Indoor epoxy cast LV current transformer, State Grid standard, primary rated current 600-800A, accuracy 0.2S/0.5S.
LMZ3D-SKX1 is a 0.66kV indoor current transformer with 600-800A primary and 0.2S/0.5S accuracy, ideal for low-voltage metering and protection in State Grid compliant panels.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZ3D-SKX1 | Factory nameplate marking |
| Primary Voltage | 0.66kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A | Ratio check at rated frequency |
| Accuracy Class | 0.2S/0.5S | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 10VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the window; secondary terminals are 1S1 and 1S2 for the main winding. If a second core is present, use 2S1-2S2. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point only. Ensure the secondary burden does not exceed 10VA to maintain accuracy.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary current range of LMZ3D-SKX1?
A: The primary current range is 600-800A.
Q: What accuracy classes are available?
A: Accuracy classes are 0.2S and 0.5S.
Q: Can it be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current (A) | Rated output (VA) 0.2 class | Rated output (VA) 0.5 class | Primary turns |
|---|---|---|---|---|
| LMZ1D-SKX1 | 75 | 5 | 5 | 1 |
| LMZ1D-SKX2 | 100-150 | 5 | 5 | 1 |
| LMZ2D-SKX1 | 200-600 | 5 | 5 | 1 |
| LMZ3D-SKX1 | 600-800 | 5 | 10 | 1 |
| LMZ4D-SKX1 | 800-1500 | 5 | 10 | 1 |
Dimension & outline drawing of LMZ3D-SKX1 — click image to zoom / view original.
This is a 0.66kV indoor current transformer, designed to step 600-800A primary current down to a 5A secondary for metering and protection in switchgear bays and substations. The LMZ3D-SKX1 uses dry epoxy resin insulation, with a single-turn primary winding (one primary turn) and a secondary winding that feeds measurement and protection circuits at 50/60Hz.
Accuracy is 0.2S or 0.5S, with rated output of 5VA at class 0.2 and 10VA at class 0.5. Routine factory checks include ratio and polarity verification, and the unit is built to the State Grid standard. Compared with oil-immersed or SF6 designs, the dry epoxy construction avoids liquid or gas handling, which simplifies indoor installation and maintenance. Compliance follows the IEC 61869 series, and test reports and documentation are available [On Request].
Typical deployment is in heavy-industry distribution — metallurgy, mining, cement and chemical plants — inside indoor cabinets. Earth the secondary at one point and bond it equipotentially; never open-circuit the secondary while energized. It is not intended for DC or non-standard frequencies. Custom ratios and accuracy classes, export packing and after-sales support are available on request.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LMZ3-10 Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.