminals: 1S1/1S2 for main winding, 2S1/2S2 for zero-sequence winding. Ground the secondary at one point. Follow IEC 61869 for terminal markings.
Compliant with: IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: Can this CT be installed without power interruption?
A: Yes, the split-core design allows hot-line installation.
Q: What is the inner diameter range?
A: Φ100 to Φ250, suitable for various cable sizes.
Q: What standards does it comply with?
A: IEC 61869 and GB/T 20840.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated current ratio (A) | Accuracy class | Rated output (VA) |
|---|---|---|
| 50/1 | 10P10 | 1 |
| 75/1 | 10P10 | 1.5 |
| 100/1~150/1 | 10P10 | 2.5 |
| 200/1~600/1 | 10P10 | 5 |
Dimension & outline drawing of LKZB-100-250 — click image to zoom / view original.
The LKZB-Φ100 to Φ250 is a 6kV–35kV split-core zero-sequence current transformer built to IEC 61869 and GB/T 20840, used to detect earth-fault current in three-phase distribution systems. Its dry epoxy resin casting forms the primary insulation, with the split-core window spanning conductor diameters from Φ100 to Φ250 for hot-line installation.
Accuracy class 10P10 is available across the range, with rated outputs of 1VA, 1.5VA, 2.5VA or 5VA depending on the current ratio: 50/1 at 1VA, 75/1 at 1.5VA, 100/1 to 150/1 at 2.5VA, and 200/1 to 600/1 at 5VA. The unit is intended for indoor cable-head outlet earth-fault protection and is not suited to outdoor overhead-line or pole-mounted service; other environmental ratings are [On Request].
Primary conductors pass through the core window, and the secondary circuit must never be open-circuited while the primary is energized. Ratio, accuracy class and output can be customized, with OEM marking and routine test documentation available; delivery terms are quoted on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.