Indoor epoxy cast low-voltage current transformer of State Grid standard, primary rated current 100-150A, accuracy class 0.2S/0.5S, applied for metering in low-voltage power distribution systems.
LMZ1D-SKX2 is a 0.66kV indoor current transformer for low-voltage metering, offering 0.2S/0.5S accuracy. Suitable for State Grid standard distribution panels.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZ1D-SKX2 | Factory nameplate marking |
| Primary Voltage | 0.66kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A | Ratio check at rated frequency |
| Accuracy Class | 0.2S/0.5S | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 5VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the window; secondary terminals are 1S1 and 1S2 for metering. Never open-circuit the secondary while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 and IEEE C57.13 conventions.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary current range?
A: 100-150A.
Q: What accuracy classes are available?
A: 0.2S and 0.5S.
Q: Is it suitable for outdoor use?
A: No, it is designed for indoor applications.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current (A) | Rated output (VA) 0.2 class | Rated output (VA) 0.5 class | Primary turns |
|---|---|---|---|---|
| LMZ1D-SKX1 | 75 | 5 | 5 | 1 |
| LMZ2D-SKX2 | 100-150 | 5 | 5 | 1 |
| LMZ3D-SKX1 | 200-600 | 5 | 5 | 1 |
| LMZ4D-SKX1 | 600-800 | 5 | 10 | 1 |
| LMZ4D-SKX1 | 800-1500 | 5 | 10 | 1 |
Dimension & outline drawing of LMZ1D-SKX2 — click image to zoom / view original.
The LMZ1D-SKX2 is a dry epoxy resin cast current transformer for indoor service at a primary voltage of 0.66kV, converting primary current to a 5A secondary for metering and control in low-voltage distribution systems. Its solid cast insulation is produced by vacuum casting or automatic pressure gelation, giving a void-free body that supports the 0.66kV insulation level and the mechanical integrity expected in State Grid-standard installations.
With accuracy classes 0.2S/0.5S and a rated burden of 5VA at 50/60Hz, it serves revenue metering and precision measurement across a 100-150A primary range. The 0.2S/0.5S classes are suited to this metering duty; specifying a higher class than the application needs adds cost without benefit. The unit follows the State Grid standard, and type-test and routine-test documentation can be supplied [On Request].
Typical deployment is inside indoor medium-voltage switchgear, ring-main units and centrally installed cubicles. During commissioning, verify insulation resistance, polarity and ratio before energizing, earth the secondary at one point and follow the nameplate terminal diagram. Never open-circuit the secondary while the primary is energized. Ratio and accuracy customization, sample and type-test support, and delivery terms are available on request.
Same product family, different ratings — compare before you specify.
Indoor Low Voltage Current Transformer 0.66kV
Indoor low voltage current transformer, 0.66kV rated, epoxy resin casting type, for current measurement and protection in low voltage distribution systems. Complies with IEC 61869 and GB/T 20840 standards. Wide range of current ratios available, multiple accuracy classes 0.2, 0.5, 1.0. Compact size, easy installation, suitable for switchgear and panel mounting. Customizable ratios and specifications.
State Grid Standard 0.66kV Current Transformer
Indoor epoxy cast LV current transformer, State Grid standard, primary rated current 75A, accuracy 0.2S/0.5S, for metering in low-voltage distribution systems.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2070 I is an indoor epoxy resin casting current transformer designed for CGIS gas-insulated switchgear at 35kV. It is available with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20 and 10P20. The epoxy casting has an outer diameter of Ø205mm and a through (inner) diameter of Ø70mm for busbar installation, and is rated for 50/60Hz operation. Metering classes (0.2FS10, 0.5SFS10) and protection classes (5P10, 10P10, 5P20, 10P20) cover both measurement and relay protection inside CGIS panels.