Indoor low voltage current transformer, 0.66kV rated, epoxy resin casting type, for current measurement and protection in low voltage distribution systems. Complies with IEC 61869 and GB/T 20840 standards. Wide range of current ratios available, multiple accuracy classes 0.2, 0.5, 1.0. Compact size, easy installation, suitable for switchgear and panel mounting. Customizable ratios and specifications.
Indoor LV CT for 0.66kV systems, suitable for metering and protection in switchgear and panels. Confirm ratio and accuracy class per application.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869 / GB/T 20840 |
| Model Code | LMZ1-2-3-0.66 | Factory nameplate marking |
| Primary Voltage | 0.66kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | 0.2/0.5/1.0 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869 / GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
connect primary in series with the line. Secondary terminals are 1S1 and 1S2 (protection winding if present: 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 / IEEE C57.13 terminal conventions.
Compliant with: IEC 61869 / GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the maximum system voltage for this CT?
A: Rated for 0.66kV systems.
Q: What accuracy classes are available?
A: 0.2, 0.5, and 1.0.
Q: Can it be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current (A) | 0.2 class | 0.5 class | 1 class | Primary Turns through core |
|---|---|---|---|---|---|
| LMZ(1,2,3)-0.66 | 100 | - | - | 5 | 1 |
| LMZ(1,2,3)-0.66 | 200-400 | 5 | 5 | 7.5 | 1 |
| LMZ(1,2,3)-0.66 | 500-800 | 10 | 10 | 15 | 1 |
| LMZ(1,2,3)-0.66 | 1000-1500 | 15 | 15 | 20 | 1 |
| LMZ(1,2,3)-0.66 | 2000-3000 | 20 | 20 | 25 | 1 |
Dimension & outline drawing of LMZ1-2-3-0.66 — click image to zoom / view original.
This is an indoor low-voltage current transformer for 0.66kV switchgear and distribution compartments, stepping primary current down to a 5A or 1A secondary for metering and protection. Its dry epoxy resin insulation and compact moulded body suit panel mounting where space is tight.
Accuracy classes 0.2, 0.5 and 1.0 are available, with rated outputs of 5VA to 25VA depending on the primary current range; for example the 2000–3000A range carries 20VA at class 0.2 and 25VA at class 1.0, with a single primary through-turn. Each unit is routine-tested for ratio and polarity before dispatch, and type and routine test reports to IEC 61869 and GB/T 20840 are available [On Request].
Typical deployment is in heavy-industry distribution — metallurgy, mining, cement and chemical plants — indoors only. Observe P1/P2 orientation, earth the secondary at one point, and never open-circuit the secondary while energized. For OEM branding, custom ratios and document packages, contact the factory.
Same product family, different ratings — compare before you specify.
State Grid Standard 0.66kV Current Transformer
Indoor epoxy cast LV current transformer, State Grid standard, primary rated current 75A, accuracy 0.2S/0.5S, for metering in low-voltage distribution systems.
State Grid Standard 0.66kV Current Transformer
Indoor epoxy cast low-voltage current transformer of State Grid standard, primary rated current 100-150A, accuracy class 0.2S/0.5S, applied for metering in low-voltage power distribution systems.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2070 I is an indoor epoxy resin casting current transformer designed for CGIS gas-insulated switchgear at 35kV. It is available with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20 and 10P20. The epoxy casting has an outer diameter of Ø205mm and a through (inner) diameter of Ø70mm for busbar installation, and is rated for 50/60Hz operation. Metering classes (0.2FS10, 0.5SFS10) and protection classes (5P10, 10P10, 5P20, 10P20) cover both measurement and relay protection inside CGIS panels.