中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLMK8-0.66
LMK8-0.66 Indoor Low Voltage Bury-plug Current Transformer 0.66kV
0.66kVLMK8-0.66
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 0.66kV
Secondary Metering (1S1 - 1S2):5A/1A (0.2/0.5/1.0)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LMK8-0.66

LMK8-0.66 Indoor Low Voltage Bury-plug Current Transformer 0.66kV

Indoor low voltage bury-plug type current transformer, 0.66kV rated, epoxy resin casting type, for current measurement, control and protection in low voltage distribution systems. Complies with IEC 61869 and GB/T 20840 standards. Bury-plug terminal design with connection pipes, easy and safe wiring. Compact size, transparent dust cover, clean and safe. Wide range of current ratios available. Customizable ratios and specifications.

Key Engineering Advantages

  • LV bury-plug current transformer
  • 0.66kV
  • epoxy resin
  • easy safe wiring
  • transparent dust cover
  • customizable
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LMK8-0.66

Electrical Parameters

Primary Rated Voltage (Un):0.66kV
Secondary Winding Currents:5A/1A
Metering & Protection Class:0.2/0.5/1.0
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Standards Conformance:IEC 61869 / GB/T 20840
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor low-voltage current transformer for 0.66kV systems, suitable for measurement and protection in distribution panels.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 61869 / GB/T 20840
Model CodeLMK8-0.66Factory nameplate marking
Primary Voltage0.66kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class0.2/0.5/1.0Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 61869 / GB/T 20840Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Low voltage distribution panels (0.66kV)
  • Current measurement and metering
  • Protection and control circuits
  • Indoor installations with dry epoxy insulation

Not Recommended For

  • Outdoor installations
  • High voltage systems above 1kV
  • Gas-insulated switchgear (GIS)
  • DC applications

Topology & Wiring

Connect primary through the bushing. Secondary terminals are 1S1/1S2 for the main winding; if dual ratio, use 2S1-2S2 for protection winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point per IEC 61869.

Standards & Compliance

Compliant with: IEC 61869 / GB/T 20840

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the accuracy class of this CT?

A: Available accuracy classes are 0.2, 0.5, and 1.0.

Q: What are the secondary ratings?

A: Secondary ratings are 5A or 1A.

Q: Is this CT suitable for outdoor use?

A: No, it is designed for indoor use only.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LMK8-0.66
10 cols · 34 rows

LMKB-0.66 Series Current Transformer — Technical Data

ModelRated primary current (A)Rated secondary current (A)Accuracy class (Combined )Rated output (VA)Primary turns (turns)Overall dimensionsWindow dimensions (mm) W×H
WDH
LMKB-0.66/301050.55656357226×16
LMKB-0.66/301550.55456357226×16
LMKB-0.66/302050.55356357226×16
LMKB-0.66/302550.55256357226×16
LMKB-0.66/303050.55256357226×16
LMKB-0.66/304050.55256357226×16
LMKB-0.66/305050.55156357226×16
LMKB-0.66/306050.55156357226×16
LMKB-0.66/307550.55156357226×16
LMKB-0.66/3010050.55156357226×16
LMKB-0.66/3015050.55156357226×16
LMKB-0.66/3020050.55156357226×16
LMKB-0.66/3025050.55156357226×16
LMKB-0.66/3030050.55156357226×16
LMKB-0.66/4025050.52.51664385Ø22 40×10
LMKB-0.66/4030050.52.51664385Ø22 40×10
LMKB-0.66/4040050.52.51664385Ø22 40×10
LMKB-0.66/4050050.52.51664385Ø22 40×10
LMKB-0.66/4060050.52.51664385Ø22 40×10
LMKB-0.66/6050050.551854599Ø46 60×21
LMKB-0.66/6060050.551854599Ø46 60×21
LMKB-0.66/6075050.551854599Ø46 60×21
LMKB-0.66/6080050.551854599Ø46 60×21
LMKB-0.66/60100050.551854599Ø46 60×21
LMKB-0.66/80100050.510110651127Ø50 81×31
LMKB-0.66/80120050.510110651127Ø50 81×31
LMKB-0.66/80150050.510110651127Ø50 81×31
LMKB-0.66/80200050.510110651127Ø50 81×31
LMKB-0.66/100100050.510112751136Ø60 102×31
LMKB-0.66/100120050.510112751136Ø60 102×31
LMKB-0.66/100150050.510112751136Ø60 102×31
LMKB-0.66/100200050.510112751136Ø60 102×31
LMKB-0.66/100250050.510112751136Ø60 102×31
LMKB-0.66/100300050.510112751136Ø60 102×31
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LMK8-0.66 — click image to zoom / view original.

Product Overview

About This Product

LMK8-0.66

This indoor low-voltage current transformer is built to the IEC 61869 and GB/T 20840 standard family, and that framework defines how its 0.66kV primary circuit is specified, tested and documented for metering and control duty. The unit uses dry epoxy resin insulation applied by vacuum casting or automatic pressure gelation, producing a solid, void-free body that encapsulates the winding and core.

Accuracy classes 0.2, 0.5 and 1.0 are available, with a rated burden of 2.5VA and a 5A or 1A secondary at 50/60Hz; the class chosen governs how tightly ratio and phase error are held across the load range. It sits in the low-voltage bury-plug segment, where the absence of a primary fuse keeps the wiring compact, so fuse-based protection must be provided elsewhere in the scheme. Compliance evidence is available [On Request]. Typical deployment is inside indoor switchgear, ring-main units and central cubicles.

Terminal naming follows the nameplate diagram, with the secondary earthed at one point; never open-circuit the secondary while energized. The indoor enclosure is not for outdoor exposure. Custom ratios and secondary winding configurations are available, with documentation packages and delivery terms quoted on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs